|  Network UPS Tools Documentation
 | |
| =================================
 | |
| 
 | |
| :Info: Program support page: <http://www.networkupstools.org/>
 | |
| :Author: Arnaud Quette <aquette.dev@gmail.com> and others, see AUTHORS file.
 | |
| :Copyright: Released under the GNU GPL - see COPYING for details.
 | |
| 
 | |
| Mailing list details: http://alioth.debian.org/mail/?group_id=30602
 | |
| 
 | |
| .. contents::
 | |
| 
 | |
| ===========
 | |
| Description
 | |
| ===========
 | |
| 
 | |
| Network UPS Tools is a collection of programs which provide a common
 | |
| interface for monitoring and administering UPS and PDU hardware.  NUT comes in
 | |
| two flavors: the "classic" and the "HAL enabled" one.
 | |
| 
 | |
| The "classic" flavor
 | |
| --------------------
 | |
| 
 | |
| It is the standard installation that uses a layered approach to connect
 | |
| all of the NUT parts.
 | |
| 
 | |
| Drivers are provided for a wide assortment of equipment.  They
 | |
| understand the specific language of each device and map it back to a
 | |
| compatibility layer.  This means both an expensive "smart" protocol UPS
 | |
| and a simple "power strip" model can be handled transparently.
 | |
| 
 | |
| This information is cached by the network server ``upsd``, which then
 | |
| answers queries from the clients.  upsd contains a number of access
 | |
| control features to limit the abilities of the clients.  Only authorized
 | |
| hosts may monitor or control your hardware if you wish.  Since the
 | |
| notion of monitoring over the network is built into the software, you
 | |
| can hang many systems off one large UPS and they will all shut down
 | |
| together. You can also use NUT to power on, off or cycle your data centers
 | |
| nodes, individually or globally through PDUs outlets.
 | |
| 
 | |
| Clients such as upsmon check on the status of the hardware and do things
 | |
| when necessary.  The most important task is shutting down the operating
 | |
| system cleanly before the UPS runs out of power.  Other programs are
 | |
| also provided to log UPS status regularly, monitor status through your
 | |
| web browser, and more.
 | |
| 
 | |
| The "HAL enabled" flavor
 | |
| ------------------------
 | |
| 
 | |
| This one is intended for use:
 | |
| 
 | |
| - with supported USB UPS,
 | |
| - on HAL enabled systems (Linux, FreeBSD, Sun Solaris),
 | |
| - on HAL enabled desktops (Gnome and possibly KDE) 
 | |
| 
 | |
| Using this approach, you don't have to configure NUT files, nor to
 | |
| manually start components, nor to install a specific NUT client.
 | |
| 
 | |
| Upon plugging your USB UPS, the right driver will be automatically
 | |
| launched, and the according Power Manager GUI will pop up.
 | |
| 
 | |
| Note that this feature is still beta and incomplete. But it
 | |
| represents a major evolution, and a huge user experience improvement!
 | |
| 
 | |
| For more information, refer to INSTALL and docs/nut-hal.txt.
 | |
| 
 | |
| ==========
 | |
| Installing
 | |
| ==========
 | |
| 
 | |
| If you are installing these programs for the first time, go read the
 | |
| INSTALL file to find out how to do that.  This document contains more
 | |
| information on what all of this stuff does.
 | |
| 
 | |
| 
 | |
| =========
 | |
| Upgrading
 | |
| =========
 | |
| 
 | |
| When upgrading from an older version, always check the UPGRADING file to
 | |
| see what may have changed.  Compatibility issues and other changes will
 | |
| be listed there to ease the process.
 | |
| 
 | |
| 
 | |
| =============
 | |
| Documentation
 | |
| =============
 | |
| 
 | |
| This file gives an overview of the software.  You should read the man
 | |
| pages, included example configuration files, and auxiliary documentation
 | |
| for the parts that you intend to use.
 | |
| 
 | |
| 
 | |
| ===================
 | |
| Network Information
 | |
| ===================
 | |
| 
 | |
| These programs are designed to share information over the network.  In
 | |
| the examples below, ``localhost`` is used as the hostname.  This can also
 | |
| be an IP address or a fully qualified domain name.  You can specify a
 | |
| port number if your upsd process runs on another port.
