Desc: Frequently Asked Questions
File: FAQ
Date: 20 January 2006
Auth: Russell Kroll <rkroll@exploits.org>
      Arnaud Quette <aquette.dev@gmail.com>
 
-----------------------------------------------------------------------------

 Q: I just upgraded, and ...

 A: You have read UPGRADING in the base directory of the distribution,
    right?  If not, go read it now, then come back to this file if your
    question wasn't answered in there.

-----------------------------------------------------------------------------

 Q: upsstats says "Error: can't open template file (upsstats.html)".
    How do I fix this?

 A: Go into your configuration path (/usr/local/ups/etc by default) and
    copy the sample template files over to their real names.  The sample
    template files are installed with 'make install-cgi-conf' and can 
    also be found inside the source distribution in the conf directory. 

-----------------------------------------------------------------------------

 Q: upsmon fails the login and says "username required" now.

 A: Go read the UPGRADING file again.

-----------------------------------------------------------------------------

 Q: My 1.4 CGI programs won't talk to my 2.0 upsd.  What should I do?

 A: Upgrade the CGI programs to 2.0.  While 1.4 was intended as a 
    compatibility tree that used the new protocol by default, the CGI
    programs were not upgraded at the same time.  The 1.4 versions
    still use the old REQ protocol, and your 2.0 upsd expects GET.

-----------------------------------------------------------------------------

 Q: I just upgraded from 1.2 and upsmon now fails to start, saying
    "Fatal error: insufficient power configured!".  Why?

 A: You didn't read the top of the error, where upsmon says that it 
    ignored the invalid MONITOR line because UPS directives now require
    a UPS name.  It also means you didn't see the same warning in 
    UPGRADING.

    At least you saw this in the FAQ before asking the list.

-----------------------------------------------------------------------------

 Q: My UPS driver now says it's "broken", and won't start.  What now?

 Q: My favorite UPS driver disappeared after an upgrade.  What now?

 A: Drivers are occasionally removed from the tree if they are no longer
    receiving maintenance, or sometimes renamed to better reflect their
    hardware support scope or replaced by a more generic driver.
    There have been several architectural changes to the driver code
    in recent times, and drivers which were not converted by someone
    are eventually dropped.

    This is called progress.  We do this in order to avoid a situation
    where someone believes that a driver is being maintained when it is
    actually rotting slowly in the tree.  It also keeps the tree free of
    old compatibility hacks for code that nobody actually uses anyway.

    To get a driver back into current releases, you need to convert it
    yourself or get someone to do it for you.  This is not difficult.
    The hardest part of any driver is decoding the protocol, and that's
    already been done in the old version.

-----------------------------------------------------------------------------

 Q: I just upgraded and now I can't talk to older versions.

 A: Version 2.0 can't communicate with anything before 1.4 due to the
    protocol changes.  Version 1.4 can communicate with both 2.0 and
    most older versions since it was a transitional release and has
    compatibility code for both protocols.

-----------------------------------------------------------------------------

 Q: My UPS driver program won't work.  I'm starting it as root, and root
    owns the device, so what's the problem?

 A: The drivers drop root privileges long before the serial port is
    opened.  You'll need to change the permissions on that port so that
    their new user id can access it.  Normally this is "nobody", but it 
    may be changed at compile-time by using configure --with-user.

    Read the error message.  If you have a permissions mismatch, then
    you'll see something like this:

	Network UPS Tools - APC Smart protocol driver 0.60 (1.1.7)
	This program is currently running as youruid (UID 1234)
	/dev/ttyS2 is owned by user root (UID 0), mode 0600
	Change the port name, or fix the permissions or ownership 
	of /dev/ttyS2 and try again.
	Unable to open /dev/ttyS2: Permission denied

    Now is a good time to point out that using "nobody" is a bad idea,
    since it's a hack for NFS access.  You should create a new role 
    account (perhaps called "ups" or "nut"), and use that instead.

    Also, scroll down to the "security domains" question to see an
    even better way of restricting privileged operations.  Neither the
    drivers nor upsd ever need root powers, and that answer tells you
    how to make it work.

