LIEBERT(8)
|
||||
==========
|
||||
|
||||
NAME
|
||||
----
|
||||
|
||||
liebert - Driver for Liebert contact-closure UPS equipment
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the hardware-specific features of the
|
||||
liebert driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
SUPPORTED HARDWARE
|
||||
------------------
|
||||
This driver supports some Liebert UPS equipment with a contact-closure
|
||||
interface. This includes the UPStation GXT2 with their contact-closure
|
||||
cable. The smart mode ("Multilink") cable is not supported by this
|
||||
driver.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
|
||||
This driver does not support any extra settings in the
|
||||
linkman:ups.conf[5].
|
||||
|
||||
BUGS
|
||||
----
|
||||
|
||||
This driver does not yet support shutdowns by raising DTR. Be aware
|
||||
that shutdowns are not possible with the stock contact-closure cable.
|
||||
You may have to build another cable with DTR connected through to the
|
||||
UPS for it to work.
|
||||
|
||||
There is no way for this driver to detect the hardware or cable. It
|
||||
will start up successfully even if no UPS is present. This is a
|
||||
fundamental limitation of any contact-closure driver.
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
The core driver:
|
||||
~~~~~~~~~~~~~~~~
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||
Internet resources:
|
||||
~~~~~~~~~~~~~~~~~~~
|
||||
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|
||||