 | |
| 
 | |
| In the case of the program ``upsc``, to view the variables on the UPS called
 | |
| sparky on the ``upsd`` server running on the local machine, you'd do this::
 | |
| 
 | |
| 	/usr/local/ups/bin/upsc sparky@localhost
 | |
| 
 | |
| The default port number is 3493.  You can change this with 
 | |
| "configure --with-port" at compile-time.  To make a client talk to upsd
 | |
| on a specific port, add it after the hostname with a colon, like this::
 | |
| 
 | |
| 	/usr/local/ups/bin/upsc sparky@localhost:1234
 | |
| 
 | |
| This is handy when you have a mixed environment and some of the systems
 | |
| are on different ports.
 | |
| 
 | |
| The general form for UPS identifiers is this::
 | |
| 
 | |
| 	<upsname>[@<hostname>[:<port>]]
 | |
| 
 | |
| Keep this in mind when viewing the examples below.
 | |
| 
 | |
| 
 | |
| ========
 | |
| Manifest
 | |
| ========
 | |
| 
 | |
| This package is broken down into several categories:
 | |
| 
 | |
| - *drivers* - These programs talk directly to your UPS hardware. 
 | |
| 
 | |
| - *server* - upsd serves data from the drivers to the network.
 | |
| 
 | |
| - *clients* - They talk to upsd and do things with the status data.
 | |
| 
 | |
| - *cgi-bin* - Special class of clients that you can use with your web server.
 | |
| 
 | |
| 
 | |
| =======
 | |
| Drivers
 | |
| =======
 | |
| 
 | |
| These programs provide support for specific UPS models.  They understand
 | |
| the protocols and port specifications which define status information
 | |
| and convert it to a form that upsd can understand.
 | |
| 
 | |
| To configure drivers, edit ups.conf.  For this example, we'll have a UPS
 | |
| called "sparky" that uses the apcsmart driver and is connected to
 | |
| ``/dev/ttyS1``.  That's the second serial port on most Linux-based systems.
 | |
| The entry in ``ups.conf`` looks like this::
 | |
| 
 | |
| 	[sparky]
 | |
| 		driver = apcsmart
 | |
| 		port = /dev/ttyS1
 | |
| 
 | |
| To start and stop drivers, use upsdrvctl.  By default, it will start or
 | |
| stop every UPS in the config file::
 | |
| 
 | |
| 	/usr/local/ups/bin/upsdrvctl start
 | |
| 	/usr/local/ups/bin/upsdrvctl stop
 | |
| 
 | |
| However, you can also just start or stop one by adding its name::
 | |
| 
 | |
| 	/usr/local/ups/bin/upsdrvctl start sparky
 | |
| 	/usr/local/ups/bin/upsdrvctl stop sparky
 | |
| 
 | |
| To get the driver name for your device, refer to the below section
 | |
| called "HARDWARE SUPPORT TABLE".
 | |
| 
 | |
| Extra Settings
 | |
| --------------
 | |
| 
 | |
| Some drivers may require additional settings to properly communicate
 | |
| with your hardware.  If it doesn't detect your UPS by default, check the
 | |
| driver's man page or help (-h) to see which options are available.
 | |
| 
 | |
| For example, the apcsmart driver allows setting "cable" to "940-0095B".
 | |
| To use this feature, just add another line to your ups.conf section for
 | |
| that UPS::
 | |
| 
 | |
| 	[sparky]
 | |
| 		driver = apcsmart
 | |
| 		port = /dev/ttyS1
 | |
| 		cable = 940-0095B
 | |
| 
 | |
| Hardware Support Table
 | |
| ----------------------
 | |
| 
 | |
| The NUT Hardware support table is available in the source directory:
 | |
| 
 | |
| 	nut-X.Y.Z/data/driver.list
 | |
| 
 | |
| This one should also be distributed with your favorite packages.
