@ -0,0 +1,98 @@
|
|||
MGE-UTALK(8)
|
||||
============
|
||||
|
||||
NAME
|
||||
----
|
||||
|
||||
mge-utalk - Driver for MGE UPS SYSTEMS UTalk protocol equipment
|
||||
|
||||
SYNOPSIS
|
||||
--------
|
||||
|
||||
*mge-utalk* -h
|
||||
|
||||
*mge-utalk* -a 'UPS_NAME' ['OPTIONS']
|
||||
|
||||
NOTE: This man page only documents the hardware-specific features of the
|
||||
mge-utalk driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
|
||||
mge-utalk supports the following legacy units, using the MGE UTalk protocol:
|
||||
|
||||
Pulsar ESV+,
|
||||
Pulsar ES+,
|
||||
Pulsar EL,
|
||||
Pulsar EX,
|
||||
Pulsar EXtreme,
|
||||
Comet EXtreme,
|
||||
Comet (Utalk Serial Card, ref 66060),
|
||||
Galaxy (Utalk Serial Card, ref 66060).
|
||||
|
||||
This driver also support some newer models with backward UTalk compatibility,
|
||||
such as Pulsar Evolution and Pulsar EXtreme C. As these models also support
|
||||
the SHUT protocol, prefer mge-shut for serial communication, or use the USB
|
||||
port, if available, with the usbhid-ups driver.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
|
||||
This driver supports the following optional settings in the linkman:ups.conf[5]:
|
||||
|
||||
*lowbatt*='num'::
|
||||
Set the low battery warning threshold at which shutdown is initiated by
|
||||
linkman:upsmon[8].
|
||||
+
|
||||
The factory default value is 30 (in percent), and can be settable depending on
|
||||
the exact model.
|
||||
|
||||
*offdelay*='num'::
|
||||
Set the timer before the UPS is turned off after the kill power command is
|
||||
sent (via the *-k* switch).
|
||||
+
|
||||
The default value is 20 (in seconds).
|
||||
|
||||
*ondelay*='num'::
|
||||
Set the delay before the UPS is turned on, after the power returns.
|
||||
+
|
||||
The default value is 1 (in minutes).
|
||||
|
||||
*oldmac*::
|
||||
Set this flag if you are running Linux on an Oldworld Macintosh box
|
||||
(all beige Apple Macintosh). This might also be needed for other
|
||||
OSs (like *BSD) running on PowerMac.
|
||||
|
||||
KNOWN ISSUES
|
||||
------------
|
||||
|
||||
Repetitive timeout and staleness
|
||||
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
||||
|
||||
Older models, such as ES/ESV ones, might report repetitive "data stale" errors.
|
||||
This is due to the fact that these models don't support too much polling.
|
||||
To solve this problem, add "pollinterval=20" in ups.conf, and change the value
|
||||
of MAXAGE to 25 in upsd.conf, and DEADTIME to 25 in upsmon.conf.
|
||||
|
||||
AUTHOR
|
||||
------
|
||||
|
||||
Hans Ekkehard Plesser,
|
||||
Arnaud Quette,
|
||||
Martin Loyer,
|
||||
Patrick Agrain,
|
||||
Nicholas Reilly,
|
||||
Dave Abbott,
|
||||
Marek Kralewski
|
||||
|
||||