Network UPS Tools Documentation
|
||||
=================================
|
||||
|
||||
:Info: Program support page: <http://www.networkupstools.org/>
|
||||
:Author: Arnaud Quette <aquette.dev@gmail.com> and others, see AUTHORS file.
|
||||
:Copyright: Released under the GNU GPL - see COPYING for details.
|
||||
|
||||
Mailing list details: http://alioth.debian.org/mail/?group_id=30602
|
||||
|
||||
.. contents::
|
||||
|
||||
===========
|
||||
Description
|
||||
===========
|
||||
|
||||
Network UPS Tools is a collection of programs which provide a common
|
||||
interface for monitoring and administering UPS and PDU hardware. NUT comes in
|
||||
two flavors: the "classic" and the "HAL enabled" one.
|
||||
|
||||
The "classic" flavor
|
||||
--------------------
|
||||
|
||||
It is the standard installation that uses a layered approach to connect
|
||||
all of the NUT parts.
|
||||
|
||||
Drivers are provided for a wide assortment of equipment. They
|
||||
understand the specific language of each device and map it back to a
|
||||
compatibility layer. This means both an expensive "smart" protocol UPS
|
||||
and a simple "power strip" model can be handled transparently.
|
||||
|
||||
This information is cached by the network server ``upsd``, which then
|
||||
answers queries from the clients. upsd contains a number of access
|
||||
control features to limit the abilities of the clients. Only authorized
|
||||
hosts may monitor or control your hardware if you wish. Since the
|
||||
notion of monitoring over the network is built into the software, you
|
||||
can hang many systems off one large UPS and they will all shut down
|
||||
together. You can also use NUT to power on, off or cycle your data centers
|
||||
nodes, individually or globally through PDUs outlets.
|
||||
|
||||
Clients such as upsmon check on the status of the hardware and do things
|
||||
when necessary. The most important task is shutting down the operating
|
||||
system cleanly before the UPS runs out of power. Other programs are
|
||||
also provided to log UPS status regularly, monitor status through your
|
||||
web browser, and more.
|
||||
|
||||
The "HAL enabled" flavor
|
||||
------------------------
|
||||
|
||||
This one is intended for use:
|
||||
|
||||
- with supported USB UPS,
|
||||
- on HAL enabled systems (Linux, FreeBSD, Sun Solaris),
|
||||
- on HAL enabled desktops (Gnome and possibly KDE)
|
||||
|
||||
Using this approach, you don't have to configure NUT files, nor to
|
||||
manually start components, nor to install a specific NUT client.
|
||||
|
||||
Upon plugging your USB UPS, the right driver will be automatically
|
||||
launched, and the according Power Manager GUI will pop up.
|
||||
|
||||
Note that this feature is still beta and incomplete. But it
|
||||
represents a major evolution, and a huge user experience improvement!
|
||||
|
||||
For more information, refer to INSTALL and docs/nut-hal.txt.
|
||||
|
||||
==========
|
||||
Installing
|
||||
==========
|
||||
|
||||
If you are installing these programs for the first time, go read the
|
||||
INSTALL file to find out how to do that. This document contains more
|
||||
information on what all of this stuff does.
|
||||
|
||||
|
||||
=========
|
||||
Upgrading
|
||||
=========
|
||||
|
||||
When upgrading from an older version, always check the UPGRADING file to
|
||||
see what may have changed. Compatibility issues and other changes will
|
||||
be listed there to ease the process.
|
||||
|
||||
|
||||
=============
|
||||
Documentation
|
||||
=============
|
||||
|
||||
This file gives an overview of the software. You should read the man
|
||||
pages, included example configuration files, and auxiliary documentation
|
||||
for the parts that you intend to use.
|
||||
|
||||
|
||||
===================
|
||||
Network Information
|
||||
===================
|
||||
|
||||
These programs are designed to share information over the network. In
|
||||
the examples below, ``localhost`` is used as the hostname. This can also
|
||||
be an IP address or a fully qualified domain name. You can specify a
|
||||
port number if your upsd process runs on another port.
|
||||
|
||||
In the case of the program ``upsc``, to view the variables on the UPS called
|
||||
sparky on the ``upsd`` server running on the local machine, you'd do this::
|
||||
|
||||
/usr/local/ups/bin/upsc sparky@localhost
|
||||
|
||||
The default port number is 3493. You can change this with
|
||||
"configure --with-port" at compile-time. To make a client talk to upsd
|
||||
on a specific port, add it after the hostname with a colon, like this::
|
||||
|
||||
/usr/local/ups/bin/upsc sparky@localhost:1234
|
||||
|
||||
This is handy when you have a mixed environment and some of the systems
|
||||
are on different ports.
