'\" t .\" Title: powercom .\" Author: [see the "AUTHOR" section] .\" Generator: DocBook XSL Stylesheets v1.76.1 .\" Date: 07/26/2013 .\" Manual: NUT Manual .\" Source: Network UPS Tools 2.6.5 .\" Language: English .\" .TH "POWERCOM" "8" "07/26/2013" "Network UPS Tools 2\&.6\&.5" "NUT Manual" .\" ----------------------------------------------------------------- .\" * Define some portability stuff .\" ----------------------------------------------------------------- .\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ .\" http://bugs.debian.org/507673 .\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html .\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ .ie \n(.g .ds Aq \(aq .el .ds Aq ' .\" ----------------------------------------------------------------- .\" * set default formatting .\" ----------------------------------------------------------------- .\" disable hyphenation .nh .\" disable justification (adjust text to left margin only) .ad l .\" ----------------------------------------------------------------- .\" * MAIN CONTENT STARTS HERE * .\" ----------------------------------------------------------------- .SH "NAME" powercom \- UPS driver for serial Powercom/Trust/Advice UPS equipment .SH "NOTE" .sp This man page only documents the hardware\-specific features of the powercom driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&. .SH "SUPPORTED HARDWARE" .sp This driver supports many similar kinds of serial UPS hardware (as well as a few USB UPS models with USB\-to\-serial adapters)\&. The most common ones are the Trust 425/625, Powercom, and Advice Partner/King PR750\&. Others using the same protocol may also work\&. For USB connections, you might need \fBusbhid-ups\fR(8)\&. .sp For more specific guidance on which driver is applicable for a USB connection, see the NUT Hardware Compatibility List (HCL)\&. .SH "EXTRA ARGUMENTS" .sp This driver supports the following optional settings in the \fBups.conf\fR(5) file: .PP \fBlinevoltage\fR=\fIvalue\fR .RS 4 An integer specifying the line voltage\&. It can\(cqt be auto detected\&. Acceptable values are in the range of 110\-120 or 220\-240\&. The default is \fI230\fR\&. .RE .PP \fBmanufacturer\fR=\fIname\fR .RS 4 Specify the manufacturer name, which also can\(cqt be auto detected\&. This is a user defined string, so any name is acceptable\&. The default is \fIPowerCom\fR\&. .RE .PP \fBmodelname\fR=\fIname\fR .RS 4 Specify the model name, which also can\(cqt be auto detected\&. This is a user defined string, so any name is acceptable\&. The default is \fIUnknown\fR\&. .RE .PP \fBserialnumber\fR=\fIvalue\fR .RS 4 Like modelname above, but for the serial number\&. The default is \fIUnknown\fR\&. .RE .PP \fBtype\fR=\fIname\fR .RS 4 The exact type of the communication protocol within the powercom family, that will be used to communicate with the UPS\&. The type is named after the first modelname that was coded with that protocol\&. The acceptable names are \fITrust\fR, \fIEgys\fR, \fIKP625AP\fR, \fIIMP\fR, \fIKIN\fR, \fIBNT\fR, and \fIBNT\-other\fR\&. The default is \fITrust\fR\&. .sp \fIBNT\-other\fR is a special type for other BNT models (such as the 1500A at 120V and can be used to override ALL models using ALL of the following values\&. .RE .PP \fBshutdownArguments\fR={{\fIminutes\fR,\fIseconds\fR},\fIwhether_minutes_should_be_used\fR} .RS 4 The minutes and seconds that the UPS should wait between receiving the shutdown command and actually shutting off\&. The other argument should be set to the character \fIn\fR only when the minutes value should be skipped and not sent to the UPS\&. The default is type\-dependent and is given below\&. The braces and commas are mandatory\&. Note that there should be no whitespace characters\&. .RE .PP \fBnumOfBytesFromUPS\fR=\fIvalue\fR .RS 4 The number of bytes in a UPS frame: 16 is common, 11 for \fITrust\fR\&. The default is type\-dependent and is given below\&. .RE .PP \fBmethodOfFlowControl\fR=\fIname\fR .RS 4 The method of serial communication flow control that is engaged by the UPS\&. The default is type\-dependent and is given below\&. Acceptable names are \fIdtr0rts1\fR, \fIdtr1\fR or \fIno_flow_control\fR\&. .RE .PP \fBvalidationSequence\fR={{\fIindex1\fR,\fIvalue1\fR},{\fIindex2\fR,\fIvalue2\fR},{\fIindex3\fR,\fIvalue3\fR}} .RS 4 (Only for types KP625AP, Trust, Egys\&.) 