nut/docs/man/apcsmart.txt
2015-04-30 15:53:36 +02:00

385 lines
14 KiB
Text

APCSMART(8)
===========
NAME
----
apcsmart - Driver for American Power Conversion Smart Protocol UPS equipment
SYNOPSIS
--------
*apcsmart* -h
*apcsmart* -a 'UPS_NAME' [-x option=value ...]
NOTE: This man page only documents the hardware-specific features of the
apcsmart driver. For information about the core driver, see
linkman:nutupsdrv[8].
SUPPORTED HARDWARE
------------------
The apcsmart driver should recognize (or at the very least, work with) the
majority of Smart-UPS models - which includes Smart-UPS, Matrix-UPS and Back-UPS
lineups, among few other ones.
Currently, we can roughly divide APC hardware into four groups (note that the
division isn't strict by any means, and the borders between those are pretty fuzzy):
[very] "old" models::
These models usually have old APC logo, white color and _no_ programmable
EEPROM; you won't find them listed anywhere on APC's site either. The support
for those will be usually based on driver's compatibility tables, or if the
model (firmware) is not listed in those - the driver will try to follow the very
basic subset of features, while still trying to remain useful. Despite
"smart" tagname, they often tend to behave in pretty dumb way (see the
section below about shutdown behaviour).
+
--
.Example models:
* Smart-UPS 2000I
* Smart-UPS 900I
--
"new" models::
These models usually come from late 1990s / pre-2009 times. They are often
referred as "3rd. gen". For the most part, they have programmable EEPROM,
report supported commands and capabilites, and should work just fine with the
apcsmart driver.
"microlink" models::
WARNING: these are not _natively_ supported by *apcsmart* (or *apcupsd*,
for that matter, if you're wondering). Around 2007, APC (now APC Schneider)
decided to go back to its proprietry roots, and all the new models (SMT,
SMX, SURTD) use completely different protocol and cables. If you purchased
a new APC UPS - that uses cable with RJ45 on the one end, and DB-9 on the
other - then you have such model. Your only option to support it through
*NUT* is to purchase a "legacy communications card" - part #AP9620 (google
\'AP9620' for more details). Or if that's not an option, rely on official
software.
Microsol models::
Several Microsol serial models sold in Brazil have been rebranded as APC
Back-UPS, and the model numbers tend to start with "BZ". If you have one
of these "Nobreaks", they will not work with the *apcsmart* driver - please
see the linkman:solis[8] driver instead.
+
--
.Example models:
* Back-UPS BZ1200-BR
* Back-UPS BZ2200BI-BR
--
Another thing to remember is that Smart protocol is not USB protocol. If you
have UPS with both USB and serial ports, then depending on how you connect it,
you will need either apcsmart or usbhid-ups driver.
CABLING
-------
This driver expects to see a 940-0024C cable or a clone by default. You
can switch to the 940-0095B dual-mode cable support with the \'cable='
definition described below.
If your 940-xx24X cable is broken or missing, use this diagram to build
a clone:
http://www.networkupstools.org/cables.html#_940_0024c_clone
NOTE: The "xx" is either "00" for a short cable, or the number of feet
of a longer cable. The "X" is a letter representing the minor revision
of the physical cable and its connectors ("C" and "E" are commonly found
revisions). All minor revisions should use the same pin-outs and
wiring.
You can specify alternate cable in linkman:ups.conf[5]:
*cable*=940-0095B
Alternatively, you can also provide it on the command line using:
-x *cable*=940-0095B
TTY MODES
---------
By default the driver works in canonical mode, but it proved to be a problem in
Windows systems. Furthermore there's a possibility of some obscure serial cards
or serial-USB converters that could cause problems as well. You can use
\'ttymode=' option to force non-canonical discipline in linkman:ups.conf[5]:
*ttymode*=raw
Alternatively, you can also provide it on the command line using:
-x *ttymode*=raw
NOTE: Any other value will make the driver work in the canonical mode.
EXPLANATION OF SHUTDOWN METHODS SUPPORTED BY APC UPSES
------------------------------------------------------
APC hardware supports a lot of shutdown methods, that themselves can differ in
behaviour quite a bit, depending on the model.