 A: You can also specify a user with "user=" in the global part of
    ups.conf.  Just define it before any of your [sections]:

		user = nut

	[myups]
		driver = mge-shut
		port = /dev/ttyS0

-----------------------------------------------------------------------------

 Q: upsc, upsstats, and the other clients say "access denied".  The device
    communication port (serial, USB or network) permissions are fine, so what
    gives? 

 A: In this case, "access denied" means the access to upsd, not the device
    communication port.  You're being denied since the system has no
    permission to speak to upsd according to the access controls.

    There can be various reasons. To fix it, check:
    - the LISTEN directive in upsd.conf. It should allow your local or remote
      access method,
    - your firewall rules. Port 3493/tcp must be opened to incoming connexions,
    - your tcp-wrappers configuration (hosts.allow and hosts.deny).

    Refer to the upsd(8) and upsd.conf(5) manpages for more information.

-----------------------------------------------------------------------------

 Q: I have an APC Smart-UPS connected with a grey APC cable and it won't
    work.  The Back-UPS type in the genericups driver works but then I 
    don't get to use all the nifty features in there.  Why doesn't the 
    right driver work?

 A: The problem lies in your choice of cable.  APC's grey cables
    generally only do "dumb" signalling - very basic yes/no info about
    the battery and line status.  While that is sufficient to detect a
    low battery condition while on battery, you miss out on all the
    goodies that you paid for.

    Note that the 940-0095B happens to be a grey cable, but it is actually
    a dual mode cable and can be used in smart mode.  If you have
    this cable, you need to edit your ups.conf to look like this:

	[myups]
		driver = apcsmart
		port = /dev/whatever
		cable = 940-0095B

    All other grey cables from APC are assumed to be "dumb".

    If your grey cable isn't the 940-0095B, the solution is to dump that
    cable and find one that supports APC's "smart" signalling.  Typically
    these come with the UPS and are black.  If your smart cable has
    wandered off, one can be built rather easily with some connectors and
    cable - there's no fancy wiring or resistors.

    See this URL for a handy diagram:

    http://random.networkupstools.org/cables/940-0024C.jpg

    There is also a text version of that diagram in the docs/cables
    directory of the NUT source distribution.  Either one should allow
    you to build a good clone of APC's 940-0024C cable.
   
    There are simpler solutions involving 3 wires that work just fine
    too, but Powerchute won't find the loopback DTR-DCD and RTS-CTS and
    will be annoyed.  If you don't ever plan to use Powerchute, 3 wires
    (RxD, TxD, GND) are sufficient.

    It should also be noted that the genericups driver has no way to
    detect the UPS, so it will fire up quite happily if it can open the
    serial port.  Merely having it start up is not necessarily an
    indication of success.  You should start it and then check the
    status with upsc or similar to be sure that it's reading the
    hardware properly.

-----------------------------------------------------------------------------

 Q: Why does configure fail to find gd?

 A: Recent versions of gd should be detected automatically through the
    gdlib-config script.  Note that gd 2.0.5 through 2.0.7 have an
    unusable script, so upgrade to the newest version if you have one
    of those installed.

    If you're stuck with an older version of gd, you can use it if you
    specify the flags manually.  Look in gd's Makefile for "LIBS=", 
    then use that value when you call configure:

	./configure --with-gd-libs="<whatever>" --with-cgi

    If you don't have gd's Makefile available for some reason, you're
    in for a lot of trial and error.  

-----------------------------------------------------------------------------

 Q: Why PNG?  You used to generate GIF bars with upsimage back in 1998
    or 1999...

 A: http://www.burnallgifs.org/

-----------------------------------------------------------------------------

 Q: Why doesn't upsd implement the functionality of upsmon?  I have to
    run THREE programs to monitor my UPS!

 A: I try to follow the "tool for the job" philosophy.  It may mean
    more programs running, but the flexibility you get is usually
    worth it.

