235 lines
9.1 KiB
C
235 lines
9.1 KiB
C
/* mge-utalk.h - monitor MGE UPS for NUT with UTalk protocol
|
|
*
|
|
* Copyright (C) 2002 - 2005
|
|
* Arnaud Quette <arnaud.quette@free.fr> & <arnaud.quette@mgeups.com>
|
|
* Hans Ekkehard Plesser <hans.plesser@itf.nlh.no>
|
|
* Martin Loyer <martin@ouifi.net>
|
|
* Patrick Agrain <patrick.agrain@alcatel.fr>
|
|
* Nicholas Reilly <nreilly@magma.ca>
|
|
* Dave Abbott <d.abbott@dcs.shef.ac.uk>
|
|
* Marek Kralewski <marek@mercy49.de>
|
|
*
|
|
* This driver is a collaborative effort by the above people,
|
|
* Sponsored by MGE UPS SYSTEMS <http://opensource.mgeups.com/>
|
|
*
|
|
* This program is free software; you can redistribute it and/or modify
|
|
* it under the terms of the GNU General Public License as published by
|
|
* the Free Software Foundation; either version 2 of the License, or
|
|
* (at your option) any later version.
|
|
*
|
|
* This program is distributed in the hope that it will be useful,
|
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
* GNU General Public License for more details.
|
|
*
|
|
* You should have received a copy of the GNU General Public License
|
|
* along with this program; if not, write to the Free Software
|
|
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
|
*
|
|
*/
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Default Values for UPS Variables */
|
|
/* --------------------------------------------------------------- */
|
|
|
|
#define DEFAULT_LOWBATT 30 /* low battery level, in % */
|
|
|
|
/* delay between return of utility power and powering up of load (in MINUTES) */
|
|
#define DEFAULT_ONDELAY 1
|
|
#define DEFAULT_OFFDELAY 20 /* delay before power off, in SECONDS */
|
|
|
|
#define MIN_CONFIRM_TIME 3 /* shutdown must be confirmed in */
|
|
#define MAX_CONFIRM_TIME 15 /* this interval */
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Model Name formating entries */
|
|
/* --------------------------------------------------------------- */
|
|
typedef struct {
|
|
char *basename; /* as returned by Si 1 <data 2> */
|
|
char *finalname;
|
|
} models_name_t;
|
|
|
|
models_name_t Si1_models_names [] =
|
|
{
|
|
/* Pulsar EX */
|
|
{ "Pulsar EX7", "Pulsar EX 7" },
|
|
{ "Pulsar EX10", "Pulsar EX 10" },
|
|
{ "Pulsar EX15", "Pulsar EX 15" },
|
|
{ "Pulsar EX20", "Pulsar EX 20" },
|
|
{ "Pulsar EX30", "Pulsar EX 30" },
|
|
{ "Pulsar EX40", "Pulsar EX 40" },
|
|
|
|
/* Pulsar ES+ */
|
|
{ "Pulsar ES2+", "Pulsar ES 2+" },
|
|
{ "Pulsar ES5+", "Pulsar ES 5+" },
|
|
|
|
/* Pulsar ESV+ */
|
|
{ "Pulsar ESV5+", "Pulsar ESV 5+" },
|
|
{ "Pulsar ESV8+", "Pulsar ESV 8+" },
|
|
{ "Pulsar ESV11+", "Pulsar ESV 11+" },
|
|
{ "Pulsar ESV14+", "Pulsar ESV 14+" },
|
|
{ "Pulsar ESV22+", "Pulsar ESV 22+" },
|
|
|
|
/* Pulsar EXtreme */
|
|
{ "EXTREME 1500", "Pulsar EXtreme 1500" },
|
|
{ "EXTREME 2000", "Pulsar EXtreme 2000" },
|
|
{ "EXTREME 2500", "Pulsar EXtreme 2500" },
|
|
{ "EXTREME 3000", "Pulsar EXtreme 3000" },
|
|
|
|
/* Comet EXtreme */
|
|
{ "EXTREME 4.5", "Comet EXtreme 4.5" },
|
|
{ "EXTREME 6", "Comet EXtreme 6" },
|
|
{ "EXTREME 9", "Comet EXtreme 9" },
|
|
{ "EXTREME 12", "Comet EXtreme 12" },
|
|
|
|
/* Comet */
|
|
{ "COMET 5", "Comet 5" },
|
|
{ "COMET 7", "Comet 7.5" },
|
|
{ "COMET 10", "Comet 10" },
|
|
{ "COMET 15", "Comet 15" },
|
|
