Desc: Contact closure hardware
|
||||
File: contact-closure.txt
|
||||
Date: 14 March 2004
|
||||
Auth: Russell Kroll <rkroll@exploits.org>
|
||||
|
||||
This is a collection of notes that apply to contact closure UPS
|
||||
hardware, specifically those monitored by the genericups driver.
|
||||
|
||||
Definitions
|
||||
-----------
|
||||
|
||||
"Contact closure" refers to a situation where one line is connected to
|
||||
another inside UPS hardware to indicate some sort of situation. These
|
||||
can be relays, or some other form of switching electronics. The generic
|
||||
idea is that you either have a signal on a line, or you don't. Think
|
||||
binary.
|
||||
|
||||
Usually, the source for a signal is the host PC. It provides a high
|
||||
(logic level 1) from one of its outgoing lines, and the UPS returns it
|
||||
on one or more lines to communicate. The rest of the time, the UPS
|
||||
either lets it float or connects it to the ground to indicate a 0.
|
||||
|
||||
Other equipment generates the high and low signals internally, and does
|
||||
not require cable power. These signals just appear on the right lines
|
||||
without any special configuration on the PC side.
|
||||
|
||||
Bad levels
|
||||
----------
|
||||
|
||||
Some evil cabling and UPS equipment uses the transmit or receive lines
|
||||
as their reference points for these signals. This is not sufficient to
|
||||
register as a high signal on many serial ports. If you have problems
|
||||
reading certain signals on your system, make sure your UPS isn't trying
|
||||
to do this.
|
||||
|
||||
Signals
|
||||
-------
|
||||
|
||||
Unlike their smarter cousins, this kind of UPS can only give you very
|
||||
simple yes/no answers. Due to the limited number of serial port lines
|
||||
that can be used for this purpose, you typically get two pieces of data:
|
||||
|
||||
1. "On line" or "on battery"
|
||||
2. "Battery OK" or "Low battery"
|
||||
|
||||
That's it. Some equipment actually swaps the second one for a
|
||||
notification about whether the battery needs to be replaced, which makes
|
||||
life interesting for those users.
|
||||
|
||||
Most hardware also supports an outgoing signal from the PC which means
|
||||
"shut down the load immediately". This is generally implemented in such
|
||||
a way that it only works when running on battery. Most hardware or
|
||||
cabling will ignore the shutdown signal when running on line power.
|
||||
|
||||
New genericups types
|
||||
--------------------
|
||||
|
||||
If none of the existing types in the genericups driver work completely,
|
||||
make a note of which ones (if any) manage to work partially. This can
|
||||
save you some work when creating support for your hardware.
|
||||
|
||||
Use that information to create a list of where the signals from your UPS
|
||||
appear on the serial port at the PC end, and whether they are active
|
||||
high or active low. You also need to know what outgoing lines, if any,
|
||||
need to be raised in order to supply power to the contacts. This is
|
||||
known as cable power. Finally, if your UPS can shut down the load, that
|
||||
line must also be identified.
|
||||
|
||||
There are only 4 incoming and 2 outgoing lines, so not many combinations
|
||||
are left. The other lines on a typical 9 pin port are transmit,
|
||||
receive, and the ground. Anything trying to do a high/low signal on
|
||||
those three is beyond the scope of the genericups driver. The only
|
||||
exception is an outgoing BREAK, which we already support.
|
||||
|
||||
When editing the genericups.h, the values have the following meanings:
|
||||
|
||||
Outgoing lines:
|
||||
|
||||
line_norm = what to set to make the line "normal" - i.e. cable power
|
||||
line_sd = what to set to make the UPS shut down the load
|
||||
|
||||
Incoming lines:
|
||||
|
||||
line_ol = flag that appears for on line / on battery
|
||||
val_ol = value of that flag when the UPS is on battery
|
||||
line_bl = flag that appears for low battery / battery OK
|
||||
val_bl = value of that flag when the battery is low
|
||||
|
||||
This may seem a bit confusing to have two variables per value that
|
||||
we want to read, but here's how it works. If you set line_ol to
|
||||
TIOCM_RNG, then the value of TIOCM_RNG (0x080 on my box) will be anded
|
||||
with the value of the serial port whenever a poll occurs. If that flag
|
||||
exists, then the result of the and will be 0x80. If it does not exist,
|
||||
the result will be 0.
|
||||
|
||||
So, if line_ol = foo, then val_ol can only be foo or 0.
|
||||
|
||||
As a general case, if line_ol == val_ol, then the value you're reading
|
||||
is active high. Otherwise, it's active low. Check out the guts of
|
||||
upsdrv_updateinfo() to see how it really works.
|
||||
|
||||
Custom definitions
|
||||
------------------
|
||||
|
||||
Late in the 1.3 cycle, a feature was merged which allows you to create
|
||||
custom monitoring settings without editing the model table. Just set
|
||||
upstype to something close, then use settings in ups.conf to adjust the
|
||||
rest. See the genericups man page for more details.
|
||||