Imported Upstream version 2.4.3
This commit is contained in:
commit
26fb71b504
446 changed files with 148951 additions and 0 deletions
34
docs/cables/apc-rs500-serial.txt
Normal file
34
docs/cables/apc-rs500-serial.txt
Normal file
|
@ -0,0 +1,34 @@
|
|||
Desc: APC UPS cable - for Back-UPS RS 500
|
||||
File: apc-rs500-serial.txt
|
||||
Date: 14 July 2004
|
||||
Auth: Russell Kroll <rkroll@exploits.org>, Martin Edlman <edlman@fortech.cz>
|
||||
|
||||
This document was constructed from a mail from Martin. He figured out
|
||||
the pinouts to make the Back-UPS RS 500 work with a normal serial port.
|
||||
Here are the details:
|
||||
|
||||
---
|
||||
|
||||
UPS side PC side
|
||||
RJ45 (8 pins) DB9F
|
||||
|
||||
1 orange/white 2,8,9
|
||||
2 orange 1
|
||||
3 green/white chassis/ground
|
||||
4 blue -
|
||||
5 blue/white -
|
||||
6 green 5
|
||||
7 brown/white 4,6
|
||||
8 brown -
|
||||
|
||||
+---+
|
||||
+-----+ +-----+
|
||||
| |
|
||||
+---------------+
|
||||
8 7 6 5 4 3 2 1
|
||||
|
||||
view from back (cable entry)
|
||||
---
|
||||
|
||||
Note this results in OL=-CTS, LB=DCD, SD=ST, CP=RTS, so it should work
|
||||
with the existing genericups type 20.
|
233
docs/cables/apc.txt
Normal file
233
docs/cables/apc.txt
Normal file
|
@ -0,0 +1,233 @@
|
|||
Desc: APC UPS cables
|
||||
File: apc.txt
|
||||
Date: 12 Februari 2010
|
||||
Auth: Arjen de Korte <adkorte-guest@alioth.debian.org
|
||||
|
||||
http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-August/000118.html
|
||||
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram |
|
||||
| This information is verified and tested to be 100% correct. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||||
| --------- -------- -------------- |
|
||||
| |
|
||||
| (SHELL)<---------+----//----+----------------<(SHELL) |
|
||||
| | | |
|
||||
| - - |
|
||||
| | | | | |
|
||||
| CHASSIS 9<--------------//---------------------<5 SG |
|
||||
| | | | | |
|
||||
| TXD 2<--------------//---------------------<2 RXD |
|
||||
| | | | | |
|
||||
| RXD 1<--------------//---------------------<3 TXD |
|
||||
| | | | | |
|
||||
| - - +--<1 DCD |
|
||||
| | |
|
||||
| +--<4 DTR |
|
||||
| NOTES: |
|
||||
| Cable type is shielded 28AWG. +--<7 RTS |
|
||||
| The DB shells are connected | |
|
||||
| to each other via the shield. +--<8 CTS |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Operation: The UPS communicates with the Computer via |
|
||||
| ordinary RS-232 serial protocol at 2400-8N1 with software |
|
||||
| flow control. Jumpered pins in the DB9F connector are for |
|
||||
| automatic or PNP cable identification by UPS software. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Male (pins) Female (holes) |
|
||||
| DB9 RS-232 PC |
|
||||
| type connector 1 5 5 1 |
|
||||
| ---------------- _______________ _______________ |
|
||||
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||||
| looking into the \ . . . . / \ o o o o / |
|
||||
| end of the cable ----------- ----------- |
|
||||
| 6 9 9 6 |
|
||||
| |
|
||||
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
|
||||
|
||||
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Gray APC 940-0020B Simple Signalling UPS Cable Wiring Diagram |
|
||||
| This information is verified and tested to be 100% correct. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||||
| --------- -------- -------------- |
|
||||
| |
|
||||
| (SHELL)<-------+----//----+-------------------<(SHELL) |
|
||||
| | | |
|
||||
| CHASSIS 9<--+ - - |
|
||||
| | | | | | |
|
||||
| COMMON 4<--+---------//------------------------<5 SG |
|
||||
| | | | | |
|
||||
| POWER-FAIL 2<------------//------------------------<8 CTS |
|
||||
| | | | | |
|
||||
| SHUTDOWN 1<------------//------------------------<4 DTR |
|
||||
| | | | | |
|
||||
| BATTERY-LOW 5<------------//--------47K--+--47K--+--<7 RTS |
|
||||
| | | | | | | |
|
||||
| - - | E | |
|
||||
| NOTES: |B |<--+ |
