NUT outlets management and PDU notes
|
||||
====================================
|
||||
|
||||
NUT supports advanced outlets management for any kind of device that proposes
|
||||
it. This chapter introduces how to manage outlets in general, and how to take
|
||||
advantage of the provided features.
|
||||
|
||||
Introduction
|
||||
------------
|
||||
|
||||
Outlets are the core of Power Distribution Units. They allow you to turn on,
|
||||
turn off or cycle the load on each outlet.
|
||||
|
||||
Some UPS models also provide manageable outlets (Eaton, MGE, Powerware,
|
||||
Tripplite, ...) that help save power in various ways, and manage loads more
|
||||
intelligently.
|
||||
|
||||
Finally, some devices can be managed in a PDU-like way. Consider blade systems:
|
||||
the blade chassis can be controlled remotely to turn on, turn off or
|
||||
cycle the power on individual blade servers.
|
||||
|
||||
NUT allows you to control all these devices!
|
||||
|
||||
|
||||
NUT outlet data collection
|
||||
--------------------------
|
||||
|
||||
NUT provides a complete and uniform integration of outlets related data,
|
||||
through the 'outlet' collection.
|
||||
|
||||
First, there is a special outlet, called 'main outlet'.
|
||||
You can access it through 'outlet.{id, desc, ...}' without any index.
|
||||
|
||||
Any modification through the 'main outlet' will affect *all* outlets.
|
||||
For example, calling the command 'outlet.load.cycle' will cycle all outlets.
|
||||
|
||||
Next, outlets index starts from *1*. Index '0' is implicitly reserved to
|
||||
the 'main outlet'. So the first outlet is 'outlet.1.*'.
|
||||
|
||||
For a complete list of outlet data and commands, refer to the
|
||||
<<nut-names,NUT command and variable naming scheme>>.
|
||||
|
||||
An example upsc output (data/epdu-managed.dev) is available in the source
|
||||
archive.
|
||||
|
||||
NOTE: The variables supported depend on the exact device type.
|
||||
|
||||
|
||||
Outlets on PDU
|
||||
--------------
|
||||
|
||||
Smart Power Distribution Units provide at least various meters, related to
|
||||
current, power and voltage.
|
||||
|
||||
Some more advanced devices also provide control through the 'load.off',
|
||||
'load.on' and 'load.cycle' commands.
|
||||
|
||||
Outlets on UPS
|
||||
--------------
|
||||
|
||||
Some advanced Uninterruptible Power Supplies provide smart outlet management.
|
||||
|
||||
This allows to program a limited backup time to non-critical loads in order
|
||||
to keep the maximum of the battery reserve for critical equipment.
|
||||
|
||||
This also allows the same remote electrical management of devices provided
|
||||
by PDUs, which can be very interesting in Data Centers.
|
||||
|
||||
For example, on small setup, you can plug printers, USB devices, hubs, (...)
|
||||
into managed outlets. Depending on your UPS's capabilities, you will be able to
|
||||
turn off those loads:
|
||||
|
||||
- after some minutes of back-up time using 'outlet.n.delay.start',
|
||||
- when reaching a percentage battery charge using
|
||||
'outlet.n.autoswitch.charge.low'.
|
||||
|
||||
This will ensure a maximum runtime for the computer.
|
||||
|
||||
On bigger systems, with bigger UPSs, this is the same thing with servers
|
||||
instead of small devices.
|
||||
|
||||
NOTE: If you need the scheduling function and your device doesn't support
|
||||
it, you can still use
|
||||
<<Advanced_usage_scheduling_notes,NUT scheduling features>>.
|
||||
|
||||
WARNING: don't plug the UPS's communication cable (USB or network) on a managed outlet.
|
||||
Otherwise, all computers will be stopped as soon as the communication is lost.
|
||||
|
||||
Other type of devices
|
||||
---------------------
|
||||
|
||||
As mentioned in the introduction, some other devices can be considered and managed like
|
||||
PDUs. This is the case in most blade systems, where the blade chassis offers
|
||||
power management services.
|
||||
|
||||
This way, you can control remotely each blade server as if it were a PDU
|
||||
outlet.
|
||||
|
||||
This category of devices is generally called Remote Power Controls - RPC in NUT.
|
||||