 | |
| For example, it is available on Debian systems as:
 | |
| 
 | |
| 	/usr/share/nut/driver.list
 | |
| 
 | |
| For another take on this list, try the web page: 
 | |
| 
 | |
| 	http://random.networkupstools.org/compat/
 | |
| 
 | |
| If your driver has vanished, see the FAQ and UPGRADING files.
 | |
| 
 | |
| Generic UPS Driver
 | |
| ------------------
 | |
| 
 | |
| The ``genericups`` driver will support many models that use the same basic
 | |
| principle to communicate with the computer.  This is known as "contact
 | |
| closure", and basically involves raising or lowering signals to indicate
 | |
| power status.
 | |
| 
 | |
| This type of UPS tends to be cheaper, and only provides the very simplest
 | |
| data about power and battery status.  Advanced features like battery
 | |
| charge readings and such require a "smart" UPS and a driver which
 | |
| supports it.
 | |
| 
 | |
| See the genericups(8) man page for more information.
 | |
| 
 | |
| There is also a document called contact-closure.txt included with the
 | |
| source distribution that contains information on this kind of hardware
 | |
| and details on adding additional types to the genericups driver.
 | |
| 
 | |
| UPS Shutdowns
 | |
| -------------
 | |
| 
 | |
| upsdrvctl can also shut down (power down) all of your UPS hardware.
 | |
| 
 | |
| **WARNING:** if you play around with this command, expect your filesystems
 | |
| to die.  Don't power off your computers unless they're ready for it::
 | |
| 
 | |
| 	/usr/local/ups/bin/upsdrvctl shutdown
 | |
| 	/usr/local/ups/bin/upsdrvctl shutdown sparky
 | |
| 
 | |
| You should read the shutdown.txt file in the docs subdirectory to
 | |
| learn more about when to use this feature.  If called at the wrong time,
 | |
| you may cause data loss by turning off a system with a filesystem
 | |
| mounted read-write.
 | |
| 
 | |
| 
 | |
| ==============
 | |
| Network Server
 | |
| ==============
 | |
| 
 | |
| ``upsd`` is responsible for passing data from the drivers to the client 
 | |
| programs via the network.  It should be run immediately after ``upsdrvctl``
 | |
| in your system's startup scripts.
 | |
| 
 | |
| ``upsd`` should be kept running whenever possible, as it is the only source
 | |
| of status information for the monitoring clients like ``upsmon``.
 | |
| 
 | |
| 
 | |
| ======
 | |
| upsmon
 | |
| ======
 | |
| 
 | |
| ``upsmon`` provides the essential feature that you expect to find in UPS
 | |
| monitoring software: safe shutdowns when the power fails.
 | |
| 
 | |
| In the layered scheme of NUT software, it is a client.  It has this
 | |
| separate section in the documentation since it is so important.
 | |
| 
 | |
| You configure it by telling it about UPSes that you want to monitor in
 | |
| upsmon.conf.  Each UPS can be defined as one of three possible types:
 | |
| 
 | |
| - Master
 | |
| 
 | |
| 	This UPS supplies power to the system running upsmon, and
 | |
| 	this system is also responsible for shutting it down when
 | |
| 	the battery is depleted.  This occurs after any slave systems
 | |
| 	have disconnected safely.
 | |
| 
 | |
| 	If your UPS is plugged directly into a system's serial port,
 | |
| 	the upsmon on that system should define that UPS as a master.
 | |
| 
 | |
| - Slave
 | |
| 
 | |
| 	This UPS supplies power to the system running upsmon, but 
 | |
| 	this system can't shut it down directly.  This system will
 | |
| 	shut down the operating system before the master turns off the
 | |
| 	power.
 | |
| 
 | |
| 	Use this mode when you run multiple computers on the same UPS.
 | |
| 	Obviously, only one can be connected to the serial port on the
 | |
| 	UPS, and that system is the master.  Everything else is a
 | |
| 	slave.
 | |
|    
 | |
| - Monitor-only
 | |
| 
 | |
| 	This UPS will still generate notifications about status
 | |
| 	changes (on battery, on line, etc.) but no shutdowns of the
 | |
| 	local system result from critical situations on that UPS.
