173 lines
9.4 KiB
C
173 lines
9.4 KiB
C
/* netvision-mib.c - data to monitor Socomec Sicon UPS equipped
|
|
* with Netvision WEB/SNMP card/external box with NUT
|
|
*
|
|
* Copyright (C)
|
|
* 2004 Thanos Chatziathanassiou <tchatzi@arx.net>
|
|
* 2012 Manuel Bouyer <bouyer@NetBSD.org>
|
|
*
|
|
* This program is free software; you can redistribute it and/or modify
|
|
* it under the terms of the GNU General Public License as published by
|
|
* the Free Software Foundation; either version 2 of the License, or
|
|
* (at your option) any later version.
|
|
*
|
|
* This program is distributed in the hope that it will be useful,
|
|
* but WITHOUT ANY WARRANTY; without even the implied warranty of
|
|
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
|
* GNU General Public License for more details.
|
|
*
|
|
*
|
|
* You should have received a copy of the GNU General Public License
|
|
* along with this program; if not, write to the Free Software
|
|
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
|
*
|
|
*/
|
|
|
|
#include "netvision-mib.h"
|
|
|
|
#define NETVISION_MIB_VERSION "0.3"
|
|
|
|
#define NETVISION_SYSOID ".1.3.6.1.4.1.4555.1.1.1"
|
|
|
|
/* SNMP OIDs set */
|
|
#define NETVISION_OID_UPS_MIB ".1.3.6.1.4.1.4555.1.1.1.1"
|
|
#define NETVISION_OID_UPSIDENTMODEL ".1.3.6.1.4.1.4555.1.1.1.1.1.1.0"
|
|
#define NETVISION_OID_UPSIDENTFWVERSION ".1.3.6.1.4.1.4555.1.1.1.1.1.2.0"
|
|
#define NETVISION_OID_UPSIDENTAGENTSWVERSION ".1.3.6.1.4.1.4555.1.1.1.1.1.3.0"
|
|
#define NETVISION_OID_UPSIDENTUPSSERIALNUMBER ".1.3.6.1.4.1.4555.1.1.1.1.1.4.0"
|
|
|
|
/* UPS Battery */
|
|
#define NETVISION_OID_BATTERYSTATUS ".1.3.6.1.4.1.4555.1.1.1.1.2.1.0"
|
|
static info_lkp_t netvision_batt_info[] = {
|
|
{ 2, "" }, /* battery normal */
|
|
{ 3, "LB" }, /* battery low */
|
|
{ 4, "LB" }, /* battery depleted */
|
|
{ 5, "DISCHRG" }, /* battery discharging */
|
|
{ 6, "RB" }, /* battery failure */
|
|
{ 0, "NULL" }
|
|
};
|
|
|
|
#define NETVISION_OID_SECONDSONBATTERY ".1.3.6.1.4.1.4555.1.1.1.1.2.2.0"
|
|
#define NETVISION_OID_BATT_RUNTIME_REMAINING ".1.3.6.1.4.1.4555.1.1.1.1.2.3.0"
|
|
#define NETVISION_OID_BATT_CHARGE ".1.3.6.1.4.1.4555.1.1.1.1.2.4.0"
|
|
#define NETVISION_OID_BATT_VOLTS ".1.3.6.1.4.1.4555.1.1.1.1.2.5.0"
|
|
|
|
#define NETVISION_OID_INPUT_NUM_LINES ".1.3.6.1.4.1.4555.1.1.1.1.3.1.0" /* 1phase or 3phase UPS input */
|
|
#define NETVISION_OID_INPUT_FREQ ".1.3.6.1.4.1.4555.1.1.1.1.3.2.0"
|
|
#define NETVISION_OID_OUTPUT_NUM_LINES ".1.3.6.1.4.1.4555.1.1.1.1.4.3.0" /* 1phase or 3phase UPS output */
|
|
#define NETVISION_OID_OUTPUT_FREQ ".1.3.6.1.4.1.4555.1.1.1.1.4.2.0"
|
|
|
|
#define NETVISION_OID_BYPASS_FREQ ".1.3.6.1.4.1.4555.1.1.1.1.5.1.0"
|
|
#define NETVISION_OID_BYPASS_NUM_LINES ".1.3.6.1.4.1.4555.1.1.1.1.5.2.0" /* 1phase or 3phase UPS input */
|
|
/*
|
|
three phase ups provide input/output/load for each phase
|
|
in case of one-phase output, only _P1 should be used
|
|
*/
|
|
|
|
#define NETVISION_OID_OUT_VOLTAGE_P1 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.1"
|
|
#define NETVISION_OID_OUT_CURRENT_P1 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.1"
|
|
#define NETVISION_OID_OUT_LOAD_PCT_P1 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.1"
|
|
#define NETVISION_OID_IN_VOLTAGE_P1 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.1"
|
|
#define NETVISION_OID_IN_CURRENT_P1 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.1"
|
|
#define NETVISION_OID_BY_VOLTAGE_P1 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.1"