    Yes, the machine with the UPS attached will generally have 3
    processes (driver, upsd, upsmon) running, but this design allows a
    much bigger setup.  Imagine a data room with a bunch of machines
    all drawing power from the same UPS.  The rest of them just run
    upsmon.

    Besides, if upsmon were rolled into upsd, upsd would get even
    bigger than it is now.  You'd have one less process, but the
    RAM consumption would be pretty close to now.

    See data-room.txt for more configuration ideas and explanations.

 A: If this really bothers you, roll up your sleeves and use the
    sockdebug code to write a "upsmon" type program that sits on top of
    the state sockets.  It won't work over the network, but it means
    you don't need upsd.  It also means only one host can monitor the
    UPS. 

    This is also a good option to consider if you can't use networked
    monitoring code for security or safety reasons.

    See ideas.txt for more on this and other related topics.

-----------------------------------------------------------------------------

 Q: Why isn't upssched part of upsmon?

 A: Most users will never have any reason to use upssched.  It's
    complicated, and getting it right for your situation can be tricky.
    Having it live in a separate program saves resources and lets most
    people avoid it completely.

-----------------------------------------------------------------------------

 Q: Why doesn't upsmon send a SIGPWR signal to init so it can deal with
    power events?

 A: New versions of the init man page taken from the sysvinit package
    are saying that usage of SIGPWR is discouraged, since /dev/initctl 
    control channel is the preferred way of communication.

 A: The name of the game is portability.  Not everyone's init handles
    that kind of signalling gracefully.  What's more, some admins
    might want to do things differently even if they have that kind of
    init running.

    So, to be compatible, upsmon just invokes a shell command.  If you
    want to use init's SIGPWR stuff, just put the right "kill" line in
    a shell script and make upsmon call it.  Everyone wins.

-----------------------------------------------------------------------------

 Q: Why can't upsset read my upsset.passwd file?

 A: You have an old version of upsset installed, since the current
    version doesn't use that file.  Install a new version and then try
    it again.

    Be sure to secure your CGI directory as instructed in the
    upsset.conf.

-----------------------------------------------------------------------------

 Q: Why won't bestups talk to my Best Fortress UPS?

 A: There are at least two different protocols being used for hardware
    with very similar names.  The bestups driver tends to support the
    units built around the newer "PhoenixTec" protocol.  

    Previous releases of this software included a driver called
    bestfortress which supported the older Best hardware.  See the
    earlier entries about updating old drivers which have been removed
    from the tree.

-----------------------------------------------------------------------------

 Q: What's this about "data stale"?

 A: It means your UPS driver hasn't updated things in a little while.
    upsd refuses to serve up data that isn't fresh, so you get the
    errors about staleness.

    If this happens to you, make sure your driver is still running.
    Also look at the syslog.  Sometimes the driver loses the connection
    to the UPS, and that will also make the data go stale.

    Note: some very slow machines have trouble keeping up with the
    serial ports during periods of extreme load.  My old 486 used to
    flip between "stale" and "OK" while running backups.

    If this happens a lot, you might consider cranking up DEADTIME
    in the upsmon.conf to suppress some of the warnings for shorter
    intervals.  Use caution when adjusting this number, since it
    directly affects how long you run on battery without knowing
    what's going on with the UPS.

    Note: some drivers occasionally need more time to update than the
    default value of MAXAGE (in upsd.conf) allows.  As a result, they 
    are temporarily marked stale even though everything is fine.  This
    can happen with MGE Ellipse equipment - see the mge-shut man page.
    In such cases, you can raise the value of MAXAGE to avoid these
    warnings; try a value like 25 or 30.

-----------------------------------------------------------------------------

 Q: Why do the client programs say "Driver not connected" when I try
    to run them?

 A: This means that upsd can't connect to the driver for some reason.
    Your ups.conf entry might be wrong, or the driver might not be 
    running.  Maybe your state path is not configured properly.

    Check your syslog.  upsd will complain regularly if it can't
    connect to a driver, and it should say why it can't connect.

    Note: if you jumped in with both feet and didn't follow the INSTALL
    document, you probably started upsd by itself.  You have to run
    'upsdrvctl start' to start the drivers after configuring ups.conf.