*S* (soft hibernate)::
This is most basic command present in probably all APC models. It will
hibernate the UPS, and subsequently wake it up when the mains supply
returns. *The command doesn't work if the UPS is running on mains.*
"old" models:::
The behaviour here is unfortunately pretty primitive - when the power
returns, the UPS just wakes up. No grace periods, no min. battery
charge condition, etc. This is probably not what you want.
"new" models:::
The behaviour here is as expected - the power is cut off after the
EEPROM defined grace period. The UPS will wake up when the power
returns, after the EEPROM defined delay AND if the EEPROM defined min.
battery charge level is met. The delay is counted from the power\'s
return.
*CS* (aka "force OB hack")::
This is a trick to make UPS power down even if it\'s running on mains.
Immediately before issuing *S*, "simulate power failure" is issued. The
remaining behaviour is as in *S* case.
+
The name came from APC CS models, where such trick was used to power down
UPSes in consistent fashion using only *S*. It\'s better to use *@nnn*
command if your UPS supports it (and is not too old, see below).
*@nnn* (hard hibernate)::
This is basic command used to hibernate UPS regardless if it\'s
running on batteries or on mains. The option takes 3 digits argument which
can be used to specify additional wakeup delay (in 6 minute units).
+
--
"old" models:::
The behaviour is - unfortunately - similary primitive to *S*. The UPS
unconditionally wakes up after $$nnn*6$$ minutes - *it doesn\'t care if the
power returned !* If nnn = 000, then UPS will do precisely nothing. On
those models you\'re better specifying nnn > 0, if you can estimate
the kind of power problems that might be happening in your environment.
Another thing to consider with "old" models - you might lose the
connection with the UPS, until it wakes up (with *S*, the serial
connection is kept alive).
"new" models:::
All the usual variables defined in EEPROM are respected (see *S*).
Additionally, if nnn > 0, the $$nnn*6$$ minutes are added to EEPROM
defined delay. UPS will not power up if it\'s running on batteries,
contrary to what "old" models used to do - the combined delay is counted
from the moment of power return.
--
+
Supposedly there exist models that take 2 digits instead of 3. Just in case,
NUT also supports such variation. You have to provide exactly 2 digits to
trigger it (*awd* option, or argument to one of the supported instant commands).
*K* (delayed poweroff)::
This is permanent poweroff - the UPS will not wake up automatically. On
newer units, it will respect applicable EEPROM variables.
*Z* (instant poweroff)::
This is also permanent poweroff - the UPS will not wake up automatically.
The poweroff is executed immediately.
SHUTDOWN CONTROL BY NUT
-----------------------
There are three options used to control the shutdown behaviour.
*sdtype*=[0-5]::
This option takes a single digit (0-5) as an argument. See below for
details.
*advorder*=no|[0-4]+::
This option takes string of digits as an argument. Methods listed are tried
in turn until one of them succeedes. Note that the meaning of digits is
different from *sdtype*. See below for details.
*awd*=[0-9]{1,3}::
This option lets you specify additional wakeup delay used by *@*. If you
provide exactly 2 digits, the driver will try 2 digits variation (see
previous section for more info). Otherwise standard 3 digits variation is
used. *Note: the time unit is 6 minutes !*
Keep in mind that *sdtype* and *advorder* are mutually exclusive. If *advorder*
is provided, *sdtype* is ignored. If *advorder* is set to \'no', *sdtype* is
used instead.
If nothing is provided, *NUT* will assume *sdtype*=0 - which is generally fine
for anything not too ancient or not too quirky.
SDTYPE
~~~~~~
The values permitted are from 0 to 5. Only one can be specified. Anything else
will cause apcsmart to exit.
0::
issue soft hibernate (*S*) if the UPS is running on batteries, otherwise issue
hard hibernate (*@*)
1::
issue soft hibernate (*S*) (if on batteries), and if it fails (or on mains) -
try hard hibernate (*@*)
2::
issue instant poweroff (*Z*)
3::
issue delayed poweroff (*K*)
4::
issue "force OB hack" (*CS*)
5::
issue hard hibernate (*@*)
NOTE: Hard hibernate\'s additional wakeup delay can be provided by *awd*.
ADVORDER
~~~~~~~~
The argument is either a word \'no', or a string of 1 - 5 digits in [0 - 4]
range. Each digit maps to the one of shutdown methods supported by APC UPSes.
Methods listed in this way are tried in order, until one of them succedes.
If *advorder* is undefined or set to \'no', *sdtype* is used instead.
