Imported Upstream version 2.6.0
This commit is contained in:
parent
26fb71b504
commit
459aaf9392
510 changed files with 40508 additions and 18859 deletions
93
docs/man/netxml-ups.txt
Normal file
93
docs/man/netxml-ups.txt
Normal file
|
|
@ -0,0 +1,93 @@
|
|||
netxml-ups(8)
|
||||
=============
|
||||
|
||||
NAME
|
||||
----
|
||||
netxml-ups - Driver for Eaton / MGE Network Management Card / Proxy
|
||||
(XML/HTTP Protocol) equipment
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the hardware-specific features of the
|
||||
netxml-ups driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
netxml-ups support all recent Eaton / MGE models which use a Network
|
||||
Management Card or Proxy (MGE XML/HTTP protocol based). This applies to both
|
||||
Eaton (previously MGE Office Protection Systems) and to MGE UPS SYSTEMS.
|
||||
Supported card and proxy models are:
|
||||
|
||||
* NMC Minislot (Ref 66102, firmware EA or newer),
|
||||
* SNMP/Web Minislot card (Ref 66244)
|
||||
* NMC Transverse (Ref 66074),
|
||||
* NMC & Modbus/JBus (Ref 66103),
|
||||
* Network Management Proxy,
|
||||
* ePDU Monitored (newer version).
|
||||
|
||||
Older models, such as SNMP card (Ref 66062 and Ref 66045), use the SNMP
|
||||
protocol and should use the linkman:snmp-ups[8] driver with the "mibs=mge"
|
||||
parameter.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
This driver supports the following optional settings in the
|
||||
linkman:ups.conf[5]:
|
||||
|
||||
*timeout*='value'::
|
||||
The timeout for connecting to and reading from the UPS. Defaults to 5 seconds.
|
||||
Don't change this value unless you know exactly what you're doing.
|
||||
|
||||
This value *must never* be higher than half the MAXAGE value specified in
|
||||
linkman:upsd.conf[5], otherwise you run the risk that linkman:upsd[8] declares
|
||||
the driver stale while it is waiting for a connection to timeout.
|
||||
|
||||
*login*='value'::
|
||||
Set the login value for authenticated mode. This feature also needs the
|
||||
*password* argument, and allows value settings in the card.
|
||||
This feature is not used yet.
|
||||
|
||||
*password*='value'::
|
||||
Set the password value, needed with the login for authenticated mode.
|
||||
This feature is not used yet.
|
||||
|
||||
IMPLEMENTATION
|
||||
--------------
|
||||
The hostname of the UPS is specified with the "port" value in
|
||||
*ups.conf*, i.e.:
|
||||
|
||||
[mgexml]
|
||||
driver = netxml-ups
|
||||
port = http://netxml-ups.example.com:80
|
||||
|
||||
Specifying the method to connect to the UPS (http, https) is mandatory.
|
||||
If the port is equal to the default for the method specified (80 for http,
|
||||
443 for https) it may be omitted.
|
||||
|
||||
In order not to overload older NMCs by polling them too frequently, it is
|
||||
recommended to increase the "pollinterval" (see linkman:nutupsdrv[8]) and
|
||||
linkman:ups.conf[5]) to at least 5 seconds.
|
||||
|
||||
KNOWN ISSUES
|
||||
------------
|
||||
Don't connect to the UPS through a proxy. Although it would be trivial to add
|
||||
support for proxies, this is not recommended and don't ask for it. Not only
|
||||
because it will prevent the driver to make a persistent connection to the UPS,
|
||||
but also it adds an additional failure mode. If the proxy goes down (for
|
||||
whatever reason), the driver will no longer be able to reach the UPS.
|
||||
|
||||
AUTHORS
|
||||
-------
|
||||
Arjen de Korte <adkorte-guest@alioth.debian.org>
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver:
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
Internet resources:
|
||||
~~~~~~~~~~~~~~~~~~~
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||