mge-shut \- Driver for SHUT Protocol UPS equipment
.SH"SYNOPSIS"
.sp
\fBmge\-shut\fR\-h
.sp
\fBmge\-shut\fR\-a \fIUPS_NAME\fR [\fIOPTIONS\fR]
.ifn\{\
.sp
.\}
.RS4
.it1an-trap
.nran-no-space-flag1
.nran-break-flag1
.br
.ps+1
\fBNote\fR
.ps-1
.br
.sp
This man page only documents the hardware\-specific features of the mge\-shut driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.sp.5v
.RE
.SH"SUPPORTED HARDWARE"
.sp
mge\-shut supports all recent Eaton, MGE and Dell UPS models which use the SHUT (Serial HID UPS Transfer) protocol\&.
.sp
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U\-Talk protocol and should use the mge\-utalk driver\&.
.SH"EXTRA ARGUMENTS"
.sp
This driver also supports the following optional settings:
.PP
\fBlowbatt\fR=\fInum\fR
.RS4
Set the low battery warning threshold at which shutdown is initiated by
\fBupsmon\fR(8)\&.
.sp
The factory default value is 30 (in percent), and can be settable depending on the exact model\&.
.RE
.PP
\fBoffdelay\fR=\fInum\fR
.RS4
Set the timer before the UPS is turned off after the kill power command is sent (via the
\fB\-k\fR
switch)\&.
.sp
The default value is 20 (in seconds)\&. Usually this
\fBmust be lower\fR
than
\fIondelay\fR, but the driver will
\fBnot\fR
warn you upon startup if it isn\(cqt\&.
.RE
.PP
\fBondelay\fR=\fInum\fR
.RS4
Set the timer for the UPS to switch on in case the power returns after the kill power command had been sent but before the actual switch off\&. This ensures the machines connected to the UPS are, in all cases, rebooted after a power failure\&.
.sp
The default value is 30 (in seconds)\&. Usually this
\fBmust be greater\fR
than offdelay, but the driver will
\fBnot\fR
warn you upon startup if it isn\(cqt\&. Some UPS\(cqes will restart no matter what, even if the power is (still) out at the moment this timer elapses\&. In that case, you could try if setting
ondelay parameter was set in ten seconds unit in the legacy mge\-shut driver ( 3 for 30 seconds) \&. It is now set in seconds ( 30 for 30 seconds)\&. Make sure you use the correct unit in your configuration\&.