The mapping is as follows:
[horizontal]
0:: soft hibernate (*S*)
1:: hard hibernate (*@*)
2:: delayed poweroff (*K*)
3:: instant poweroff (*Z*)
4:: "force OB hack" (*CS*)
NOTE: Hard hibernate\'s additional wakeup delay can be provided by *awd*.
IGNORING LB STATE
-----------------
APC units - even if they report LB mode - will not go into shutdown
automatically. This gives us even more control with reference to "when to
actually shutdown PSU". Since version 2.6.2, NUT supports *ignorelb* option in
driver's section of linkman:ups.conf[5]. When such option is in effect,
the core driver will ignore LB state as reported by specific driver and
start shutdown basing the decision _only_ on two conditions:
battery.charge < battery.charge.low
*OR*
battery.runtime < battery.runtime.low
Of course - if any of the variables are not available, the appropriate condition
is not checked. If you want to explicitly disable one of the conditions, simply
override the right hand variable causing the condition to always evaluate to
false (you can even provide negative numbers).
APC UPSes don't have battery.charge.low - you will have to define it if you want
to use such condition (prefix the variable with `override.` or `default.`).
"New" units have battery.runtime.low, but depending on battery quality, firmware
version, calibration and UPS load - this variable can be underestimated quite a bit -
especially right after going into OB state. This in turn can cause LB to be
asserted, which under normal conditions will cause *NUT* to initiate the
shutdown. You might want to disable this condition entirely, when relying on
*ignorelb* option (this was actually the main motivation behind introduction of
such feature).
Simple example:
[source,conf]
----
[apc]
ignorelb
override.battery.charge.low = 15
override.battery.runtime.low = -1
----
This would cause apcsmart to go into shutdown _only_ if detected battery charge
< 15%. Runtime condition is always false in this example.
You could ask - why bother ? Well, the reason is already hinted above. APC units
can be very picky about the batteries, and their firmware can underestimate the
remaining runtime (especially right after going into OB state). *ignorelb*
option and *$$override.*$$* let you remain in control of the UPS, not UPS in control
of you.
Furthermore, this allows to specify conditions similary to how it's done in
apcupsd daemon, so it should be welcome by people used to that software.
SUPPORTED INSTANT COMMANDS
--------------------------
The apcsmart driver exposes following instant commands:
shutdown.return::
executes soft hibernate
shutdown.return cs::
executes "force OB hack"
shutdown.return at:<nbr>::
executes "hard hibernate" with $$<nbr>*6$$ minutes additional wakeup delay (<nbr> format
is the same as of *awd* option)
shutdown.stayoff::
executes "delayed poweroff"
load.off::
executes "instant poweroff"
All the above commands must be issued 2nd time to have any effect (no less than 3
seconds, and no more than 15 seconds after the initial call). Those commands are
mostly useful for manual testing, when your machine is not powered by the UPS
you\'re testing.
Other supported commands:
- load.on
- test.panel.start
- test.failure.start
- test.battery.start
- test.battery.stop
- bypass.start
- bypass.stop
- calibrate.start
- calibrate.stop
PREVIOUS DRIVER VERSION
-----------------------
Previous driver is still available as *apcsmart-old*, should there be any need to
use earlier version (bugs, incompatiblities with new functionality, etc.). In
due time, *apcsmart-old* will be phased out completely, but this won't happen until
the new version gets solid exposure with no pending issues.
BUGS
----
Some older APC UPS models return bogus data in the status register during
a front panel test. This is usually detected and discarded, but some
other unexpected values have occasionally slipped through.
APC UPS models with both USB and serial ports require a power cycle when
switching from USB communication to serial, and perhaps vice versa.
AUTHOR
------
Nigel Metheringham <Nigel.Metheringham@Intechnology.co.uk> (drawing
heavily on the original apcsmart driver by Russell Kroll). This driver
was called newapc for a time and was renamed in the 1.5 series. In 2.6.2
it was renamed to apcsmart-old, being superseded by updated version with
new features, which is maintained by Michal Soltys <soltys@ziu.info>
SEE ALSO
--------
linkman:nutupsdrv[8], linkman:ups.conf[5], linkman:usbhid-ups[8],
linkman:solis[8]
Internet resources:
~~~~~~~~~~~~~~~~~~~
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
// vim: tw=80 ai si ts=8 sts=4 sw=4 et :