{ "COMET 20", "Comet 20" },
|
|
{ "COMET 30", "Comet 30" },
|
|
{ "COMET 12", "Comet 12" },
|
|
{ "COMET 18", "Comet 18" },
|
|
{ "COMET 24", "Comet 24" },
|
|
{ "COMET 36", "Comet 36" },
|
|
|
|
/* FIXME: complete with Pulsar ?EL 2/4/7?, EXL, SX, PSX/CSX, Evolution?,... */
|
|
|
|
/* end of structure. */
|
|
{ NULL, "Generic UTalk model" }
|
|
};
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Model Information for legacy models */
|
|
/* --------------------------------------------------------------- */
|
|
|
|
/* Structure defining how to get name and model for a particular Si output
|
|
* This is for older UPS (Pulsar ESV,SV) which don't support Plug'n'Play 'Si 1' command
|
|
*/
|
|
typedef struct {
|
|
int Data1; /* Data1, Family model */
|
|
int Data2; /* Data2, Type */
|
|
/* Data3, SoftLevel is not implemented here, while it's always null or zero.*/
|
|
const char *name; /* ASCII model name (like 'Si 1' output */
|
|
} mge_model_info_t;
|
|
|
|
/* Array containing Model information for legacy models
|
|
* NOTE:
|
|
* - Array is terminated by element with type NULL.
|
|
*/
|
|
|
|
static mge_model_info_t mge_model[] = {
|
|
/* Pulsar SV page */
|
|
{ 3000, 5, "Pulsar SV3" },
|
|
{ 3000, 6, "Pulsar SV5/8/11" },
|
|
{ 3000, 7, "Pulsar SV3" },
|
|
{ 3000, 8, "Pulsar SV5/8" },
|
|
{ 3000, 10, "Pulsar SV11/ESV13" },
|
|
/* Pulsar ESV page */
|
|
{ 3000, 11, "Pulsar ESV17" },
|
|
{ 3000, 12, "Pulsar ESV20" },
|
|
{ 3000, 13, "Pulsar ESV13" },
|
|
{ 3000, 14, "Pulsar ESV17" },
|
|
{ 3000, 15, "Pulsar ESV20" },
|
|
{ 3000, 17, "Pulsar ESV8" },
|
|
/* Pulsar ESV+ compatibility (though these support Si1) */
|
|
{ 3000, 51, "Pulsar ESV 11+" },
|
|
{ 0, 0, NULL }
|
|
};
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Multiplier Tables */
|
|
/* --------------------------------------------------------------- */
|
|
|
|
/* First index : Table number, fetched with "Ai" command
|
|
* Second index: unit, as in enum above
|
|
* NOTE:
|
|
* - to make the table index the same as the MGE table number,
|
|
* dummy table row multiplier[0][] is inserted
|
|
* - unit MIN2SEC is used to convert values in minutes sent by
|
|
* the UPS (WAKEDELAY) to seconds
|
|
* - the final column corresponds to unit NONE
|
|
*/
|
|
|
|
/* units in multiplier table */
|
|
typedef enum eunits
|
|
{ VOLT = 0, AMPERE, HERTZ, VOLTAMP, WATT, DEGCELS, MIN2SEC, NONE } units_t;
|
|
|
|
static const double multiplier[4][8] = {
|
|
/* V A Hz VA W C MIN2SEC NONE */
|
|
{ 1 , 1 , 1 , 1, 1, 1, 60, 1 },
|
|
{ 1 , 1 , 0.1 , 1000, 1000, 1, 60, 1 },
|
|
{ 0.01, 0.01, 1 , 1, 1, 1, 60, 1 },
|
|
{ 1 , 0.01, 0.1 , 1, 1, 1, 60, 1 }
|
|
};
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Explicit Booleans */
|
|
/* --------------------------------------------------------------- */
|
|
|
|
/* use explicit booleans */
|
|
#ifdef FALSE
|
|
#undef FALSE
|
|
#endif /* FALSE */
|
|
#ifdef TRUE
|
|
#undef TRUE
|
|
#endif /* TRUE */
|
|
typedef enum ebool { FALSE=0, TRUE } bool_t;
|
|
|
|
|
|
/* --------------------------------------------------------------- */
|
|
/* Query Commands and their Mapping to INFO_ Variables */
|
|
/* --------------------------------------------------------------- */
|
|
|
|
/* Structure defining how to query UPS for a variable and write
|
|
information to INFO structure.