-----------------------------------------------------------------------------

 Q: Everything works perfectly during the shutdown, and the UPS comes 
    back on, but my system stays off.  What's happening?

 A: Assuming you don't have the problem in the next question, then you
    probably have an ATX motherboard, have APM or ACPI enabled in your
    kernel (assuming Linux here), and are reaching the 'halt' at the
    bottom of your shutdown scripts.

    Your machine obeys and shuts down, and stays down, since it
    remembers the 'last state' when the UPS restarts.

    One solution is to change your shutdown scripts so you never reach
    that point.  You *want* the system to die without reaching the
    part where the kernel tells it to shut down.  A possible script
    might look like this:

	# other shutdown stuff here (mount -o remount,ro ...)

	if (test -f /etc/killpower)
	then
		/usr/local/ups/bin/upsdrvctl shutdown

		sleep 600	# this should never return

		# uh oh, we never got shut down! (power race?)
		reboot
	fi

	halt -p

    The other solution is to change your BIOS setting to "always power
    on" instead of "last state", assuming that's possible.

-----------------------------------------------------------------------------

 Q: My system has an ATX power supply.  It will power off just fine, but
    it doesn't turn back on.  What can I do to fix this?

 A: This depends on how clueful your motherboard manufacturer is, and
    isn't a matter of the OS.  You have to do one of the following
    things depending on what's supported:

    - Set a jumper on the motherboard that means "return after outage"

    - Set something in the BIOS that says "power up after power failure"

    - Try using something (like a capacitor) across the power button 
      to "push" it for you - this might not work if it needs a delay

    - Hack the cable between the power supply and the motherboard to fool
      it into powering up whenever line power is present

    - Teach a monkey to watch the machine and press the power button
      when the outage is over.

      This might work, but it creates high produce bills.

    If you can't use one of the first two options, give the board to
    an enemy.  Let them worry about it.

-----------------------------------------------------------------------------

 Q: My PowerMac G4 won't power back up by itself (into Linux) after the
    UPS shuts down.  What can I do about this?

 A: This is about the same situation as the ATX question above, only
    worse.  Earlier Macs apparently supported a hack where you could
    cat some magic characters at /dev/adb to enable "server mode".
    This would instruct the system to reboot while unattended.

    From Usenet post <6boftzxz51.fsf@ecc-office.sp.cs.cmu.edu>:

	# Send packet over the ADB bus to the PowerMac CUDA chip
	# telling it to reboot automatically when power is restored
	# after a power failure.

	cat /etc/local/autoboot.adb > /dev/adb

    autoboot.adb contains these three bytes (in hex):  01 13 01

    Unfortunately, the hardware has evolved and there is no good
    equivalent for this hack on today's systems.

    If you find out how to do this, please send me some mail, since
    this affects one of my systems and my stop-gap solution is getting
    cranky.

    Note: this question has been in the FAQ for over a year and 
    there's still no answer.  Let me guess: everyone who runs a server
    on Mac hardware has a team of trained monkeys, and feeds them
    by growing bananas in the tropical environment formed by waste heat
    from the equipment. 

    The rest of us are still waiting for the answer.  Booting into the
    Mac OS to frob the "file server" panel is not an acceptable
    solution.

 A: If you're on OS X, this is relatively simple to fix.  Go to system
    preferences, click on energy saver, click on the options tab, check
    "Restart automatically after a power failure".

    If you're on some other OS, hope they've figured out how to duplicate
    the above in a non-simian manner.

-----------------------------------------------------------------------------

 Q: I want to keep the drivers and upsd in their own security domains.
    How can this be accomplished?

 A: Using a few role accounts and a common group, you can limit access
    to resources such as the serial port(s) leading to the UPS
    hardware.

    This is just an example.  Change the values to suit your systems.

    Create a user called 'nutdev' and another called 'nutsrv'.  Put
    them both in a group called 'nut'.

    Change the owner of any serial ports that will be used to nutdev,
    and set the mode to 0600.  Then change the ownership of your state
    directory (usually /var/state/ups) to nutdev.nut.