|
|
#define NETVISION_OID_BY_CURRENT_P1 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.1"
|
|
|
|
#define NETVISION_OID_OUT_VOLTAGE_P2 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.2"
|
|
#define NETVISION_OID_OUT_CURRENT_P2 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.2"
|
|
#define NETVISION_OID_OUT_LOAD_PCT_P2 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.2"
|
|
#define NETVISION_OID_IN_VOLTAGE_P2 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.2"
|
|
#define NETVISION_OID_IN_CURRENT_P2 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.2"
|
|
#define NETVISION_OID_BY_VOLTAGE_P2 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.2"
|
|
#define NETVISION_OID_BY_CURRENT_P2 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.2"
|
|
|
|
#define NETVISION_OID_OUT_VOLTAGE_P3 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2.3"
|
|
#define NETVISION_OID_OUT_CURRENT_P3 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3.3"
|
|
#define NETVISION_OID_OUT_LOAD_PCT_P3 ".1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4.3"
|
|
#define NETVISION_OID_IN_VOLTAGE_P3 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5.3"
|
|
#define NETVISION_OID_IN_CURRENT_P3 ".1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3.3"
|
|
#define NETVISION_OID_BY_VOLTAGE_P3 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2.3"
|
|
#define NETVISION_OID_BY_CURRENT_P3 ".1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3.3"
|
|
|
|
#define NETVISION_OID_OUTPUT_SOURCE ".1.3.6.1.4.1.4555.1.1.1.1.4.1.0"
|
|
|
|
#define NETVISION_OID_CONTROL_STATUS ".1.3.6.1.4.1.4555.1.1.1.1.8.1"
|
|
#define NETVISION_OID_CONTROL_SHUTDOWN_DELAY ".1.3.6.1.4.1.4555.1.1.1.1.8.2"
|
|
|
|
static info_lkp_t netvision_output_info[] = {
|
|
{ 1, "" }, /* output source other */
|
|
{ 2, "" }, /* output source none */
|
|
{ 3, "OL" }, /* output source normal */
|
|
{ 4, "OL BYPASS" }, /* output source bypass */
|
|
{ 5, "OB" }, /* output source battery */
|
|
{ 6, "OL BOOST" }, /* output source booster */
|
|
{ 7, "OL TRIM" }, /* output source reducer */
|
|
{ 8, "OL" }, /* output source standby */
|
|
{ 9, "" }, /* output source ecomode */
|
|
{ 0, "NULL" }
|
|
};
|
|
|
|
/* Snmp2NUT lookup table */
|
|
static snmp_info_t netvision_mib[] = {
|
|
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTAGENTSWVERSION, "SOCOMEC SICON UPS",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTMODEL,
|
|
"Generic SNMP UPS", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
{ "ups.serial", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTUPSSERIALNUMBER, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
{ "ups.firmware.aux", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_UPSIDENTFWVERSION, "",
|
|
SU_FLAG_STATIC | SU_FLAG_OK, NULL },
|
|
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_BATTERYSTATUS, "",
|
|
SU_FLAG_OK | SU_STATUS_BATT, &netvision_batt_info[0] },
|
|
{ "ups.status", ST_FLAG_STRING, SU_INFOSIZE, NETVISION_OID_OUTPUT_SOURCE, "",
|
|
SU_FLAG_OK | SU_STATUS_PWR, &netvision_output_info[0] },
|
|
|
|
/* ups load */
|
|
{ "ups.load", 0, 1, NETVISION_OID_OUT_LOAD_PCT_P1, 0, SU_INPUT_1, NULL },
|
|
|
|
/*ups input,output voltage, output frquency phase 1 */
|
|
{ "input.phases", 0, 1.0, NETVISION_OID_INPUT_NUM_LINES, 0, SU_FLAG_SETINT, NULL, &input_phases },
|
|
{ "input.frequency", 0, 0.1, NETVISION_OID_INPUT_FREQ, 0, SU_FLAG_OK, NULL },
|
|