 | |
| 
 | |
| For a typical home user, there's one computer connected to one UPS.
 | |
| That means you run a driver, upsd, and upsmon in master mode.
 | |
| 
 | |
| Additional Information
 | |
| ----------------------
 | |
| 
 | |
| More information on configuring upsmon can be found in these places:
 | |
| 
 | |
|  - The man page - upsmon(8)
 | |
| 
 | |
|  - big-servers.txt in the docs subdirectory
 | |
| 
 | |
|  - shutdown.txt in the docs subdirectory
 | |
| 
 | |
|  - The stock upsmon.conf that comes with the package
 | |
| 
 | |
| 
 | |
| =======
 | |
| Clients
 | |
| =======
 | |
| 
 | |
| Clients talk to upsd over the network and do useful things with the data
 | |
| from the drivers.  There are tools for command line access, and a few
 | |
| special clients which can be run through your web server as CGI
 | |
| programs.
 | |
| 
 | |
| For more details on specific programs, refer to their man pages.
 | |
| 
 | |
| upsc
 | |
| ----
 | |
| 
 | |
| upsc is a simple client that will display the values of variables known
 | |
| to upsd and your UPS drivers.  It will list every variable by default,
 | |
| or just one if you specify an additional argument.  This can be useful 
 | |
| in shell scripts for monitoring something without writing your own 
 | |
| network code.
 | |
| 
 | |
| upsc is a quick way to find out if your driver(s) and upsd are working
 | |
| together properly.  Just run upsc <ups> to see what's going on, i.e.::
 | |
| 
 | |
| 	morbo:~$ upsc su700@localhost
 | |
| 	ambient.humidity: 035.6
 | |
| 	ambient.humidity.alarm.maximum: NO,NO
 | |
| 	ambient.humidity.alarm.minimum: NO,NO
 | |
| 	ambient.temperature: 25.14
 | |
| 
 | |
| 	[ and so on ]
 | |
| 
 | |
| If you are interested in writing a simple client that monitors upsd,
 | |
| the source code for upsc is a good way to learn about using the 
 | |
| upsclient functions.
 | |
| 
 | |
| See the upsc(8) man page for more information.
 | |
| 
 | |
| upslog
 | |
| ------
 | |
| 
 | |
| upslog will write status information from upsd to a file at set
 | |
| intervals.  You can use this to generate graphs or reports with other
 | |
| programs such as gnuplot.
 | |
| 
 | |
| upsrw
 | |
| -----
 | |
| 
 | |
| upsrw allows you to display and change the read/write variables in your
 | |
| UPS hardware.  Not all devices or drivers implement this, so this may
 | |
| not have any effect on your system.  
 | |
| 
 | |
| A driver that supports read/write variables will give results like this::
 | |
| 
 | |
| 	$ upsrw su700@localhost
 | |
| 
 | |
| 	( many skipped )
 | |
| 
 | |
| 	[ups.test.interval]
 | |
| 	Interval between self tests
 | |
| 	Type: ENUM
 | |
| 	Option: "1209600"
 | |
| 	Option: "604800" SELECTED
 | |
| 	Option: "0"
 | |
| 
 | |
| 	( more skipped )
 | |
| 
 | |
| On the other hand, one that doesn't support them won't print anything::
 | |
| 
 | |
| 	$ upsrw fenton@gearbox
 | |
| 
 | |
| 	( nothing )
 | |
| 
 | |
| upsrw requires administrator powers to change settings in the hardware.
 | |
| Refer to upsd.users(5) for information on defining users in upsd.
 | |
| 
 | |
| upscmd
 | |
| ------
 | |
| 
 | |
| Some UPS hardware and drivers support the notion of an instant command -
 | |
| a feature such as starting a battery test, or powering off the load.
 | |
| You can use upscmd to list or invoke instant commands if your
 | |
| hardware/drivers support them.
