RICHCOMM_USB(8)
|
||||
===============
|
||||
|
||||
NAME
|
||||
----
|
||||
richcomm_usb - Driver UPS equipment using Richcomm dry-contact to USB
|
||||
solution
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the specific features of the richcomm_usb
|
||||
driver. For information about the core driver, see linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
The Richcomm dry-contact to USB solution is a generic interface that is
|
||||
used to upgrade an existing (RS-232) contact closure UPS interface to USB.
|
||||
As such, all the limitations of the underlying contact closure interface
|
||||
apply. This means that you will only get the essentials in ups.status: OL,
|
||||
OB, and LB. See also linkman:genericups[8].
|
||||
|
||||
BUGS
|
||||
----
|
||||
Most contact-closure UPSes will not power down the load if the line power
|
||||
is present. This can create a race when using slave linkman:upsmon[8]
|
||||
systems. See the linkman:upsmon[8] man page for more information.
|
||||
|
||||
The solution to both of these problems is to upgrade to a smart protocol
|
||||
UPS of some kind that allows detection and proper load cycling on command.
|
||||
|
||||
AUTHORS
|
||||
-------
|
||||
|
||||
Peter van Valderen <p.v.valderen at probu.nl>,
|
||||
Dirk Teurlings <dirk at upexia.nl>
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver:
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
The generic serial driver:
|
||||
~~~~~~~~~~~~~~~~~~~~~~~~~~
|
||||
linkman:genericups[8]
|
||||
|
||||
Internet resources:
|
||||
~~~~~~~~~~~~~~~~~~~
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||