snmp-ups(8)
|
|
===========
|
|
|
|
NAME
|
|
----
|
|
|
|
snmp-ups - Multi-MIB Driver for SNMP UPS equipment
|
|
|
|
NOTE
|
|
----
|
|
|
|
This man page only documents the hardware-specific features of the
|
|
snmp-ups driver. For information about the core driver, see
|
|
linkman:nutupsdrv[8].
|
|
|
|
SUPPORTED HARDWARE
|
|
------------------
|
|
|
|
The snmp-ups driver automatically detects and supports a wide range of
|
|
devices by loading various MIBS, such as:
|
|
|
|
*ietf*::
|
|
UPS that is RFC 1628 (UPS MIB) compliant, e.g. MGE UPS SYSTEMS, Liebert,
|
|
perhaps others (default)
|
|
|
|
*mge*::
|
|
MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards
|
|
(ref 66062, 66045, 66074 and 66244)
|
|
|
|
*apcc*::
|
|
APC AP9605, AP9606, AP9617, and AP9618 APC network management cards,
|
|
as well as any others supporting the APC POWERNET MIB
|
|
|
|
*netvision*::
|
|
Socomec Sicon UPS with Netvision Web/SNMP management card/external box
|
|
|
|
*pw*::
|
|
Powerware devices with ConnectUPS SNMP cards
|
|
|
|
*pxgx_ups*::
|
|
Eaton devices with Power Xpert Gateway UPS Card
|
|
|
|
*aphel_genesisII*::
|
|
Eaton Powerware ePDU Monitored
|
|
|
|
*aphel_revelation*::
|
|
Eaton Powerware ePDU Managed
|
|
|
|
*raritan*::
|
|
Various Raritan PDUs (Dominion PX, PM, RPC)
|
|
|
|
*raritan-px2*::
|
|
Various Raritan PDUs (Dominion PX2)
|
|
|
|
*baytech*::
|
|
Various BayTech PDUs
|
|
|
|
*cpqpower*::
|
|
HP/Compaq AF401A management card, perhaps others
|
|
|
|
*cyberpower*::
|
|
Cyberpower RMCARD201. Should also support RMCARD100 (net version),
|
|
RMCARD202 and RMCARD301
|
|
|
|
*huawei*::
|
|
Huawei UPS5000-E, perhaps others
|
|
|
|
*tripplite*::
|
|
TrippLite UPSes; at this time this is the IETF MIB mapping with just
|
|
the Tripplite entry point OID to verify the device vendor, and a real
|
|
hardware-specific configuration will be added in the future development.
|
|
|
|
For a complete and up-to-date listing, you can query the driver by passing
|
|
the *mibs=--list* argument (see below).
|
|
|
|
EXTRA ARGUMENTS
|
|
---------------
|
|
|
|
This driver supports the following optional settings in the
|
|
linkman:ups.conf[5]:
|
|
|
|
*port*='hostname[:port]'::
|
|
Set SNMP hostname, or IP address, and port number of the peer SNMP agent.
|
|
There is no default for the hostname, but the default port is 161.
|
|
|
|
*mibs*='--list'::
|
|
A special option which allows to list the currently known MIB-to-NUT mappings
|
|
and exit the driver binary, intended for command-line usage like this:
|
|
----
|
|
$ snmp-ups -a snmp-test -x mibs=--list
|
|
----
|
|
|
|
*mibs*='name'::
|
|
Set MIB compliance (default=auto, allowed entries: refer to SUPPORTED
|
|
HARDWARE above).
|
|
+
|
|
With "auto", the driver will try a select set of SNMP objects until it finds
|
|
one that the device responds to.
|
|
+
|
|
Note that since NUT 2.6.2, snmp-ups has a new method that uses sysObjectID
|
|
(which is a pointer to the preferred MIB of the device) to detect supported
|
|
devices. This renders void the *requirement* to use the "mibs" option.
|
|
|
|
*community*='name'::
|
|
Set community name (default = public).
|
|
Note that a RW community name is required to change UPS settings and
|
|
send commands (as for a powerdown).
|
|
|
|
*snmp_version*='version'::
|
|
Set SNMP version (default = v1, allowed: v2c, v3)
|
|
|
|
*snmp_retries*='retries'::
|
|
Specifies the number of Net-SNMP retries to be used in the requests (default=5)
|
|
|
|
*snmp_timeout*='timeout'::
|
|
Specifies the Net-SNMP timeout in seconds between retries (default=1)
|
|
|
|
*symmetrathreephase*::
|
|
Enable APCC three phase Symmetra quirks (use on APCC three phase Symmetras):
|
|
Convert from three phase line-to-line voltage to line-to-neutral voltage
|
|
(default: not enabled)
|
|
|
|
*pollfreq*='num'::
|
|
Set polling interval for full updates, in seconds, to reduce SNMP network
|
|
traffic relative to the quick updates performed every "pollinterval" (the
|
|
latter option is described in linkman:ups.conf[5]).