 | |
| 
 | |
| Use the -l command to list them, like this::
 | |
| 
 | |
| 	$ upscmd -l su700@localhost
 | |
| 	Instant commands supported on UPS [su700@localhost]:
 | |
| 
 | |
| 	load.on - Turn on the load immediately
 | |
| 	test.panel.start - Start testing the UPS panel
 | |
| 	calibrate.start - Start run time calibration
 | |
| 	calibrate.stop - Stop run time calibration
 | |
| 
 | |
| 	[ snip ]
 | |
| 
 | |
| upscmd requires administrator powers to start instant commands.
 | |
| To define users and passwords in upsd, see upsd.users(5).
 | |
| 
 | |
| ============
 | |
| CGI Programs
 | |
| ============
 | |
| 
 | |
| The CGI programs are clients that run through your web server.  They
 | |
| allow you to see UPS status and perform certain administrative commands
 | |
| from any web browser.  Javascript and cookies are not required.
 | |
| 
 | |
| These programs are not installed or compiled by default.  To compile
 | |
| and install them, first run 'configure --with-cgi', then do 'make' and
 | |
| 'make install'.  If you receive errors about "gd" during configure, go
 | |
| get it and install it before continuing.
 | |
| 
 | |
| You can get the source here:
 | |
| 
 | |
| 	http://www.boutell.com/gd/
 | |
| 
 | |
| In the event that you need libpng or zlib in order to compile gd, 
 | |
| they can be found at these URLs:
 | |
| 
 | |
| 	http://www.libpng.org/pub/png/pngcode.html
 | |
| 
 | |
| 	http://www.gzip.org/zlib/
 | |
| 
 | |
| Access Restrictions
 | |
| -------------------
 | |
| 
 | |
| The CGI programs use hosts.conf to see if they are allowed to talk to a
 | |
| host.  This keeps malicious visitors from creating queries from your web
 | |
| server to random hosts on the Internet.
 | |
| 
 | |
| If you get error messages that say "Access to that host is not
 | |
| authorized", you're probably missing an entry in your hosts.conf.
 | |
| 
 | |
| upsstats
 | |
| --------
 | |
| 
 | |
| upsstats generates web pages from HTML templates, and plugs in status
 | |
| information in the right places.  It looks like a distant relative of
 | |
| APC's old Powerchute interface.  You can use it to monitor several
 | |
| systems or just focus on one.
 | |
| 
 | |
| It also can generate IMG references to upsimage.
 | |
| 
 | |
| upsimage
 | |
| --------
 | |
| 
 | |
| This is usually called by upsstats via IMG SRC tags to draw either the
 | |
| utility or outgoing voltage, battery charge percent, or load percent.
 | |
| 
 | |
| upsset
 | |
| ------
 | |
| 
 | |
| upsset provides several useful administration functions through a web
 | |
| interface.  You can use upsset to kick off instant commands on your UPS
 | |
| hardware like running a battery test.  You can also use it to change
 | |
| variables in your UPS that accept user-specified values.
 | |
| 
 | |
| Essentially, upsset provides the functions of upsrw and upscmd, but
 | |
| with a happy pointy-clicky interface.
 | |
| 
 | |
| upsset will not run until you convince it that you have secured your
 | |
| system.  You *must* secure your CGI path so that random interlopers
 | |
| can't run this program remotely.  See the upsset.conf file.  Once you
 | |
| have secured the directory, you can enable this program in that
 | |
| configuration file.  It is not active by default.
 | |
| 
 | |
| 
 | |
| =====================
 | |
| Support / Help / etc.
 | |
| =====================
 | |
| 
 | |
| The main URL:
 | |
| 
 | |
| 	http://www.networkupstools.org/
 | |
| 
 | |
| There is also a mailing list for general queries and discussion about
 | |
| this software called nut-upsuser.  It typically moves around 50-100 messages
 | |
| per month at the time of this writing.  To join, go to the below address and
 | |
| subscribe to the desired list.
 | |
| 
 | |
| Finally, there is a developer list called nut-upsdev.  This is not
 | |
| an install help list, and any such mails probably will be ignored.
