Imported Upstream version 2.7.3
This commit is contained in:
parent
a356b56d11
commit
fd413a3168
283 changed files with 14978 additions and 6511 deletions
83
docs/man/asem.txt
Normal file
83
docs/man/asem.txt
Normal file
|
|
@ -0,0 +1,83 @@
|
|||
ASEM(8)
|
||||
=======
|
||||
|
||||
NAME
|
||||
----
|
||||
asem - driver for UPS in ASEM PB1300
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the hardware-specific features of the
|
||||
*asem* driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
The *asem* driver supports the UPS in ASEM PB1300 embedded PCs. Likely other
|
||||
I2C devices from the same manufacturer will work too, since this is a "custom"
|
||||
charger.
|
||||
|
||||
Seems that there are two versions of the charger. Older one is based on
|
||||
Max1667, newer one is a custom solution. Both are on I2C address 0x09.
|
||||
To be compatible with both versions, the driver just reads bit 15 of address
|
||||
0x13 which yields online/on battery status.
|
||||
Battery monitor is a BQ2060 at address 0x0B.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
|
||||
The required parameter for this driver is the I2C bus name:
|
||||
|
||||
*port*='dev-node'::
|
||||
On the Asem PB1300, this should be `/dev/i2c-7` for the i801 SMBUS adapter.
|
||||
|
||||
This driver also supports the following optional settings:
|
||||
|
||||
*lb*='num'::
|
||||
Set the low battery threshold to 'num' volts.
|
||||
|
||||
*hb*='num'::
|
||||
Set the high battery threshold to 'num' volts.
|
||||
|
||||
INSTALLATION
|
||||
------------
|
||||
This driver is specific to the Linux I2C API, and requires the lm_sensors
|
||||
libi2c-dev or its equivalent to compile.
|
||||
|
||||
Beware that the SystemIO memory used by the I2C controller is reserved by ACPI.
|
||||
If only a native I2C driver (e.g. i2c_i801, as of 3.5.X Linux kernels) is
|
||||
available, then you'll need to relax the ACPI resources check. For example, you
|
||||
can boot with the `acpi_enforce_resources=lax` option.
|
||||
|
||||
//////////////////////////////////////////
|
||||
Optional: use DIAGNOSTICS to describe troubleshooting techniques that are
|
||||
longer than what can be conveniently described in the driver error messages.
|
||||
|
||||
DIAGNOSTICS
|
||||
-----------
|
||||
|
||||
//////////////////////////////////////////
|
||||
|
||||
KNOWN ISSUES AND BUGS
|
||||
---------------------
|
||||
The driver shutdown function is not implemented, so other arrangements must be
|
||||
made to turn off the UPS.
|
||||
|
||||
AUTHORS
|
||||
-------
|
||||
Giuseppe Corbelli <giuseppe.corbelli@copanitalia.com>
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver:
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
Internet resources:
|
||||
~~~~~~~~~~~~~~~~~~~
|
||||
PB1300 specifications: http://www.asem.it/en/products/industrial-automation/box-pcs/performance/pb1300/
|
||||
|
||||
BQ2060 datasheet: http://www.ti.com/lit/ds/symlink/bq2060.pdf
|
||||
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||