|
||||
| RTS must be held at +V SPACE. +---| |
|
||||
| TXD must be held at -V MARK. 2N3906 |---+--<1 DCD |
|
||||
| All resistors are 5% 1/8W CF. C | |
|
||||
| Cable type is shielded 28AWG. 4K7 |
|
||||
| The DB shells are connected | |
|
||||
| to each other via the shield. +--<3 TXD |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Operation: The UPS communicates with the Computer via |
|
||||
| the RS-232 handshaking lines only, and does not use any |
|
||||
| serial protocol. Upon power fail, the UPS forces CTS to |
|
||||
| -V MARK. When the battery is low, the UPS forces DCD to |
|
||||
| +V SPACE via the transistor. When the Computer forces a |
|
||||
| +V SPACE on DTR, the UPS will shut down and turn off. |
|
||||
| Presence of the cable can be sensed by signaling on TXD |
|
||||
| while monitoring DCD. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Male (pins) Female (holes) |
|
||||
| DB9 RS-232 PC |
|
||||
| type connector 1 5 5 1 |
|
||||
| ---------------- _______________ _______________ |
|
||||
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||||
| looking into the \ . . . . / \ o o o o / |
|
||||
| end of the cable ----------- ----------- |
|
||||
| 6 9 9 6 |
|
||||
| |
|
||||
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
|
||||
|
||||
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Gray APC 940-0095A Smart Signalling UPS Cable Wiring Diagram |
|
||||
| This information is verified and tested to be 100% correct. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||||
| --------- -------- -------------- |
|
||||
| |
|
||||
| (SHELL)<-------+----//----+--------------------<(SHELL) |
|
||||
| | | |
|
||||
| CHASSIS 9<--+ - - |
|
||||
| | | | | | |
|
||||
| COMMON 4<--+---------//-------------------------<5 SG |
|
||||
| | | | | |
|
||||
| BATTERY-LOW 5<------------//--------47K--+--47K--+---<4 DTR |
|
||||
| | | | | | | |
|
||||
| | +---<6 DSR |
|
||||
| | | | | | E | |
|
||||
| NOTES: |B |<--+---<8 CTS |
|
||||
| DTR must be held at +V SPACE. | | +---| |
|
||||
| TXD must be held at -V MARK. 2N3906 |---+---<1 DCD |
|
||||
| All resistors are 5% 1/8W CF. | | C | |
|
||||
| Cable type is shielded 28AWG. 4K7 |
|
||||
| The DB shells are connected | | | |
|
||||
| to each other via the shield. +----4K7---+---<3 TXD |
|
||||
| | | | | | |
|
||||
| | |
|
||||
| | | | | | 1N4148 |
|
||||
| SHUTDOWN 1<------------//----------+----|<|-------<7 RTS |
|
||||
| | | | | K A |
|
||||
| POWER-FAIL 2<------------//---------------------+---<2 RXD |
|
||||
| | | | | | |
|
||||
| - - +---<9 RI |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Operation: The UPS can communicate with the Computer |
|
||||
| solely via the RS-232 handshaking lines, or via RS-232 |
|
||||
| serial protocol at 2400-8N1 with software flow control. |
|
||||
| Upon power fail, the UPS forces RI to -V MARK. When the |
|
||||
| battery is low, the UPS forces DCD to +V SPACE via the |
|
||||
| transistor. When the Computer forces a +V SPACE on RTS, |
|
||||
| the UPS will shut down and turn off. Jumpered pins in |
|
||||
| the DB9F connector allow for automatic automatic or PNP |
|
||||
| cable identification by UPS software. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Male (pins) Female (holes) |
|
||||
| DB9 RS-232 PC |
|
||||
| type connector 1 5 5 1 |
|
||||
| ---------------- _______________ _______________ |
|
||||
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||||
| looking into the \ . . . . / \ o o o o / |
|
||||
| end of the cable ----------- ----------- |
|
||||
| 6 9 9 6 |
|
||||
| |
|
||||
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
|
||||
|
||||
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Universal APC serial extension cable for use in conjunction |
|
||||
| with an APC UPS cable. This cable is verified to work. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| DB9M to UPS cable Shielded Cable DB9F to Computer |
