POWERCOM(8)
|
|
===========
|
|
|
|
NAME
|
|
----
|
|
|
|
powercom - UPS driver for Powercom/Trust/Advice UPS equipment
|
|
|
|
NOTE
|
|
----
|
|
This man page only documents the hardware-specific features of the
|
|
powercom driver. For information about the core driver, see
|
|
linkman:nutupsdrv[8].
|
|
|
|
SUPPORTED HARDWARE
|
|
------------------
|
|
This driver supports many similar kinds of UPS hardware. The most common
|
|
ones are the Trust 425/625, Powercom, and Advice Partner/King PR750.
|
|
Others using the same protocol may also work.
|
|
|
|
EXTRA ARGUMENTS
|
|
---------------
|
|
This driver supports the following optional settings in the
|
|
linkman:ups.conf[5] file:
|
|
|
|
*linevoltage*='value'::
|
|
An integer specifying the line voltage. It can't be auto detected. Acceptable
|
|
values are in the range of 110-120 or 220-240. The default is '230'.
|
|
|
|
*manufacturer*='name'::
|
|
Specify the manufacturer name, which also can't be auto detected. This is a
|
|
user defined string, so any name is acceptable. The default is 'PowerCom'.
|
|
|
|
*modelname*='name'::
|
|
Specify the model name, which also can't be auto detected. This is a user
|
|
defined string, so any name is acceptable. The default is 'Unknown'.
|
|
|
|
*serialnumber*='value'::
|
|
Like modelname above, but for the serial number. The default is 'Unknown'.
|
|
|
|
*type*='name'::
|
|
The exact type of the communication protocol within the powercom family, that
|
|
will be used to communicate with the UPS. The type is named after the first
|
|
modelname that was coded with that protocol. The acceptable names are
|
|
'Trust', 'Egys', 'KP625AP', 'IMP', 'KIN', 'BNT', and 'BNT-other'.
|
|
The default is 'Trust'.
|
|
+
|
|
'BNT-other' is a special type for other BNT models (such as the 1500A at 120V
|
|
and can be used to override ALL models using ALL of the following values.
|
|
|
|
*shutdownArguments*={{'minutes','seconds'},'whether_minutes_should_be_used'}::
|
|
The minutes and seconds that the UPS should wait between receiving the
|
|
shutdown command and actually shutting off. The other argument should be set
|
|
to the character 'n' only when the minutes value should be skipped and not
|
|
sent to the UPS. The default is type-dependent and is given below. The braces
|
|
and commas are mandatory. Note that there should be no whitespace characters.
|
|
|
|
*numOfBytesFromUPS*='value'::
|
|
The number of bytes in a UPS frame: 16 is common, 11 for 'Trust'. The default
|
|
is type-dependent and is given below.
|
|
|
|
*methodOfFlowControl*='name'::
|
|
The method of serial communication flow control that is engaged by the UPS.
|
|
The default is type-dependent and is given below. Acceptable names are
|
|
'dtr0rts1', 'dtr1' or 'no_flow_control'.
|
|
|
|
*validationSequence*={{'index1','value1'},{'index2','value2'},{'index3','value3'}}::
|
|
(Only for types KP625AP, Trust, Egys.)
|
|
3 pairs to be used for validating the UPS by comparing bytes of the raw data
|
|
with constant values. The index selects the byte from the UPS (see
|
|
numOfBytesFromUPS) and the value is for matching to the byte. The default is
|
|
type-dependent and is given below. The braces and commas are mandatory, as
|
|
the lack of white space characters.
|
|
|
|
*frequency*={'A','B'}::
|
|
(Only for types KP625AP, Trust, Egys.)
|
|
A pair to convert the raw frequency data to a human-readable frequency
|
|
reading using the function 1/(A*x+B). If the raw value x IS the frequency,
|
|
then set A=1/(x^2) and B=0. The default is type-dependent and is given below.
|
|
Do note that the braces and commas are mandatory as well, as the lack of
|
|
whitespace characters.
|
|
|
|
*loadPercentage*={'BatteryA','BatteryB','LineA','LineB'}::
|
|
(Only for types KP625AP, Trust, Egys.)
|
|
A quad to convert the raw load data to human readable load percentage reading
|
|
using the function A*x+B. If the raw value x IS the Load Percent, then set
|
|
A=1 and B=0. The default is type-dependent and is given below. Do note that
|
|
the braces and commas are mandatory, as the lack of white space
|
|
characters.
