CLONE(8)
|
||||
========
|
||||
|
||||
NAME
|
||||
----
|
||||
clone - UPS driver clone
|
||||
|
||||
NOTE
|
||||
----
|
||||
This man page only documents the specific features of the
|
||||
clone driver. For information about the core driver, see
|
||||
linkman:nutupsdrv[8].
|
||||
|
||||
DESCRIPTION
|
||||
-----------
|
||||
This driver, which sits on top of another driver socket, allows users to group
|
||||
clients to a particular outlet of a device and deal with this output as if it
|
||||
was a normal UPS.
|
||||
|
||||
EXTRA ARGUMENTS
|
||||
---------------
|
||||
This driver supports the following settings:
|
||||
|
||||
*load.off*='command'::
|
||||
Recommended. Set the command on the "real" UPS driver that will be used to
|
||||
switch off the outlet. You need both *load.off* and *load.on* in
|
||||
order to power cycle the outlet. Otherwise, shutting down the clients
|
||||
powered by an outlet is a one way street (see <<_important,IMPORTANT>>).
|
||||
|
||||
*load.on*='command'::
|
||||
Recommended. Set the command on the "real" UPS driver that will be used to
|
||||
switch on the outlet. You need both *load.off* and *load.on* in
|
||||
order to power cycle the outlet. Otherwise, shutting down the clients
|
||||
powered by an outlet is a one way street (see <<_important,IMPORTANT>>).
|
||||
|
||||
*load.status*='value'::
|
||||
Recommended. Set the variable on the "real" UPS driver that will be used
|
||||
to indicate the outlet status (i.e. on/off). If not specified, the clone
|
||||
driver will attempt to keep track of the outlet status, but this is less
|
||||
reliable.
|
||||
|
||||
*offdelay*='num'::
|
||||
Set the timer (in seconds) before the outlet is turned off after the
|
||||
shutdown condition (+OB LB+) for this outlet is met or a command to shutdown
|
||||
was issued. Defaults to 120 seconds.
|
||||
|
||||
*ondelay*='num'::
|
||||
Set the timer (in seconds) for the outlet to switch on in case the power
|
||||
returns after the oulet has been switched off. Defaults to 30 seconds.
|
||||
|
||||
*mincharge*='value'::
|
||||
Set the remaining battery level when the clone UPS switches to LB
|
||||
(percent).
|
||||
|
||||
*minruntime*='value'::
|
||||
Set the remaining battery runtime when the clone UPS switches to LB
|
||||
(seconds).
|
||||
|
||||
IMPLEMENTATION
|
||||
--------------
|
||||
The port specification in the linkman:ups.conf[5] reference the driver
|
||||
socket that the "real" UPS driver is using. For example:
|
||||
|
||||
[realups]
|
||||
driver = usbhid-ups
|
||||
port = auto
|
||||
|
||||
[clone-outlet-1]
|
||||
driver = clone
|
||||
port = usbhid-ups-realups
|
||||
load.on = outlet.1.load.on
|
||||
load.off = outlet.1.load.off
|
||||
load.status = outlet.1.status
|
||||
[...]
|
||||
|
||||
IMPORTANT
|
||||
---------
|
||||
Unlike a real UPS, you should *not* configure a upsmon master for this
|
||||
driver. When a upsmon master sees the OB LB flags and tells the upsd server
|
||||
it is OK to initiate the shutdown sequence, the server will latch the FSD
|
||||
status and it will not be possible to restart the systems connected without
|
||||
restarting the upsd server.
|
||||
|
||||
This will be a problem if the power returns after the clone UPS initiated
|
||||
the shutdown sequence on it's outlet, but returns before the real UPS begins
|
||||
shutting down. The solution is in the clone driver, that will insert the
|
||||
FSD flag if needed without the help of a upsmon master.
|
||||
|
||||
CAVEATS
|
||||
-------
|
||||
The clone UPS will follow the status on the real UPS driver. You can only
|
||||
make the clone UPS shutdown earlier than the real UPS driver, not later.
|
||||
If the real UPS driver initiates a shutdown, the clone UPS driver will
|
||||
immediately follow.
|
||||
|
||||
Be aware that the commands to shutdown/restart an outlet on the real UPS
|
||||
drivers are not affected, so if you tell the real UPS driver to shutdown
|
||||
the outlet of the clone UPS driver, your clients will lose power without
|
||||
warning.
|
||||
|
||||
AUTHOR
|
||||
------
|
||||
Arjen de Korte <adkorte-guest@alioth.debian.org>
|
||||
|
||||
SEE ALSO
|
||||
--------
|
||||
|
||||
linkman:upscmd[1],
|
||||
linkman:upsrw[1],
|
||||
linkman:ups.conf[5],
|
||||
linkman:nutupsdrv[8]
|
||||
|
||||