{ "input.voltage", 0, 0.1, NETVISION_OID_IN_VOLTAGE_P1, 0, SU_INPUT_1, NULL },
|
|
{ "input.current", 0, 0.1, NETVISION_OID_IN_CURRENT_P1, 0, SU_INPUT_1, NULL },
|
|
{ "input.L1-N.voltage", 0, 0.1, NETVISION_OID_IN_VOLTAGE_P1, 0, SU_INPUT_3, NULL },
|
|
{ "input.L1.current", 0, 0.1, NETVISION_OID_IN_CURRENT_P1, 0, SU_INPUT_3, NULL },
|
|
{ "input.L2-N.voltage", 0, 0.1, NETVISION_OID_IN_VOLTAGE_P2, 0, SU_INPUT_3, NULL },
|
|
{ "input.L2.current", 0, 0.1, NETVISION_OID_IN_CURRENT_P2, 0, SU_INPUT_3, NULL },
|
|
{ "input.L3-N.voltage", 0, 0.1, NETVISION_OID_IN_VOLTAGE_P3, 0, SU_INPUT_3, NULL },
|
|
{ "input.L3.current", 0, 0.1, NETVISION_OID_IN_CURRENT_P3, 0, SU_INPUT_3, NULL },
|
|
|
|
{ "output.phases", 0, 1.0, NETVISION_OID_OUTPUT_NUM_LINES, 0, SU_FLAG_SETINT, NULL, &output_phases },
|
|
{ "output.frequency", 0, 0.1, NETVISION_OID_OUTPUT_FREQ, 0, SU_FLAG_OK, NULL },
|
|
{ "output.voltage", 0, 0.1, NETVISION_OID_OUT_VOLTAGE_P1, 0, SU_OUTPUT_1, NULL },
|
|
{ "output.current", 0, 0.1, NETVISION_OID_OUT_CURRENT_P1, 0, SU_OUTPUT_1, NULL },
|
|
{ "output.load", 0, 1.0, NETVISION_OID_OUT_LOAD_PCT_P1, 0, SU_OUTPUT_1, NULL },
|
|
{ "output.L1-N.voltage", 0, 0.1, NETVISION_OID_OUT_VOLTAGE_P1, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L1.current", 0, 0.1, NETVISION_OID_OUT_CURRENT_P1, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L1.power.percent", 0, 1.0, NETVISION_OID_OUT_LOAD_PCT_P1, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L2-N.voltage", 0, 0.1, NETVISION_OID_OUT_VOLTAGE_P2, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L2.current", 0, 0.1, NETVISION_OID_OUT_CURRENT_P2, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L2.power.percent", 0, 1.0, NETVISION_OID_OUT_LOAD_PCT_P2, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L3-N.voltage", 0, 0.1, NETVISION_OID_OUT_VOLTAGE_P3, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L3.current", 0, 0.1, NETVISION_OID_OUT_CURRENT_P3, 0, SU_OUTPUT_3, NULL },
|
|
{ "output.L3.power.percent", 0, 1.0, NETVISION_OID_OUT_LOAD_PCT_P3, 0, SU_OUTPUT_3, NULL },
|
|
|
|
{ "input.bypass.phases", 0, 1.0, NETVISION_OID_BYPASS_NUM_LINES, 0, SU_FLAG_SETINT, NULL, &bypass_phases },
|
|
{ "input.bypass.frequency", 0, 0.1, NETVISION_OID_BYPASS_FREQ, 0, SU_FLAG_OK, NULL },
|
|
{ "input.bypass.voltage", 0, 0.1, NETVISION_OID_BY_VOLTAGE_P1, 0, SU_BYPASS_1, NULL },
|
|
{ "input.bypass.current", 0, 0.1, NETVISION_OID_BY_CURRENT_P1, 0, SU_BYPASS_1, NULL },
|
|
{ "input.bypass.L1-N.voltage", 0, 0.1, NETVISION_OID_BY_VOLTAGE_P1, 0, SU_BYPASS_3, NULL },
|
|
{ "input.bypass.L1.current", 0, 0.1, NETVISION_OID_BY_CURRENT_P1, 0, SU_BYPASS_3, NULL },
|
|
{ "input.bypass.L2-N.voltage", 0, 0.1, NETVISION_OID_BY_VOLTAGE_P2, 0, SU_BYPASS_3, NULL },
|
|
{ "input.bypass.L2.current", 0, 0.1, NETVISION_OID_BY_CURRENT_P2, 0, SU_BYPASS_3, NULL },
|
|
{ "input.bypass.L3-N.voltage", 0, 0.1, NETVISION_OID_BY_VOLTAGE_P3, 0, SU_BYPASS_3, NULL },
|
|
{ "input.bypass.L3.current", 0, 0.1, NETVISION_OID_BY_CURRENT_P3, 0, SU_BYPASS_3, NULL },
|
|
|
|
/* battery info */
|
|
{ "battery.charge", 0, 1, NETVISION_OID_BATT_CHARGE, "", SU_FLAG_OK, NULL },
|
|
{ "battery.voltage", 0, 0.1, NETVISION_OID_BATT_VOLTS, "", SU_FLAG_OK, NULL },
|
|
{ "battery.runtime", 0, 60, NETVISION_OID_BATT_RUNTIME_REMAINING, "", SU_FLAG_OK, NULL },
|
|
|
|
/* end of structure. */
|
|
{ NULL, 0, 0, NULL, NULL, 0, NULL }
|
|
};
|
|
|
|
mib2nut_info_t netvision = { "netvision", NETVISION_MIB_VERSION, "", NETVISION_OID_UPSIDENTMODEL, netvision_mib, NETVISION_SYSOID };
|