|
|
The default value is 30 (in seconds).
|
|
|
|
*notransferoids*::
|
|
Disable the monitoring of the low and high voltage transfer OIDs in
|
|
the hardware. This will remove input.transfer.low and input.transfer.high
|
|
from the list of variables. This should only be used on APCC Symmetra
|
|
equipment which has strangeness in the three-phase power reporting.
|
|
|
|
*secLevel*='value'::
|
|
Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv,
|
|
allowed: authNoPriv,authPriv)
|
|
|
|
*secName*='value'::
|
|
Set the securityName used for authenticated SNMPv3 messages (no default)
|
|
|
|
*authPassword*='value'::
|
|
Set the authentication pass phrase used for authenticated SNMPv3 messages
|
|
(no default)
|
|
|
|
*privPassword*='value'::
|
|
Set the privacy pass phrase used for encrypted SNMPv3 messages (no default)
|
|
|
|
*authProtocol*='value'::
|
|
Set the authentication protocol (MD5, SHA, SHA256, SHA384 or SHA512) used for
|
|
authenticated SNMPv3 messages (default=MD5). Note that the exact protocol list
|
|
depends on Net-SNMP library capabilities; check help of the `snmp-ups` binary
|
|
program for the run-time supported list.
|
|
|
|
*privProtocol*='value'::
|
|
Set the privacy protocol (DES, AES, AES192 or AES256) used for encrypted SNMPv3
|
|
messages (default=DES). Note that the exact protocol list depends on Net-SNMP
|
|
library capabilities; check help of the `snmp-ups` binary program for the
|
|
run-time supported list.
|
|
|
|
REQUIREMENTS
|
|
------------
|
|
|
|
You will need to install the Net-SNMP package from
|
|
http://www.net-snmp.org/ before building this driver.
|
|
|
|
SNMP v3 also requires OpenSSL support from http://www.openssl.org.
|
|
|
|
LIMITATIONS
|
|
-----------
|
|
|
|
Shutdown
|
|
~~~~~~~~
|
|
|
|
The shutdown sequence should be tested before relying on NUT to send a
|
|
shutdown command to the UPS. The problem is that the host network stack may
|
|
have been torn down by the time the driver is invoked to send the shutdown
|
|
command. The driver attempts to send +shutdown.return+, +shutdown.reboot+,
|
|
and +load.off.delay+ commands to the UPS in sequence, stopping after the first
|
|
supported command.
|
|
|
|
INSTALLATION
|
|
------------
|
|
|
|
This driver is only built if the Net-SNMP development files are present at
|
|
configuration time. You can also force it to be built by using
|
|
+configure --with-snmp=yes+ before calling make.
|
|
|
|
EXAMPLES
|
|
--------
|
|
|
|
The hostname of the UPS is specified with the "port" value in
|
|
`ups.conf`, and may include a non-standard (161) remote peer port:
|
|
|
|
------
|
|
[snmpv1]
|
|
driver = snmp-ups
|
|
port = snmp-ups.example.com
|
|
community = public
|
|
snmp_version = v1
|
|
pollfreq = 15
|
|
desc = "Example SNMP v1 device"
|
|
|
|
[snmpv3]
|
|
driver = snmp-ups
|
|
port = 166.99.224.132:170
|
|
snmp_version = v3
|
|
secLevel = authPriv
|
|
secName = mysecurityname
|
|
authPassword = myauthenticationpassphrase
|
|
privPassword = myprivatepassphrase
|
|
desc = "Example SNMP v3 device, with the highest security level"
|
|
------
|
|
|
|
AUTHORS
|
|
-------
|
|
|
|
* Arnaud Quette
|
|
* Dmitry Frolov
|
|
* Jim Klimov
|
|
|
|
SEE ALSO
|
|
--------
|
|
|
|
The core driver:
|
|
~~~~~~~~~~~~~~~~
|
|
|
|
linkman:nutupsdrv[8]
|
|
|
|
NUT SNMP Protocols Library
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
Available at: http://www.networkupstools.org/ups-protocols.html#_snmp
|
|
|
|
Internet resources:
|
|
~~~~~~~~~~~~~~~~~~~
|
|
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|