Desc: Network UPS Tools design document
|
||||
File: design.txt
|
||||
Date: 14 March 2004
|
||||
Auth: Russell Kroll <rkroll@exploits.org>
|
||||
|
||||
This software is designed around a layered scheme with drivers, a
|
||||
server and clients. These layers communicate with text-based
|
||||
protocols for easier maintenance and diagnostics.
|
||||
|
||||
The layering
|
||||
============
|
||||
|
||||
CLIENTS: upsmon, upsc, upsrw, upsstats, upsset, etc. (via upsclient)
|
||||
|
||||
< network: TCP sockets, typically on port 3493 >
|
||||
|
||||
SERVER: upsd
|
||||
|
||||
< Unix domain sockets with text-based messages >
|
||||
|
||||
DRIVERS: apcsmart, bestups, powercom, etc.
|
||||
|
||||
< serial communications, SNMP, USB, etc. >
|
||||
|
||||
EQUIPMENT: Smart-UPS 700, Fenton PowerPal 660, etc. (actual UPS hardware)
|
||||
|
||||
How information gets around
|
||||
===========================
|
||||
|
||||
From the equipment
|
||||
------------------
|
||||
|
||||
DRIVERS talk to the EQUIPMENT and receive updates. For most hardware this
|
||||
is polled (DRIVER asks EQUIPMENT about a variable), but forced updates are
|
||||
also possible. The exact method is not important, as it is abstracted
|
||||
by the driver.
|
||||
|
||||
From the driver
|
||||
---------------
|
||||
|
||||
The core of all DRIVERS maintains internal storage for every variable
|
||||
that is known along with the auxiliary data for those variables. It
|
||||
sends updates to this data to any process which connects to the Unix
|
||||
domain socket.
|
||||
|
||||
The DRIVERS will also provide a full atomic copy of their internal
|
||||
knowledge upon receiving the "DUMPALL" command on the socket. The dump
|
||||
is in the same format as updates, and is followed by "DUMPDONE". When
|
||||
"DUMPDONE" has been received, the view is complete.
|
||||
|
||||
The SERVER will connect to the socket of each DRIVER and will request a
|
||||
dump at that time. It retains this data in local storage for later use.
|
||||
It continues to listen on the socket for additional updates.
|
||||
|
||||
This protocol is documented in sock-protocol.txt.
|
||||
|
||||
From the server
|
||||
---------------
|
||||
|
||||
The SERVER's internal storage maintains a complete copy of the data
|
||||
which is in the DRIVER, so it is capable of answering any request
|
||||
immediately. When a request for data arrives from a CLIENT, the SERVER
|
||||
looks through the internal storage for that UPS and returns the
|
||||
requested data if it is available.
|
||||
|
||||
The format for requests from the CLIENT is documented in protocol.txt.
|
||||
|
||||
Instant commands
|
||||
================
|
||||
|
||||
Instant commands is the term given to a set of actions that result in
|
||||
something happening to the UPS. Some of the common ones are
|
||||
test.battery.start to initiate a battery test and test.panel.start to
|
||||
test the front panel of the UPS.
|
||||
|
||||
They are passed to the SERVER from a CLIENT using an authenticated
|
||||
network connection. The SERVER first checks to make sure that the instant
|
||||
command is valid for the DRIVER. If it's supported, a message is sent
|
||||
via a socket to the DRIVER containing the command and any auxiliary
|
||||
information.
|
||||
|
||||
At this point, there is no confirmation to the SERVER of the command's
|
||||
execution. This is (still) planned for a future release. This has been
|
||||
delayed since returning a response involves some potentially interesting
|
||||
timing issues. Remember that upsd services clients in a round-robin
|
||||
fashion, so all queries must be lightweight and speedy.
|
||||
|
||||
Setting variables
|
||||
=================
|
||||
|
||||
Some variables in the DRIVER or EQUIPMENT can be changed, and carry the
|
||||
FLAG_RW flag. Upon receiving a SET command from the CLIENT, the SERVER
|
||||
first verifies that it is valid for that DRIVER in terms of writability
|
||||
and data type. If those checks pass, it then sends the SET command
|
||||
through the socket, much like the instant command design.
|
||||
|
||||
The DRIVER is expected to commit the value to the EQUIPMENT and update
|
||||
its internal representation of that variable.
|
||||
|
||||
Like the instant commands, there is currently no acknowledgement of the
|
||||
command's completion from the DRIVER. This, too, is planned for a future
|
||||
release.
|
||||
|
||||
Example data path
|
||||
=================
|
||||
|
||||
Here's the path a piece of data might take through this architecture.
|
||||
The event is a UPS going on battery, and the final result is a pager
|
||||
delivering the alpha message to the admin.
|
||||
|
||||
1. EQUIPMENT reports on battery by setting flag in status register
|
||||
|
||||
2. DRIVER notices this flag and stores it in the ups.status variable as
|
||||
OB. This update gets pushed out to any listeners via the sockets.