3 pairs to be used for validating the UPS by comparing bytes of the raw data with constant values\&. The index selects the byte from the UPS (see numOfBytesFromUPS) and the value is for matching to the byte\&. The default is type\-dependent and is given below\&. The braces and commas are mandatory, as the lack of white space characters\&. .RE .PP \fBfrequency\fR={\fIA\fR,\fIB\fR} .RS 4 (Only for types KP625AP, Trust, Egys\&.) A pair to convert the raw frequency data to a human\-readable frequency reading using the function 1/(A*x+B)\&. If the raw value x IS the frequency, then set A=1/(x^2) and B=0\&. The default is type\-dependent and is given below\&. Do note that the braces and commas are mandatory as well, as the lack of whitespace characters\&. .RE .PP \fBloadPercentage\fR={\fIBatteryA\fR,\fIBatteryB\fR,\fILineA\fR,\fILineB\fR} .RS 4 (Only for types KP625AP, Trust, Egys\&.) A quad to convert the raw load data to human readable load percentage reading using the function A*x+B\&. If the raw value x IS the Load Percent, then set A=1 and B=0\&. The default is type\-dependent and is given below\&. Do note that the braces and commas are mandatory, as the lack of white space characters\&. .RE .PP \fBbatteryPercentage\fR={\fIBattery1\fR,\fIBattery2\fR,\fIBattery3\fR,\fILine4\fR,\fILine5\fR} .RS 4 (Only for KP625AP, Trust, Egys\&.) A 5 tuple to convert the raw battery and line data to a human\-readable battery and line percentage reading using the functions (Battery) A*x+B*y+C and (Line) D*x+E\&. If the raw value x IS the Battery Percent, then set A=1, B=0, C=0, D=1, E=0\&. The default is type\-dependent and is given below\&. Do note that the braces and commas are mandatory, as the lack of white space characters\&. .RE .PP \fBvoltage\fR={\fI240A\fR,\fI240B\fR,\fI120A\fR,\fI120B\fR} .RS 4 (Only for types KP625AP, Trust, Egys\&.) A quad that is used convert the raw voltage data to a human\-readable voltage reading using the function A*x+B\&. If the raw value x IS HALF the Voltage, then set A=2, B=0\&. The default is type\-dependent and is given below\&. Do note that the braces and commas are mandatory, as well as the lack of whitespace characters\&. .RE .SH "DEFAULT VALUES FOR THE EXTRA ARGUMENTS" .sp .if n \{\ .RS 4 .\} .nf linevoltage = 230 manufacturer = PowerCom modelname = Unknown serialnumber = Unknown type = Trust .fi .if n \{\ .RE .\} .sp The rest of the default values for the extra arguments are type\-dependent\&. However, \fIBNT\-other\fR is a special type that can be used to override ALL values for ALL models\&. .SS "Trust" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 11 methodOfFlowControl = dtr0rts1 validationSequence = {{5,0},{7,0},{8,0}} shutdownArguments = {{0,10},n} frequency = {0\&.00020997,0\&.00020928} loadPercentage = {6\&.1343,\-0\&.3808,4\&.3110,0\&.1811} batteryPercentage = {5\&.0000,0\&.3268,\-825\&.00,4\&.5639,\-835\&.82} voltage = {1\&.9216,\-0\&.0977,0\&.9545,0\&.0000} .fi .if n \{\ .RE .\} .SS "KP625AP" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = dtr0rts1 validationSequence = {{5,0x80},{7,0},{8,0}} shutdownArguments = {{0,10},n} frequency = {0\&.00020997,0\&.00020928} loadPercentage = {6\&.1343,\-0\&.3808,4\&.3110,0\&.1811} batteryPercentage = {5\&.0000,0\&.3268,\-825\&.00,4\&.5639,\-835\&.82} voltage = {1\&.9216,\-0\&.0977,0\&.9545,0\&.0000} .fi .if n \{\ .RE .\} .SS "Egys" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = no_flow_control validationSequence = {{5,0x80},{7,0},{8,0}} shutdownArguments = {{0,10},n} frequency = {0\&.00020997,0\&.00020928} loadPercentage = {6\&.1343,\-0\&.3808,1\&.3333,0\&.6667} batteryPercentage = {5\&.0000,0\&.3268,\-825\&.00,2\&.2105,\-355\&.37} voltage = {1\&.9216,\-0\&.0977,0\&.9545,0\&.0000} .fi .if n \{\ .RE .\} .SS "IMP" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = no_flow_control validationSequence = {{5,0xFF},{7,0},{8,0}} shutdownArguments = {{1,30},y} .fi .if n \{\ .RE .\} .SS "KIN" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = no_flow_control validationSequence = {{11,0x4b},{8,0},{8,0}} shutdownArguments = {{1,30},y} .fi .if n \{\ .RE .\} .SS "BNT" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = no_flow_control validationSequence = {{11,0x42},{8,0},{8,0}} shutdownArguments = {{1,30},y} .fi .if n \{\ .RE .\} .SS "BNT\-other" .sp .if n \{\ .RS 4 .\} .nf numOfBytesFromUPS = 16 methodOfFlowControl = no_flow_control validationSequence = {{8,0},{8,0},{8,0}} shutdownArguments = {{1,30},y} frequency = {0\&.00027778,0\&.0000} loadPercentage = {1\&.0000,0\&.0,1\&.0000,0\&.0} batteryPercentage = {1\&.0000,0\&.0000,0\&.0000,1\&.0000,0\&.0000} voltage = {2\&.0000,0\&.0000,2\&.0000,0\&.0000} .fi .if n \{\ .RE .\} .SH "AUTHOR" .sp Peter Bieringer , Alexey Sidorov , Keven L\&. Ates .SH "SEE ALSO" .SS "The core driver:" .sp \fBnutupsdrv\fR(8) .SS "Internet resources:" .sp The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/