|
||||
| ----------------- --- 28AWG ---- ---------------- |
|
||||
| |
|
||||
| (SHELL)<----+-------------//-------------+----<(SHELL) |
|
||||
| | | |
|
||||
| - - |
|
||||
| | | | | |
|
||||
| 1<------------------//------------------<1 DCD |
|
||||
| | | | | |
|
||||
| 2<------------------//------------------<2 RXD |
|
||||
| | | | | |
|
||||
| 3<------------------//------------------<3 TXD |
|
||||
| | | | | |
|
||||
| 4<------------------//------------------<4 DTR |
|
||||
| | | | | |
|
||||
| 5<------------------//------------------<5 SG |
|
||||
| | | | | |
|
||||
| 6<------------------//------------------<6 DSR |
|
||||
| | | | | |
|
||||
| 7<------------------//------------------<7 RTS |
|
||||
| | | | | |
|
||||
| 8<------------------//------------------<8 CTS |
|
||||
| | | | | |
|
||||
| 9<------------------//------------------<9 RI |
|
||||
| | | | | |
|
||||
| - - |
|
||||
| NOTE: The DB shells are connected to each other via the shield. |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
| |
|
||||
| Male (pins) Female (holes) |
|
||||
| DB9 RS-232 PC |
|
||||
| type connector 1 5 5 1 |
|
||||
| ---------------- _______________ _______________ |
|
||||
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||||
| looking into the \ . . . . / \ o o o o / |
|
||||
| end of the cable ----------- ----------- |
|
||||
| 6 9 9 6 |
|
||||
| |
|
||||
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||||
| |
|
||||
+-----------------------------------------------------------------+
|
||||
|
59
docs/cables/ge-imv-victron.txt
Normal file
59
docs/cables/ge-imv-victron.txt
Normal file
|
@ -0,0 +1,59 @@
|
|||
Desc: IMV Victron UPS cables
|
||||
File: victron.txt
|
||||
Date: 13 April 2002
|
||||
Auth: Daniel Prynych <Daniel.Prynych@hornet.cz>
|
||||
|
||||
Data cable 1 for UPS:
|
||||
GE/IMV/Victron Match - 500 700 700L 1000 1000L 1500 2200 3000
|
||||
GE/IMV/Victron NetPro (NetPro 19 ") - 600 1000 1200 2000 3000 4000
|
||||
|
||||
Driver: victronups (newvictronups)
|
||||
|
||||
|
||||
UPS PC 9 pin [2~connector
|
||||
1 --------- 3
|
||||
2 --------- 2
|
||||
5 --------- 5 GND
|
||||
4 DTR
|
||||
|
|
||||
1 DCD
|
||||
|
||||
------------------------------------
|
||||
|
||||
Data cable 2 for UPS:
|
||||
GE/IMV Victron Match Lite (all types)
|
||||
|
||||
|
||||
Driver: victronups (newvictronups)
|
||||
|
||||
UPS PC 9 pin connector
|
||||
2 --------- 3
|
||||
3 --------- 2
|
||||
4 --------- 5 GND
|
||||
4 DTR
|
||||
|
|
||||
1 DCD
|
||||
|
||||
-----------------------------------
|
||||
|
||||
Crack cable: for UPS
|
||||
|
||||
Victron Lite (no IMV Victron Match Lite)
|
||||
|
||||
|
||||
Driver: genericsups
|
||||
|
||||
UPS PC 9 pin connector
|
||||
1 ---------- 4 DTR
|
||||
7 ---------- 1 DCD ----------+
|
||||
9 ---------- 8 CTS -----+ |
|
||||
5 ---------- 5 GND | |
|
||||
| |
|
||||
R R 6,8k - 10k ohm
|
||||
| |
|
||||
7 RTS------+----+
|
||||
|
||||
----------------------------------------------
|
||||
GE is General Electric Company.
|
||||
|
||||
On July 31, 2001, the General Electric Company, acquisited IMV (Victron) company.
|
12
docs/cables/imv.txt
Normal file
12
docs/cables/imv.txt
Normal file
|
@ -0,0 +1,12 @@
|
|||
Desc: IMV Match19 700 - 1500
|
||||
File: imv.txt
|
||||
Date: 06 April 2002
|
||||
Auth: Niels S. Richthof <niels@richthof.de>
|
||||
|
||||
|
||||
"UPS-VIC23-2" PC 9 pin connector
|
||||
|
||||
1 ---------------- 3
|
||||
2 ---------------- 2
|
||||
4 ---------------- 7
|
||||
5 ---------------- 5
|
52
docs/cables/mgeups.txt
Normal file
52
docs/cables/mgeups.txt
Normal file
|
@ -0,0 +1,52 @@
|
|||
Desc: MGE UPS SYSTEMS serial cable
|
||||
File: mgeups.txt
|
||||
Date: 10 April 2002
|
||||
Auth: Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>
|
||||
|
||||
This document describes the cable for MGE smart protocols : UTalk (ASCII),
|
||||
and SHUT (Serial HID UPS Transfer, binary) .
