device: General unit information
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
NOTE: these data will be redundant with some ups.* information
NOTE: some of these data will be redundant with ups.* information
during a transition period. The ups.* data will then be removed.
[options="header"]
|========================================================================
| Name | Description | Example value
| device.model | Device model | BladeUPS
| device.mfr | Device manufacturer | Eaton
| device.serial | Device serial number (opaque string) | WS9643050926
| device.type | Device type (ups, pdu, scd) | ups
|========================================================================
|====================================================================================
| Name | Description | Example value
| device.model | Device model | BladeUPS
| device.mfr | Device manufacturer | Eaton
| device.serial | Device serial number (opaque string) | WS9643050926
| device.type | Device type (ups, pdu, scd, psu) | ups
| device.description | Device description (opaque string) | Some ups
| device.contact | Device administrator name (opaque string) | John Doe
| device.location | Device physical location (opaque string) | 1rst floor
| device.part | Device part number (opaque string) | 123456789
| device.macaddr | Physical network address of the device | 68:b5:99:f5:89:27
|=====================================================================================
ups: General unit information
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
@ -110,6 +115,10 @@ ups: General unit information
(enabled or disabled) | yes
|===============================================================================
NOTE: When present, the value of *ups.start.auto* has an impact on shutdown.*
commands. For the sake of coherence, shutdown commands will set *ups.start.auto*
to the right value before issuing the command. Ie, shutdown.stayoff will first
set *ups.start.auto* to *no*, while shutdown.return will set it to *yes*.
input: Incoming line/power information
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
@ -240,7 +249,7 @@ Valid with/without context (ie. per phase or aggregated/averaged)
| current | Current (A)
| current.maximum | Maximum seen current (A)
| current.minimum | Minimum seen current (A)
| peakcurrent | Peak current
| current.peak | Peak current
| voltage | Voltage (V)
| voltage.nominal | Nominal voltage (V)
| voltage.maximum | Maximum seen voltage (V)
@ -295,36 +304,40 @@ battery: Any battery details
[options="header"]
|===============================================================================
| Name | Description | Example value
| battery.charge | Battery charge (percent) | 100.0
| Name | Description | Example value
| battery.charge | Battery charge (percent) | 100.0
| battery.charge.low | Remaining battery level when
UPS switches to LB (percent) | 20
UPS switches to LB (percent) | 20
| battery.charge.restart | Minimum battery level for
UPS restart after power-off | 20
UPS restart after power-off | 20
| battery.charge.warning | Battery level when UPS switches
to "Warning" state (percent) | 50
| battery.voltage | Battery voltage (V) | 24.84
| battery.capacity | Battery capacity (Ah) | 7.2
| battery.current | Battery current (A) | 1.19
| battery.temperature | Battery temperature (degrees C) | 050.7
| battery.voltage.nominal | Nominal battery voltage (V) | 024
| battery.runtime | Battery runtime (seconds)
Remaining battery runtime | 1080
| battery.runtime.low | when UPS switches to LB
(seconds) | 180
| battery.alarm.threshold | Battery alarm threshold | 0 (immediate)
| battery.date | Battery change date (opaque
string) | 11/14/00
to "Warning" state (percent) | 50
| battery.voltage | Battery voltage (V) | 24.84
| battery.voltage.nominal | Nominal battery voltage (V) | 024
| battery.voltage.low | Minimum battery voltage, that
triggers FSD status | 21,52
| battery.voltage.high | Maximum battery voltage
(Ie battery.charge = 100) | 26,9
| battery.capacity | Battery capacity (Ah) | 7.2
| battery.current | Battery current (A) | 1.19
| battery.temperature | Battery temperature (degrees C) | 050.7
| battery.runtime | Battery runtime (seconds) | 1080
| battery.runtime.low | Remaining battery runtime when
UPS switches to LB (seconds) | 180
| battery.runtime.restart | Minimum battery runtime for UPS
restart after power-off (seconds) | 120
| battery.alarm.threshold | Battery alarm threshold | 0 (immediate)
| battery.date | Battery change date (opaque string) | 11/14/00
| battery.mfr.date | Battery manufacturing date
(opaque string) | 2005/04/02
| battery.packs | Number of battery packs | 001
| battery.packs.bad | Number of bad battery packs | 000
(opaque string) | 2005/04/02
| battery.packs | Number of battery packs | 001
| battery.packs.bad | Number of bad battery packs | 000
| battery.type | Battery chemistry (opaque
string) | PbAc
string) | PbAc
| battery.protection | Prevent deep discharge of
battery | yes
battery | yes
| battery.energysave | Switch off when running on
battery and no/low load | no
battery and no/low load | no
|===============================================================================
@ -385,13 +398,19 @@ represent the whole set of outlets of the device.
| outlet.n.autoswitch.charge.low | Remaining battery level to
power off this outlet
(percent) | 80
| outlet.n.battery.charge.low | Remaining battery level to
power off this outlet
(percent) | 80
| outlet.n.delay.shutdown | Interval to wait before
shutting down this outlet
(seconds) | 180
| outlet.n.delay.start | Interval to wait before
restarting this outlet
(seconds) | 120
(seconds) | 120
| outlet.n.timer.shutdown | Time before the outlet load
will be shutdown (seconds) | 20
| outlet.n.timer.start | Time before the outlet load
will be started (seconds) | 30
| outlet.n.current | Current (A) | 0.19
| outlet.n.current.maximum | Maximum seen current (A) | 0.56
| outlet.n.realpower | Current value of real
@ -406,7 +425,6 @@ represent the whole set of outlets of the device.
| outlet.n.power | Apparent power (VA) | 46
|===============================================================================
driver: Internal driver information
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
@ -442,6 +460,8 @@ Instant commands
| Name | Description
| load.off | Turn off the load immediately
| load.on | Turn on the load immediately
| load.off.delay | Turn off the load possibly after a delay
| load.on.delay | Turn on the load possibly after a delay
| shutdown.return | Turn off the load possibly after a delay
and return when power is back
| shutdown.stayoff | Turn off the load possibly after a delay
@ -468,4 +488,9 @@ Instant commands
| beeper.disable | Disable UPS beeper/buzzer
| beeper.mute | Temporarily mute UPS beeper/buzzer
| beeper.toggle | Toggle UPS beeper/buzzer
| outlet.n.shutdown.return | Turn off the outlet possibly after a delay
and return when power is back
| outlet.n.load.off | Turn off the outlet immediately
| outlet.n.load.on | Turn on the outlet immediately
| outlet.n.load.cycle | Power cycle the outlet immediately
|========================================================================