 | |
| 
 | |
| The mailing lists are archived on the web:
 | |
| 
 | |
| 	http://alioth.debian.org/mail/?group_id=30602
 | |
| 
 | |
| Try running some searches against the archives.  Many times, problems have
 | |
| already been answered by someone else. Currently, there is no internal
 | |
| search engine, so you will have to try with a search engine like Google.
 | |
| 
 | |
| There is more documentation in the docs/ directory within the source 
 | |
| tree.  Be sure to read through the files in there (especially the
 | |
| FAQ) before mailing the list for help.  Many times the questions have
 | |
| already been answered in the files which are right in front of you.
 | |
| 
 | |
| 
 | |
| ===================================
 | |
| Making your own clients (upsclient)
 | |
| ===================================
 | |
| 
 | |
| The upsclient.a library can be linked into other programs to give access
 | |
| to upsd and UPS status information.  Clients like upsc are provided as
 | |
| examples of how to retrieve data using the upsclient functions.  Other
 | |
| programs not included in this package may also use this library, as wmnut.
 | |
| 
 | |
| This library file and the associated header files are not installed by
 | |
| default.  You must './configure --with-lib' to enable building and
 | |
| installing these files. The libraries can then be build and installed
 | |
| with 'make' and 'make install' as usual. This must be done before
 | |
| building other (non-NUT) programs which depend on them.
 | |
| 
 | |
| To obtain the right compilation and link flags, two helpers are provided:
 | |
| one for platform providing pkg-config, and the other (libupsclient-config)
 | |
| for platform not providing pkg-config.
 | |
| 
 | |
| 
 | |
| =================
 | |
| Version Numbering
 | |
| =================
 | |
| 
 | |
| The version numbers work like this: if the middle number is odd, it's a
 | |
| development tree, otherwise it is the stable tree.
 | |
| 
 | |
| The past stable trees were 1.0, 1.2, 1.4 and 2.0, with the latest stable tree
 | |
| designated 2.2.  The development trees were 1.1, 1.3, 1.5 and 2.1.
 | |
| 
 | |
| The jump to 2.2 is mostly due to the large changes to the features list.
 | |
| There have also been a number of architectural changes which may not be
 | |
| noticeable to most users.
 | |
| 
 | |
| 
 | |
| ====================================
 | |
| Backwards and Forwards Compatibility
 | |
| ====================================
 | |
| 
 | |
| The old network code spans a range from about 0.41.1 when TCP support 
 | |
| was introduced up to the recent 1.4 series.  It used variable names
 | |
| like STATUS, UTILITY, and LOADPCT.  Many of these names go back to the
 | |
| earliest prototypes of this software from 1997.  At that point there
 | |
| was no way to know that so many drivers would come along and introduce 
 | |
| so many new variables and commands.  The resulting mess grew out of
 | |
| control over the years.
 | |
| 
 | |
| During the 1.3 development cycle, all variables and instant commands
 | |
| were renamed to fit into a tree-like structure.  There are major groups,
 | |
| like input, output and battery.  Members of those groups have been
 | |
| arranged to make sense - input.voltage and output.voltage compliment
 | |
| each other.  The old names were UTILITY and OUTVOLT.  The benefits in
 | |
| this change are obvious.
 | |
| 
 | |
| The 1.4 clients can talk to either type of server, and can handle either
 | |
| naming scheme.  1.4 servers have a compatibility mode where they can
 | |
| answer queries for both names, even though the drivers are internally
 | |
| using the new format.
 | |
| 
 | |
| When 1.4 clients talk to 1.4 or 2.0 (or more recent) servers, they will
 | |
| use the new names.
 | |
| 
 | |
| Here's a table to make it easier to visualize:
 | |
| 
 | |
|    +--------+------------------------+
 | |
|    |        | Server                 |
 | |
|    +--------+-----+-----+-----+------+
 | |
|    | Client | 1.0 | 1.2 | 1.4 | 2.0+ |
 | |
|    +========+=====+=====+=====+======+
 | |
|    | 1.0    | yes | yes | yes | no   |
 | |
|    +--------+-----+-----+-----+------+
 | |
|    | 1.2    | yes | yes | yes | no   |
 | |
|    +--------+-----+-----+-----+------+
 | |
|    | 1.4    | yes | yes | yes | yes  |
 | |
|    +--------+-----+-----+-----+------+
 | |
|    | 2.0    | no  | no  | yes | yes  |
 | |
|    +--------+-----+-----+-----+------+
 | |
| 
 | |
| Version 2.0 (and more recent) does not contain backwards compatibility for
 | |
| the old protocol and variable/command names.  As a result, 2.0 clients can't 
 | |
| talk to anything older than a 1.4 server.  If you ask a 2.0 client to 
 | |
| fetch "STATUS", it will fail.  You'll have to ask for "ups.status" 
 | |
| instead.