    For my development system this yields the following /dev entries:

    0 crw-------   1 nutdev   tty        4,  64 Sep  3 17:11 /dev/ttyS0
    0 crw-------   1 nutdev   tty        4,  65 Sep  3 17:11 /dev/ttyS1

    Switch to root, then start the drivers:

    # /usr/local/ups/bin/upsdrvctl -u nutdev start

    The listing for /var/state/ups then looks like this:

    4 drwxrwx---   2 nutdev   nut          4096 Aug 20 18:37 .
    4 drwxr-xr-x   4 root     root         4096 May 14 21:20 ..
    4 srw-rw----   1 nutdev   nut             0 Sep  3 17:10 apcsmart-ttyS0
    4 srw-rw----   1 nutdev   nut             0 Sep  3 17:10 megatec-ttyS1

    You may have to remove old socket or state files first if you are
    changing to this security scheme from an older version.  The drivers
    will create new files with the right owners and modes.

    Note that /var/state/ups is group writable since upsd will
    place the upsd.pid file here.

    You may have to change the groups of upsd.conf and upsd.users to
    make them readable.  These files should not be owned by nutsrv,
    since someone could compromise the daemon and change the config
    files.  Instead, put nutsrv in a group ("nut" in this example), then
    make the files owned by root.nut, with mode 0640.

    Once the config files are ready, start upsd:

    # /usr/local/ups/sbin/upsd -u nutsrv

    Check your syslog to be sure everything's happy, then be sure to
    update your startup scripts so it uses this procedure on your next
    boot.

    If you like this, you'll probably also find the chroot process to
    be useful and interesting.  See chroot.txt for more details.

-----------------------------------------------------------------------------

 Q: What's the point of that 'security domains' concept above?

 A: The point is limiting your losses.  If someone should happen to
    break into upsd in that environment, they should only gain access
    to that one user account.  Direct access to the serial device is
    not possible, since that is owned by another user.

    There is also the possibility of running the drivers and upsd in a
    chroot jail.  See the chroot.txt provided in the source 
    distribution for an example implementation. 

    Why give would-be vandals any sort of help?

    Put it this way - I *wrote* good chunks of this stuff, and I still
    run the programs this way locally.  You should definitely consider
    using this technique.

-----------------------------------------------------------------------------

 Q: How can I make upsmon shut down my system after some fixed interval?

 A: You probably don't want to do this, since it doesn't maximize your
    runtime on battery.  Assuming you have a good reason for it (see
    the next entry), then look at upssched.txt or the upssched man
    page for some ideas.

-----------------------------------------------------------------------------

 Q: Why doesn't upsmon shut down my system?  I pulled the plug and nothing
    happened.

 A: Wait.  upsmon doesn't consider a UPS to be critical until it's both
    'on battery' and 'low battery' at the same time.  This is by design.
    Nearly every UPS supports the notion of detecting the low battery
    all by itself.  When the voltage drops below a certain point, it
    _will_ let you know about it.

    If your system has a really complicated shutdown procedure, you
    might need to shut down before the UPS raises the low battery flag.
    For most users, however, the default behavior is adequate.

    Ask yourself this: why buy a nice big UPS with the matching battery
    and corresponding runtime and then shutdown early?  If anything, I'd
    rather have a few more minutes running on battery during which the
    power might return.  Once the power's back, it's business as usual
    with no visible interruption in service.

    If you purposely shut down early, you guarantee an interruption in
    service by bringing down the box.

    See upssched.txt for information on how you can shutdown early if
    this is what you really want to do.

-----------------------------------------------------------------------------

 Q: The CGI programs report "access to that host is not authorized" - 
    what's going on?

 A: Those programs need to see a host in your hosts.conf before they
    will attempt communications.  This keeps people from feeding it
    random "host=" settings, which would annoy others with outgoing
    connection attempts from your system.

    If your hosts.conf turns out to be configured correctly with 
    MONITOR entries and all that, check the permissions.  Your web
    server may be running the CGI programs as a user that can't read
    the file.