|
||||
|
||||
The general form for UPS identifiers is this::
|
||||
|
||||
<upsname>[@<hostname>[:<port>]]
|
||||
|
||||
Keep this in mind when viewing the examples below.
|
||||
|
||||
|
||||
========
|
||||
Manifest
|
||||
========
|
||||
|
||||
This package is broken down into several categories:
|
||||
|
||||
- *drivers* - These programs talk directly to your UPS hardware.
|
||||
|
||||
- *server* - upsd serves data from the drivers to the network.
|
||||
|
||||
- *clients* - They talk to upsd and do things with the status data.
|
||||
|
||||
- *cgi-bin* - Special class of clients that you can use with your web server.
|
||||
|
||||
|
||||
=======
|
||||
Drivers
|
||||
=======
|
||||
|
||||
These programs provide support for specific UPS models. They understand
|
||||
the protocols and port specifications which define status information
|
||||
and convert it to a form that upsd can understand.
|
||||
|
||||
To configure drivers, edit ups.conf. For this example, we'll have a UPS
|
||||
called "sparky" that uses the apcsmart driver and is connected to
|
||||
``/dev/ttyS1``. That's the second serial port on most Linux-based systems.
|
||||
The entry in ``ups.conf`` looks like this::
|
||||
|
||||
[sparky]
|
||||
driver = apcsmart
|
||||
port = /dev/ttyS1
|
||||
|
||||
To start and stop drivers, use upsdrvctl. By default, it will start or
|
||||
stop every UPS in the config file::
|
||||
|
||||
/usr/local/ups/bin/upsdrvctl start
|
||||
/usr/local/ups/bin/upsdrvctl stop
|
||||
|
||||
However, you can also just start or stop one by adding its name::
|
||||
|
||||
/usr/local/ups/bin/upsdrvctl start sparky
|
||||
/usr/local/ups/bin/upsdrvctl stop sparky
|
||||
|
||||
To get the driver name for your device, refer to the below section
|
||||
called "HARDWARE SUPPORT TABLE".
|
||||
|
||||
Extra Settings
|
||||
--------------
|
||||
|
||||
Some drivers may require additional settings to properly communicate
|
||||
with your hardware. If it doesn't detect your UPS by default, check the
|
||||
driver's man page or help (-h) to see which options are available.
|
||||
|
||||
For example, the apcsmart driver allows setting "cable" to "940-0095B".
|
||||
To use this feature, just add another line to your ups.conf section for
|
||||
that UPS::
|
||||
|
||||
[sparky]
|
||||
driver = apcsmart
|
||||
port = /dev/ttyS1
|
||||
cable = 940-0095B
|
||||
|
||||
Hardware Support Table
|
||||
----------------------
|
||||
|
||||
The NUT Hardware support table is available in the source directory:
|
||||
|
||||
nut-X.Y.Z/data/driver.list
|
||||
|
||||
This one should also be distributed with your favorite packages.
|
||||
For example, it is available on Debian systems as:
|
||||
|
||||
/usr/share/nut/driver.list
|
||||
|
||||
For another take on this list, try the web page:
|
||||
|
||||
http://random.networkupstools.org/compat/
|
||||
|
||||
If your driver has vanished, see the FAQ and UPGRADING files.
|
||||
|
||||
Generic UPS Driver
|
||||
------------------
|
||||
|
||||
The ``genericups`` driver will support many models that use the same basic
|
||||
principle to communicate with the computer. This is known as "contact
|
||||
closure", and basically involves raising or lowering signals to indicate
|
||||
power status.
|
||||
|
||||
This type of UPS tends to be cheaper, and only provides the very simplest
|
||||
data about power and battery status. Advanced features like battery
|
||||
charge readings and such require a "smart" UPS and a driver which
|
||||
supports it.
|
||||
|
||||
See the genericups(8) man page for more information.
|
||||
|
||||
There is also a document called contact-closure.txt included with the
|
||||
source distribution that contains information on this kind of hardware
|
||||
and details on adding additional types to the genericups driver.
|
||||
|
||||
UPS Shutdowns
|
||||
-------------
|
||||
|
||||
upsdrvctl can also shut down (power down) all of your UPS hardware.
|
||||
|
||||
**WARNING:** if you play around with this command, expect your filesystems
|
||||
to die. Don't power off your computers unless they're ready for it::
|
||||
|
||||
/usr/local/ups/bin/upsdrvctl shutdown
|
||||
/usr/local/ups/bin/upsdrvctl shutdown sparky
|
||||
|
||||
You should read the shutdown.txt file in the docs subdirectory to
|
||||
learn more about when to use this feature. If called at the wrong time,
|
||||
you may cause data loss by turning off a system with a filesystem
|
||||
mounted read-write.
