nut/docs/man/mge-shut.8

138 lines
4.3 KiB
Groff
Raw Normal View History

2011-01-26 09:35:08 +00:00
'\" t
.\" Title: mge-shut
.\" Author: [see the "AUTHOR" section]
2015-04-30 13:53:36 +00:00
.\" Generator: DocBook XSL Stylesheets v1.78.1 <http://docbook.sf.net/>
2016-07-18 00:11:41 +00:00
.\" Date: 12/29/2015
2011-01-26 09:35:08 +00:00
.\" Manual: NUT Manual
2016-07-18 00:11:41 +00:00
.\" Source: Network UPS Tools 2.7.3.1
2011-01-26 09:35:08 +00:00
.\" Language: English
.\"
2016-07-18 00:11:41 +00:00
.TH "MGE\-SHUT" "8" "12/29/2015" "Network UPS Tools 2\&.7\&.3\&." "NUT Manual"
2011-01-26 09:35:08 +00:00
.\" -----------------------------------------------------------------
.\" * Define some portability stuff
.\" -----------------------------------------------------------------
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.\" http://bugs.debian.org/507673
.\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.ie \n(.g .ds Aq \(aq
.el .ds Aq '
.\" -----------------------------------------------------------------
.\" * set default formatting
.\" -----------------------------------------------------------------
.\" disable hyphenation
.nh
.\" disable justification (adjust text to left margin only)
.ad l
.\" -----------------------------------------------------------------
.\" * MAIN CONTENT STARTS HERE *
.\" -----------------------------------------------------------------
.SH "NAME"
mge-shut \- Driver for SHUT Protocol UPS equipment
.SH "SYNOPSIS"
.sp
\fBmge\-shut\fR \-h
.sp
\fBmge\-shut\fR \-a \fIUPS_NAME\fR [\fIOPTIONS\fR]
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBNote\fR
.ps -1
.br
.sp
This man page only documents the hardware\-specific features of the mge\-shut driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.sp .5v
.RE
.SH "SUPPORTED HARDWARE"
.sp
mge\-shut supports all recent Eaton, MGE and Dell UPS models which use the SHUT (Serial HID UPS Transfer) protocol\&.
.sp
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U\-Talk protocol and should use the mge\-utalk driver\&.
.SH "EXTRA ARGUMENTS"
.sp
This driver also supports the following optional settings:
.PP
\fBlowbatt\fR=\fInum\fR
.RS 4
Set the low battery warning threshold at which shutdown is initiated by
\fBupsmon\fR(8)\&.
.sp
The factory default value is 30 (in percent), and can be settable depending on the exact model\&.
.RE
.PP
\fBoffdelay\fR=\fInum\fR
.RS 4
Set the timer before the UPS is turned off after the kill power command is sent (via the
\fB\-k\fR
switch)\&.
.sp
The default value is 20 (in seconds)\&. Usually this
\fBmust be lower\fR
than
\fIondelay\fR, but the driver will
\fBnot\fR
warn you upon startup if it isn\(cqt\&.
.RE
.PP
\fBondelay\fR=\fInum\fR
.RS 4
Set the timer for the UPS to switch on in case the power returns after the kill power command had been sent but before the actual switch off\&. This ensures the machines connected to the UPS are, in all cases, rebooted after a power failure\&.
.sp
The default value is 30 (in seconds)\&. Usually this
\fBmust be greater\fR
than offdelay, but the driver will
\fBnot\fR
warn you upon startup if it isn\(cqt\&. Some UPS\(cqes will restart no matter what, even if the power is (still) out at the moment this timer elapses\&. In that case, you could try if setting
\fIondelay = \-1\fR
in
\fBups\&.conf\fR
helps\&.
2012-08-12 21:39:31 +00:00
.if n \{\
.sp
.\}
.RS 4
.it 1 an-trap
.nr an-no-space-flag 1
.nr an-break-flag 1
.br
.ps +1
\fBWarning\fR
.ps -1
.br
ondelay parameter was set in ten seconds unit in the legacy mge\-shut driver ( 3 for 30 seconds) \&. It is now set in seconds ( 30 for 30 seconds)\&. Make sure you use the correct unit in your configuration\&.
.sp .5v
.RE
2011-01-26 09:35:08 +00:00
.RE
.PP
\fBnotification\fR=\fInum\fR
.RS 4
Set notification type to 1 (no), 2 (light) or 3 (yes)\&.
.sp
2012-08-12 21:39:31 +00:00
This argument is ignored\&. It is only here for backward compatibility\&.
2011-01-26 09:35:08 +00:00
.RE
.SH "KNOWN ISSUES"
.SS "Repetitive timeout and staleness"
.sp
Some models tends to be unresponsive with the default polling frequency\&. The result is that you have some "data stale" errors in your system log\&.
.sp
In this case, simply modify the general parameter "pollinterval" to a higher value (like 10 for 10 seconds)\&. This should solve the issue\&.
.sp
Using \fInotification=3\fR might also help\&.