 | |
| 
 | |
| Authors of separate monitoring programs should have used the 1.4 series
 | |
| to write support for the new variables and command names.  Client
 | |
| software can easily support both versions as long as they like.  If upsd
 | |
| returns 'ERR UNKNOWN-COMMAND' to a GET request, you need to use REQ.
 | |
| 
 | |
| 
 | |
| ==========================
 | |
| Hacking / Development Info
 | |
| ==========================
 | |
| 
 | |
| Additional documentation can be found in the docs subdirectory.
 | |
| 
 | |
| Information on creating new drivers can be found in new-drivers.txt.
 | |
| Also be sure to look at skel.c and main.c.  All drivers are just
 | |
| collections of support functions built around a common core, so most of
 | |
| the dull housekeeping work has been handled for you.
 | |
| 
 | |
| Information on the NUT variables naming can be found in new-names.txt.
 | |
| Information on the architecture and how it all fits together is in the
 | |
| design.txt file.  In short, there's a lot more documentation out there.
 | |
| 
 | |
| Also be sure to read developers.txt, as it explains a lot about the
 | |
| tree, including some of the functions that are provided for your use.
 | |
| 
 | |
| 
 | |
| ================================
 | |
| Acknowledgements / Contributions
 | |
| ================================
 | |
| 
 | |
| MGE UPS SYSTEMS provided extensive technical documents for their UPS product
 | |
| line, along with many units for development of NUT-related projects. The
 | |
| company also sponsored and later hired Arnaud Quette to further officially
 | |
| support these efforts. 
 | |
| 
 | |
| Several drivers such as mge-utalk, mge-shut, snmp-ups, hidups, and usbhid-ups
 | |
| are the result of this collaboration, in addition to the WMNut, MGE HID Parser
 | |
| the libhid projects, .... The features page has improved artwork thanks to Luc
 | |
| and Arnaud of MGE. Other client projects such as KNutClient and ups-monitor
 | |
| have also received assistance. 
 | |
| 
 | |
| The master NUT site and several related projects are hosted on MGE's equipment
 | |
| at no cost to the project.
 | |
| 
 | |
| More information on their open source support can be found on their web site:
 | |
| http://opensource.mgeups.com/contrib.htm 
 | |
| 
 | |
| Fenton Technologies contributed a PowerPal 660 to the project.  Their open 
 | |
| stance and quick responses to technical inquiries are appreciated for 
 | |
| making the development of the fentonups driver possible.
 | |
| 
 | |
| Bo Kersey of VirCIO (http://www.vircio.com) provided a Best Power 
 | |
| Fortress 750 to facilitate the bestups driver.  
 | |
| 
 | |
| Invensys Energy Systems provided the SOLA/Best "Phoenixtec" protocol
 | |
| document currently residing at the following URL:
 | |
| 
 | |
| 	http://random.networkupstools.org/protocols/sola.html
 | |
| 
 | |
| PowerKinetics technical support provided documentation on their MiniCOL
 | |
| protocol, which is archived in the NUT protocol library online:
 | |
| 
 | |
| 	http://random.networkupstools.org/protocols/minicol/
 | |
| 
 | |
| Cyber Power Systems contributed a 700AVR model for testing and driver
 | |
| development.
 | |
| 
 | |
| Liebert Corporation supplied serial test boxes and a UPStation GXT2  
 | |
| with the Web/SNMP card for development of the liebert driver and
 | |
| expansion of the existing snmp-ups driver.
 | |
| 
 |