|
|
|
|
*batteryPercentage*={'Battery1','Battery2','Battery3','Line4','Line5'}::
|
|
(Only for KP625AP, Trust, Egys.)
|
|
A 5 tuple to convert the raw battery and line data to a human-readable
|
|
battery and line percentage reading using the functions (Battery)
|
|
A*x+B*y+C and (Line) D*x+E. If the raw value x IS the Battery Percent, then
|
|
set A=1, B=0, C=0, D=1, E=0. The default is type-dependent and is given below.
|
|
Do note that the braces and commas are mandatory, as the lack of white space
|
|
characters.
|
|
|
|
*voltage*={'240A','240B','120A','120B'}::
|
|
(Only for types KP625AP, Trust, Egys.)
|
|
A quad that is used convert the raw voltage data to a human-readable voltage
|
|
reading using the function A*x+B. If the raw value x IS HALF the Voltage,
|
|
then set A=2, B=0. The default is type-dependent and is given below. Do note
|
|
that the braces and commas are mandatory, as well as the lack of whitespace
|
|
characters.
|
|
|
|
DEFAULT VALUES FOR THE EXTRA ARGUMENTS
|
|
--------------------------------------
|
|
linevoltage = 230
|
|
manufacturer = PowerCom
|
|
modelname = Unknown
|
|
serialnumber = Unknown
|
|
type = Trust
|
|
|
|
The rest of the default values for the extra arguments are type-dependent.
|
|
However, 'BNT-other' is a special type that can be used to override ALL
|
|
values for ALL models.
|
|
|
|
Trust
|
|
~~~~~
|
|
numOfBytesFromUPS = 11
|
|
methodOfFlowControl = dtr0rts1
|
|
validationSequence = {{5,0},{7,0},{8,0}}
|
|
shutdownArguments = {{0,10},n}
|
|
frequency = {0.00020997,0.00020928}
|
|
loadPercentage = {6.1343,-0.3808,4.3110,0.1811}
|
|
batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}
|
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
|
|
|
KP625AP
|
|
~~~~~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = dtr0rts1
|
|
validationSequence = {{5,0x80},{7,0},{8,0}}
|
|
shutdownArguments = {{0,10},n}
|
|
frequency = {0.00020997,0.00020928}
|
|
loadPercentage = {6.1343,-0.3808,4.3110,0.1811}
|
|
batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}
|
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
|
|
|
Egys
|
|
~~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = no_flow_control
|
|
validationSequence = {{5,0x80},{7,0},{8,0}}
|
|
shutdownArguments = {{0,10},n}
|
|
frequency = {0.00020997,0.00020928}
|
|
loadPercentage = {6.1343,-0.3808,1.3333,0.6667}
|
|
batteryPercentage = {5.0000,0.3268,-825.00,2.2105,-355.37}
|
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
|
|
|
IMP
|
|
~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = no_flow_control
|
|
validationSequence = {{5,0xFF},{7,0},{8,0}}
|
|
shutdownArguments = {{1,30},y}
|
|
|
|
KIN
|
|
~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = no_flow_control
|
|
validationSequence = {{11,0x4b},{8,0},{8,0}}
|
|
shutdownArguments = {{1,30},y}
|
|
|
|
BNT
|
|
~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = no_flow_control
|
|
validationSequence = {{11,0x42},{8,0},{8,0}}
|
|
shutdownArguments = {{1,30},y}
|
|
|
|
BNT-other
|
|
~~~~~~~~~
|
|
numOfBytesFromUPS = 16
|
|
methodOfFlowControl = no_flow_control
|
|
validationSequence = {{8,0},{8,0},{8,0}}
|
|
shutdownArguments = {{1,30},y}
|
|
frequency = {0.00027778,0.0000}
|
|
loadPercentage = {1.0000,0.0,1.0000,0.0}
|
|
batteryPercentage = {1.0000,0.0000,0.0000,1.0000,0.0000}
|
|
voltage = {2.0000,0.0000,2.0000,0.0000}
|
|
|
|
AUTHOR
|
|
------
|
|
Peter Bieringer <pb@bieringer.de>,
|
|
Alexey Sidorov <alexsid@altlinux.org>,
|
|
Keven L. Ates <atescomp@gmail.com>
|
|
|
|
SEE ALSO
|
|
--------
|
|
|
|
The core driver:
|
|
~~~~~~~~~~~~~~~~
|
|
linkman:nutupsdrv[8]
|
|
|
|
Internet resources:
|
|
~~~~~~~~~~~~~~~~~~~
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|