    If you run your web server in a chroot jail, make sure the programs
    can still read hosts.conf.  You may have to copy it into the jail
    for this to work.  If you do that, make sure it's not writable by
    any of the user accounts which run inside the jail.   

-----------------------------------------------------------------------------

 Q: upsd is running, so why can't I connect to it?

 A: Assuming you haven't changed the TCP port number on the command line
    or at compile-time, then you probably have some sort of firewall
    blocking the connection.

    upsd listens on TCP port 3493 by default.

-----------------------------------------------------------------------------

 Q: How do you make upsmon reload the config file?

 Q: How do you make upsd reload the config file?

 A: Either find the pid of the background process and send it a SIGHUP,
    or just start it again with '-c reload'.

    If you send the signals yourself instead of using -c, be sure you
    hit the right process.  There are usually two upsmons, and you
    should only send signals to one of them.  To be safe, read the pid
    file.

-----------------------------------------------------------------------------

 Q: I just bought a new WhizBang UPS that has a USB connector.  How do
    I monitor it?

 A: There are several driver to support USB models.

    - usbhid-ups supports various manufacturers complying to the HID standard,
    - tripplite_usb supports various Tripp-Lite units,
    - bcmxcp_usb supports various Powerware units.

    Refer to the "driver-name" (8) manpage for more information.

-----------------------------------------------------------------------------

 Q: What is this usbhid-ups (formerly newhidups) about?

 A: The basic USB UPS support was done until NUT 2.2 using hidups. To allow
    a wider support accross platforms for USB/HID compliant devices,
    usbhid-ups driver uses libusb (which is available for a wide range of
    operating systems) and libhid (currently, a modified internal version
    of it).

    As of NUT 2.2, usbhid-ups completely replaces the legacy hidups driver
    and provide support for various manufacturers. At that time, it will
    be renamed to usbhid-ups.

    usbhid-ups is built automatically if possible (libusb development files
    need to be installed) and installed by the "make install" command.

-----------------------------------------------------------------------------

 Q: Why doesn't my package work?

 Q: I can't run this because there's no package for it.  Why isn't this
    in a package yet?

 A: Sorry, can't help you there.  All official releases are source code
    and are posted on http://www.networkupstools.org/ along with PGP
    signatures for verification.

    This means all packages have been built by a third party.  If you
    have an issue that's related to packaging, you will need to seek
    help with whoever built it for you.

-----------------------------------------------------------------------------

 Q: Why are there two copies of upsmon running?

 A: It's not really two complete copies if your OS forks efficiently.

    By default, upsmon runs most of the grunt work as an unprivileged
    user and keeps a stub process around with root powers that can
    only shut down the system when necessary.  This should make it much
    harder to gain root in the event a hole is ever discovered in
    upsmon.

    If this really bothers you and you like running lots of code as
    root, start upsmon with -p and it will go back to being one big
    process.  This is not recommended, so don't blame me if something
    bad happens in this mode.

-----------------------------------------------------------------------------

 Q: I have <some problem> with <some old version> ...

 A: Get the latest stable release, and see if it still happens.  If it
    goes away, it means someone else reported it and got it fixed a 
    long time ago.

    If that doesn't work, try the latest development version.

    If your problem is STILL there, then contact the mailing lists.

    Hint: check the release date on the version you have.  If it's more
    than about 6 months old, there's probably a newer stable tree
    version out there.

-----------------------------------------------------------------------------

 Q: Do you have to use a serial connection to monitor the UPS?
    What about direct network connections (SNMP or otherwise)?

 A: No. NUT currently support USB communication through usbhid-ups,
    tripplite_usb and bcmxcp_usb, and SNMP communication through snmp-ups.

    Any time there is a gap in features, it's usually because the
    group of people who own that hardware and the group of people who
    write code don't overlap.  The fix is to make them overlap -
    turn an owner into a developer or vice-versa.

-----------------------------------------------------------------------------

 Q: What happened to the patch I sent?