|
||||
|
||||
First notice that MGE UPS SYSTEMS supply a standard cable, bundled with
|
||||
the UPS unit and compatible with MS Windows and Unices (Ref 66049). For
|
||||
more information, see below note about serial cable, PnP and Unix.
|
||||
|
||||
Cable description
|
||||
-----------------
|
||||
|
||||
UPS COMPUTER
|
||||
MALE DB9 FEMALE DB9
|
||||
|
||||
2 ---------------- 2 TX
|
||||
3 ---------------- 3 RX
|
||||
5 ---------------- 5 GND
|
||||
-- 4
|
||||
|
|
||||
-- 6
|
||||
-- 7
|
||||
|
|
||||
-- 8
|
||||
|
||||
|
||||
UPS connector description
|
||||
-------------------------
|
||||
|
||||
5 4 3 2 1
|
||||
_______________
|
||||
\o o o o o/
|
||||
\ o o o o/
|
||||
---------
|
||||
9 8 7 6
|
||||
|
||||
9 pin Male DB-9 connector on UPS
|
||||
|
||||
|
||||
Notes
|
||||
-----
|
||||
- this is a universal serial cable, so it should work with
|
||||
any MGE serial model.
|
||||
- max. length of cable is 1,80 m.
|
||||
- Computer pin 6 (RTS) is reserved for PnP use, which could
|
||||
trouble communication on some Unices if cabled. However, new
|
||||
models (such as Ellipse, Evolution, Pulsar and Comet EXtreme,
|
||||
EXtreme C, ...) handle this, so you can safely cable pin 6 or
|
||||
use a standard (bundled) "windows" cable (Ref 66049).
|
26
docs/cables/powerware.txt
Normal file
26
docs/cables/powerware.txt
Normal file
|
@ -0,0 +1,26 @@
|
|||
Desc: Powerware 3115 factory cable
|
||||
File: powerware.txt
|
||||
Date: 22 July 2005
|
||||
Auth: various
|
||||
|
||||
1) Powerware 3115 factory cable
|
||||
From Peter Åstrand <altic@lysator.liu.se>
|
||||
|
||||
UPS PC 9 pin connector
|
||||
5 --------- 1
|
||||
2 --------- 2
|
||||
1 --------- 3
|
||||
4 --------- 5
|
||||
6 --------- 8
|
||||
|
||||
2) Powerware 5119 RM Cable Layout
|
||||
From Daniel Thompson <danht@callthenet.com>
|
||||
|
||||
UPS <-----------> PC
|
||||
DB9-M <--------> DB9-F
|
||||
Pin 1 <-----------> Pin 3
|
||||
Pin 2 <-----------> Pin 8
|
||||
Pin 4 <-----------> Pin 4
|
||||
Pin 5 <-----------> Pin 1
|
||||
Shells Grounded Both Ends
|
||||
|
26
docs/cables/repotec.txt
Normal file
26
docs/cables/repotec.txt
Normal file
|
@ -0,0 +1,26 @@
|
|||
Desc: Repotec 800A (800VA) & 162A (1600VA) cable
|
||||
File: repotec.txt
|
||||
Date: 11 April 2001
|
||||
Auth: Theodor Milkov <zimage@delbg.com>
|
||||
|
||||
|
||||
PC UPS
|
||||
|
||||
1 (DCD) <----+---------- 2
|
||||
|
|
||||
R 5.6k
|
||||
|
|
||||
7 (RTS) >----+
|
||||
|
||||
3 (Tx) >--------------- 6
|
||||
|
||||
4 (DTR) <----+---------- 5
|
||||
|
|
||||
R 5.6k
|
||||
|
|
||||
8 (CTS) >----+
|
||||
|
||||
5 (GND) -------------+-- 4
|
||||
|
|
||||
+-- 7
|
||||
|
16
docs/cables/sms.txt
Normal file
16
docs/cables/sms.txt
Normal file
|
@ -0,0 +1,16 @@
|
|||
Desc: SMS UPS cables, for Upsilon compatible SMS UPS
|
||||
File: sms.txt
|
||||
Date: 9 October 2001
|
||||
Auth: Marcio Gomes <tecnica@microlink.com.br>
|
||||
|
||||
|
||||
COMPUTER UPS
|
||||
FEMEA DB9 MACHO DB9
|
||||
2 ---------- 6
|
||||
3 ---------- 9
|
||||
4/8 ---------- 5
|
||||
5 ---------- 8
|
||||
|
||||
- This cable is working with Manager III 1300 VA and 650 VA, SMS Ups's
|
||||
- Jump in computer side pins 4/8 and conect to pin 1 in UPS side
|
||||
- Use megatec driver from Nut Package
|
Loading…