POWERPANEL(8)
|
||||
=============
|
||||
|
||||
NAME
|
||||
----
|
||||
|
||||
powerpanel - Driver for PowerPanel Plus compatible UPS equipment
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the hardware-specific features of the
|
||||
powerpanel driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
This driver supports CyberPower BC1200, PR2200 and many other similar
|
||||
devices, both for the text and binary protocols. The driver will
|
||||
autodetect which protocol is used.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
This driver supports the following optional settings in linkman:ups.conf[5]:
|
||||
|
||||
*protocol=*['text,binary']::
|
||||
Override the default autodetection of the protocol.
|
||||
|
||||
*manufacturer=*'value'::
|
||||
If you don't like the autodetected value, you can override this by setting
|
||||
it here.
|
||||
|
||||
*model=*'value'::
|
||||
Like manufacturer above.
|
||||
|
||||
*serial=*'value'::
|
||||
Like manufacturer above.
|
||||
|
||||
*ondelay=*'value'::
|
||||
Time to wait before switching on the UPS (1 - 9999 minutes, 0=indefinite).
|
||||
Only available with the text protocol driver (see <<_support_status,Support Status>>).
|
||||
|
||||
*offdelay=*'value'::
|
||||
Time to wait before shutting down the UPS (6 - 600 seconds). Values below 60
|
||||
seconds will be truncated to 6 seconds intervals, values above 60 seconds to
|
||||
60 seconds intervals. Only available with the text protocol driver (see
|
||||
<<_support_status,Support Status>>).
|
||||
|
||||
VARIABLES
|
||||
---------
|
||||
Depending on the type of your UPS unit, some of the following variables may
|
||||
be changed with linkman:upsrw[8]. If the driver can't read a variable from the
|
||||
UPS, it will not be made available.
|
||||
|
||||
*input.transfer.high*::
|
||||
writable: high transfer voltage point in V
|
||||
|
||||
*input.transfer.low*::
|
||||
writable: low transfer voltage point in V
|
||||
|
||||
*battery.charge.low*::
|
||||
writable: remaining battery charge percentage for low battery warning
|
||||
|
||||
*output.voltage.nominal*::
|
||||
writable: nominal output voltage in V
|
||||
|
||||
*ups.start.battery*::
|
||||
writable: allow cold start from battery
|
||||
|
||||
COMMANDS
|
||||
--------
|
||||
Depending on the type of your UPS unit, some of the following commands may
|
||||
be available.
|
||||
|
||||
* test.battery.start.quick, test.battery.stop
|
||||
|
||||
* beeper.enable, beeper.disable, beeper.toggle
|
||||
|
||||
* shutdown.return, shutdown.reboot, shutdown.stayoff
|
||||
|
||||
On many devices, these commands are unreliable, so before using them you
|
||||
must verify that these work as expected (see <<_shutdown_issues,Shutdown Issues>>).
|
||||
|
||||
* shutdown.stop
|
||||
|
||||
SUPPORT STATUS
|
||||
--------------
|
||||
Vendor support is absent for this driver, so if you need some features that
|
||||
are currently not available, provide ample documentation on what the driver
|
||||
should sent to the UPS in order to make this work. If more information
|
||||
would be available on the binary protocol, it would probably be possible to
|
||||
make 'ondelay' and 'offdelay' configurable. So far, nobody has taken the time
|
||||
to investigate what we should tell the UPS to make this work, and CyberPower
|
||||
isn't willing to share this with us.
|
||||
|
||||
SHUTDOWN ISSUES
|
||||
---------------
|
||||
If the *shutdown.return* command on your UPS doesn't seem to work,
|
||||
chances are that your UPS is an older model. Try a couple of different
|
||||
settings for 'offdelay'. If no value in the range 6..600 works, your
|
||||
UPS likely doesn't support this. In order to get the expected behaviour,
|
||||
it requires *shutdown.stayoff* (when on battery) and *shutdown.reboot*
|
||||
(when on mains). The driver will automatically fallback to these commands if
|
||||
*shutdown.return* fails, and tries to detect which one should be used when
|
||||
called with the '-k' option (or through *upsdrvctl shutdown*).
|
||||
|
||||
This isn't bullet-proof, however, and you should be prepared that the
|
||||
power will either not be shutdown or that it doesn't return when the
|
||||
power comes back. All models supported by the binary protocol and many
|
||||
supported through the text protocol are affected by this.
|
||||
|
||||
KNOWN PROBLEMS
|
||||
--------------
|
||||
The CyberPower OP series don't offer direct voltage, charge, frequency
|
||||
and temperature readings. Instead, they will return a binary value
|
||||
that needs conversion to the actual value.
|
||||
|
||||
The exact conversion needed is unknown at the time of this writing,
|
||||
hence an estimation was made based om readings from actual devices.
|
||||
This may (probably will) be off, possibly a lot. Unless you can tell
|
||||
us the exact mapping between values from the UPS and actual readings,
|
||||
don't bother to complain. We've done the best we can based on the
|
||||
limited information available. Remember, a UPS isn't a measuring
|
||||
instrument.
|
||||
|
||||
AUTHORS
|
||||
-------
|
||||
Arjen de Korte <arjen@de-korte.org>, Doug Reynolds <mav@wastegate.net>
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver:
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
Internet resources:
|
||||
~~~~~~~~~~~~~~~~~~~
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||