 A: If a release goes by and your patch hasn't been included, it was
    probably dropped.  There can be a lot of patches waiting for 
    inclusion at some points, and occasionally some have to be
    rejected.

    Design issues or severe coding style problems can be the reason
    for this.  I try to point out what the problems are, but there are
    limits.  See developers.txt for some pointers on submitting
    patches.

    Sometimes patches are put on hold due to a feature freeze.  If it
    doesn't show up once the new version opens up, send it again.

-----------------------------------------------------------------------------

 Q: I'm not much of a programmer.  How can I help?

 A: There's always work to be done outside of the realm of code bashing.
    Documentation might not always be so clear.  A user's perspective
    is sometimes needed to appreciate this.  Bug reports on a project's
    documentation are just as valuable as those for the actual source.

    Fielding questions on the mailing lists is also helpful.  This
    lets other people to focus on coding issues while allowing the
    original poster to get some information at the same time.  It's
    quite a relief to open that mailbox and find that someone else
    has already handled it successfully.

-----------------------------------------------------------------------------

 Q: I replaced the battery in my APC Smart-UPS and now it thinks the 
    battery is low all the time.  How do you fix this?

 Q: My APC UPS keeps reporting "OL LB", even after it's been charging
    for many hours.  What can I do about this?

 A: This happened to me, and some other people too.  The combination of
    our experiences should prove useful to you.

    First, you need to realize that the UPS apparently stores data about
    the battery, load, and runtime.  After replacing the battery, it
    needs to be clued in to the new situation.  If the traditional
    runtime calibration doesn't work, you have to try something a
    little more drastic.

    You need to *completely* drain the UPS while it has a good ground.
    This means you can't just pull the plug.  You also have to
    disconnect it from the computer so this software won't shut it
    down.

    The easiest way to do this is to first unplug your computer(s) from
    it, and plug in a token load like a lamp.  Also, move the UPS to a 
    power strip that doesn't switch the ground line or an outlet that
    you can switch off at your panel.

    Once the UPS is up at 100% charge (this is important), disconnect
    the power.  It _must_ remain connected to the ground, or the
    results may not be accurate.  Ignore the sounds it makes, and go
    away until it's done.  Don't do anything to the front panel while
    this is happening.

    After all of this, put things back the way they should be and let
    it charge up.  You should find that it again gives reasonable
    values and behavior, as it was when it was new.

    Thanks to Matthew Dharm for helping me nail down this procedure.

-----------------------------------------------------------------------------

 Q: multimon.cgi seems to be stuck at an old version, even though I
    just installed a new one.

 A: multimon was removed during the 1.1 development cycle.  upsstats
    now does everything it used to do, and then some.  You should just
    delete those files and start using upsstats directly.

-----------------------------------------------------------------------------

 Q: OK, I switched to upsstats.  Now it's giving me Celsius.  I like
    Fahrenheit.  Where's the config file to switch it back?

 A: Temperature scales are handled by the template files, so edit your
    upsstats.html and change it from TEMPC to TEMPF.

-----------------------------------------------------------------------------

 Q: Why is the mailing list ignoring me?

 A: You probably asked a question that's answered in this FAQ or
    somewhere else in the documentation and nobody wants to quote it
    for you.

    Convincing the other subscribers that you've actually read down this
    far might be useful.  You might mention "queequeg" for better results.

    This URL may also be helpful:

	http://www.catb.org/~esr/faqs/smart-questions.html

-----------------------------------------------------------------------------

 Q: I found some information about another kind of UPS protocol you
    don't support yet, but I don't know what to do with it.  Can you
    help?

 A: If you're not a programmer, you can still help others by making
    that protocol available.  You might host the document somewhere and
    send the URL to one of the mailing lists.

-----------------------------------------------------------------------------

 Q: How can you answer questions to situations that nobody's encountered
    yet?  Isn't this a frequently asked questions file?

 A: Magic.

 A: It's both that and a frequently *anticipated* questions file, too.

    The idea is to write it up in here so that nobody asks the mailing
    list when it finally does get released.  

-----------------------------------------------------------------------------