MGE-SHUT(8)
|
||||
===========
|
||||
|
||||
NAME
|
||||
----
|
||||
|
||||
mge-shut - Driver for SHUT Protocol UPS equipment
|
||||
|
||||
SYNOPSIS
|
||||
--------
|
||||
|
||||
*mge-shut* -h
|
||||
|
||||
*mge-shut* -a 'UPS_NAME' ['OPTIONS']
|
||||
|
||||
NOTE: This man page only documents the hardware-specific features of the
|
||||
mge-shut driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
|
||||
mge-shut supports all recent Eaton, MGE and Dell UPS models which use the SHUT
|
||||
(Serial HID UPS Transfer) protocol.
|
||||
|
||||
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U-Talk
|
||||
protocol and should use the mge-utalk driver.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
|
||||
This driver also supports the following optional settings:
|
||||
|
||||
*lowbatt*='num'::
|
||||
Set the low battery warning threshold at which shutdown is initiated by
|
||||
linkman:upsmon[8].
|
||||
+
|
||||
The factory default value is 30 (in percent), and can be settable depending on
|
||||
the exact model.
|
||||
|
||||
*offdelay*='num'::
|
||||
Set the timer before the UPS is turned off after the kill power command is
|
||||
sent (via the *-k* switch).
|
||||
+
|
||||
The default value is 20 (in seconds). Usually this *must be lower* than
|
||||
'ondelay', but the driver will *not* warn you upon startup if it isn't.
|
||||
|
||||
*ondelay*='num'::
|
||||
Set the timer for the UPS to switch on in case the power returns after the
|
||||
kill power command had been sent but before the actual switch off. This
|
||||
ensures the machines connected to the UPS are, in all cases, rebooted after
|
||||
a power failure.
|
||||
+
|
||||
The default value is 30 (in seconds). Usually this *must be greater*
|
||||
than offdelay, but the driver will *not* warn you upon startup if it
|
||||
isn't. Some UPS'es will restart no matter what, even if the power is
|
||||
(still) out at the moment this timer elapses. In that case, you could try
|
||||
if setting 'ondelay = -1' in *ups.conf* helps.
|
||||
|
||||
*notification*='num'::
|
||||
Set notification type to 1 (no), 2 (light) or 3 (yes).
|
||||
+
|
||||
The default value is 3 (yes) because of some early Ellipse models which
|
||||
need it.
|
||||
|
||||
KNOWN ISSUES
|
||||
------------
|
||||
|
||||
Repetitive timeout and staleness
|
||||
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
||||
|
||||
Some models tends to be unresponsive with the default polling frequency.
|
||||
The result is that you have some "data stale" errors in your system log.
|
||||
|
||||
In this case, simply modify the general parameter "pollinterval" to a higher
|
||||
value (like 10 for 10 seconds). This should solve the issue.
|
||||
|
||||
Using 'notification=3' might also help.
|
||||
|
||||
AUTHOR
|
||||
------
|
||||
|
||||
Arnaud Quette
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
Internet resources
|
||||
~~~~~~~~~~~~~~~~~~
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||