|
|
*/
|
|
typedef struct {
|
|
const char *type; /* INFO_* element */
|
|
int flags; /* INFO-element flags to set in addinfo */
|
|
int length; /* INFO-element length of strings */
|
|
const char cmd[32]; /* UPS command string to requets element */
|
|
const char fmt[32]; /* printf format string for INFO entry */
|
|
units_t unit; /* unit of measurement, or NONE */
|
|
bool_t ok; /* flag indicating if item is available */
|
|
} mge_info_item_t;
|
|
|
|
/* Array containing information to translate between UTalk and NUT info
|
|
* NOTE:
|
|
* - Array is terminated by element with type NULL.
|
|
* - Essential INFO items (_MFR, _MODEL, _FIRMWARE, _STATUS) are
|
|
* handled separately.
|
|
* - Array is NOT const, since "ok" can be changed.
|
|
*/
|
|
|
|
static mge_info_item_t mge_info[] = {
|
|
/* Battery page */
|
|
{ "battery.charge", 0, 0, "Bl", "%05.1f", NONE, TRUE },
|
|
{ "battery.runtime", 0, 0, "Bn", "%05d", NONE, TRUE },
|
|
{ "battery.voltage", 0, 0, "Bv", "%05.1f", VOLT, TRUE },
|
|
{ "battery.charge.low", ST_FLAG_RW | ST_FLAG_STRING, 2, "Bl ?", "%02d", NONE, TRUE },
|
|
{ "battery.voltage.nominal", 0, 0, "Bv ?", "%05.1f", VOLT, TRUE },
|
|
/* UPS page */
|
|
{ "ups.temperature", 0, 0, "St", "%05.1f", DEGCELS, TRUE },
|
|
{ "ups.load", 0, 0, "Ll", "%05.1f", NONE, TRUE },
|
|
{ "ups.delay.start", ST_FLAG_RW | ST_FLAG_STRING, 5, "Sm ?", "%03d", NONE, TRUE },
|
|
{ "ups.delay.shutdown", ST_FLAG_RW | ST_FLAG_STRING, 5, "Sn ?", "%03d", NONE, TRUE },
|
|
{ "ups.test.interval", ST_FLAG_RW | ST_FLAG_STRING, 5, "Bp ?", "%03d", NONE, TRUE },
|
|
/* Output page */
|
|
{ "output.voltage", 0, 0, "Lv", "%05.1f", VOLT, TRUE },
|
|
{ "output.current", 0, 0, "Lc", "%05.1f", AMPERE, TRUE },
|
|
/* Input page */
|
|
{ "input.voltage", 0, 0, "Uv", "%05.1f", VOLT, TRUE },
|
|
{ "input.frequency", 0, 0, "Uf", "%05.2f", HERTZ, TRUE },
|
|
/* same as LOBOOSTXFER */
|
|
{ "input.transfer.low", ST_FLAG_RW | ST_FLAG_STRING, 5, "Ee ?", "%05.1f", VOLT, TRUE },
|
|
{ "input.transfer.boost.low", ST_FLAG_RW | ST_FLAG_STRING, 5, "Ee ?", "%05.1f", VOLT, TRUE },
|
|
{ "input.transfer.boost.high", ST_FLAG_RW | ST_FLAG_STRING, 5, "Eo ?", "%05.1f", VOLT, TRUE },
|
|
{ "input.transfer.trim.low", ST_FLAG_RW | ST_FLAG_STRING, 5, "Ea ?", "%05.1f", VOLT, TRUE },
|
|
/* same as HITRIMXFER */
|
|
{ "input.transfer.high", ST_FLAG_RW | ST_FLAG_STRING, 5, "Eu ?", "%05.1f", VOLT, TRUE },
|
|
{ "input.transfer.trim.high", ST_FLAG_RW | ST_FLAG_STRING, 5, "Eu ?", "%05.1f", VOLT, TRUE },
|
|
/* terminating element */
|
|
{ NULL, 0, 0, "\0", "\0", NONE, FALSE }
|
|
};
|