|
||||
|
||||
3. SERVER upsd sees activity on the socket, reads it, parses it, and
|
||||
commits the new data to its local version of the status variable.
|
||||
|
||||
4. CLIENT upsmon does a routine poll of SERVER for "ups.status" and
|
||||
gets "OB".
|
||||
|
||||
5. CLIENT upsmon then invokes its NOTIFYCMD which is upssched.
|
||||
|
||||
6. upssched starts up a daemon to handle a timer which will expire about
|
||||
30 seconds into the future.
|
||||
|
||||
7. 30 seconds later, the timer expires since the UPS is still on battery,
|
||||
and upssched calls the CMDSCRIPT upssched-cmd.
|
||||
|
||||
8. upssched-cmd parses the args and calls sendmail.
|
||||
|
||||
9. Avian carriers, smoke signals, SMTP, and some magic result in the
|
||||
message getting from the pager company's gateway to a transmitter
|
||||
and then to the admin's pager.
|
||||
|
||||
This scenario requires some configuration, obviously:
|
||||
|
||||
1. There's a UPS driver running.
|
||||
(Whatever applies for the hardware)
|
||||
|
||||
2. upsd has a valid UPS entry in ups.conf for this UPS.
|
||||
|
||||
[myups]
|
||||
driver = upsdriver
|
||||
port = /dev/ttySx
|
||||
|
||||
3. upsd has a valid user for upsmon in upsd.users.
|
||||
|
||||
[monuser]
|
||||
password = somepass
|
||||
upsmon master
|
||||
|
||||
4. upsmon is set to monitor this UPS in upsmon.conf.
|
||||
|
||||
MONITOR myups@localhost 1 monuser somepass master
|
||||
|
||||
5. upsmon is set to EXEC the NOTIFYCMD for the ONBATT condition in
|
||||
upsmon.conf.
|
||||
|
||||
NOTIFYFLAG ONBATT EXEC
|
||||
|
||||
6. upsmon calls upssched as the NOTIFYCMD in upsmon.conf.
|
||||
|
||||
NOTIFYCMD /path/to/upssched
|
||||
|
||||
7. upssched has a 30 second timer for ONBATT in upssched.conf.
|
||||
|
||||
AT ONBATT * START-TIMER upsonbatt 30
|
||||
|
||||
8. upssched calls upssched-cmd as the CMDSCRIPT in upssched.conf.
|
||||
|
||||
CMDSCRIPT /path/to/upssched-cmd
|
||||
|
||||
8. upssched-cmd knows what to do with "upsonbatt" as its first argument
|
||||
(A quick case..esac construct, see the examples)
|
||||
|
||||
==============================================================================
|
||||
|
||||
History
|
||||
=======
|
||||
|
||||
The oldest versions of this software (1998) had no separation between
|
||||
the driver and the network server and only supported the latest APC
|
||||
Smart-UPS hardware as a result. The network protocol used brittle
|
||||
binary structs. This had numerous bad implications for compatibility
|
||||
and portability.
|
||||
|
||||
After the driver and server were separated, data was shared through the
|
||||
state file concept. Status was written into a static array (the "info
|
||||
array") by drivers, and that array was stored on disk. upsd would
|
||||
periodically read that file into a local copy of that array.
|
||||
|
||||
Shared memory mode was added a bit later, and that removed some of the
|
||||
lag from the status updates. Unfortunately, it didn't have any locking
|
||||
originally, and the possibility for corruption due to races existed.
|
||||
|
||||
mmap() support was added at some point after that, and became the
|
||||
default. The drivers and upsd would mmap() the file into memory and
|
||||
read or write from it. Locking was done using the state file as the
|
||||
token, so contention problems were avoided. This method was relatively
|
||||
quick, but it involved at least 3 copies of the data (driver, disk/mmap,
|
||||
server) and a whole lot of locking and unlocking. It could occasionally
|
||||
delay the driver or server when waiting for a lock.
|
||||
|
||||
In April 2003, the entire state management subsystem was removed and
|
||||
replaced with a single local socket. The drivers listen for
|
||||
connections and push updates asynchronously to any listeners. They also
|
||||
recognize a few commands. Drivers also dampen updates, and only push
|
||||
them out when something actually changes.
|
||||
|
||||
As a result, upsd no longer has to poll any files on the disk, and can
|
||||
just select() all of its fds and wait for activity. When one of them is
|
||||
active, it reads the fd and parses the results. Updates from the
|
||||
hardware now get to upsd about as fast as they possibly can.
|
||||
|
||||
Drivers used to call setinfo() to change the local array, and then would
|
||||
call writeinfo() to push the array onto the disk, or into the
|
||||
mmap/shared memory space. This introduced a lag since many drivers poll
|
||||
quite a few variables during an update.
|
||||