|
||||
|
||||
|
||||
==============
|
||||
Network Server
|
||||
==============
|
||||
|
||||
``upsd`` is responsible for passing data from the drivers to the client
|
||||
programs via the network. It should be run immediately after ``upsdrvctl``
|
||||
in your system's startup scripts.
|
||||
|
||||
``upsd`` should be kept running whenever possible, as it is the only source
|
||||
of status information for the monitoring clients like ``upsmon``.
|
||||
|
||||
|
||||
======
|
||||
upsmon
|
||||
======
|
||||
|
||||
``upsmon`` provides the essential feature that you expect to find in UPS
|
||||
monitoring software: safe shutdowns when the power fails.
|
||||
|
||||
In the layered scheme of NUT software, it is a client. It has this
|
||||
separate section in the documentation since it is so important.
|
||||
|
||||
You configure it by telling it about UPSes that you want to monitor in
|
||||
upsmon.conf. Each UPS can be defined as one of three possible types:
|
||||
|
||||
- Master
|
||||
|
||||
This UPS supplies power to the system running upsmon, and
|
||||
this system is also responsible for shutting it down when
|
||||
the battery is depleted. This occurs after any slave systems
|
||||
have disconnected safely.
|
||||
|
||||
If your UPS is plugged directly into a system's serial port,
|
||||
the upsmon on that system should define that UPS as a master.
|
||||
|
||||
- Slave
|
||||
|
||||
This UPS supplies power to the system running upsmon, but
|
||||
this system can't shut it down directly. This system will
|
||||
shut down the operating system before the master turns off the
|
||||
power.
|
||||
|
||||
Use this mode when you run multiple computers on the same UPS.
|
||||
Obviously, only one can be connected to the serial port on the
|
||||
UPS, and that system is the master. Everything else is a
|
||||
slave.
|
||||
|
||||
- Monitor-only
|
||||
|
||||
This UPS will still generate notifications about status
|
||||
changes (on battery, on line, etc.) but no shutdowns of the
|
||||
local system result from critical situations on that UPS.
|
||||
|
||||
For a typical home user, there's one computer connected to one UPS.
|
||||
That means you run a driver, upsd, and upsmon in master mode.
|
||||
|
||||
Additional Information
|
||||
----------------------
|
||||
|
||||
More information on configuring upsmon can be found in these places:
|
||||
|
||||
- The man page - upsmon(8)
|
||||
|
||||
- big-servers.txt in the docs subdirectory
|
||||
|
||||
- shutdown.txt in the docs subdirectory
|
||||
|
||||
- The stock upsmon.conf that comes with the package
|
||||
|
||||
|
||||
=======
|
||||
Clients
|
||||
=======
|
||||
|
||||
Clients talk to upsd over the network and do useful things with the data
|
||||
from the drivers. There are tools for command line access, and a few
|
||||
special clients which can be run through your web server as CGI
|
||||
programs.
|
||||
|
||||
For more details on specific programs, refer to their man pages.
|
||||
|
||||
upsc
|
||||
----
|
||||
|
||||
upsc is a simple client that will display the values of variables known
|
||||
to upsd and your UPS drivers. It will list every variable by default,
|
||||
or just one if you specify an additional argument. This can be useful
|
||||
in shell scripts for monitoring something without writing your own
|
||||
network code.
|
||||
|
||||
upsc is a quick way to find out if your driver(s) and upsd are working
|
||||
together properly. Just run upsc <ups> to see what's going on, i.e.::
|
||||
|
||||
morbo:~$ upsc su700@localhost
|
||||
ambient.humidity: 035.6
|
||||
ambient.humidity.alarm.maximum: NO,NO
|
||||
ambient.humidity.alarm.minimum: NO,NO
|
||||
ambient.temperature: 25.14
|
||||
|
||||
[ and so on ]
|
||||
|
||||
If you are interested in writing a simple client that monitors upsd,
|
||||
the source code for upsc is a good way to learn about using the
|
||||
upsclient functions.
|
||||
|
||||
See the upsc(8) man page for more information.
|
||||
|
||||
upslog
|
||||
------
|
||||
|
||||
upslog will write status information from upsd to a file at set
|
||||
intervals. You can use this to generate graphs or reports with other
|
||||
programs such as gnuplot.
|
||||
|
||||
upsrw
|
||||
-----
|
||||
|
||||
upsrw allows you to display and change the read/write variables in your
|
||||
UPS hardware. Not all devices or drivers implement this, so this may
|
||||
not have any effect on your system.
|
||||
|
||||
A driver that supports read/write variables will give results like this::
|
||||
|
||||
$ upsrw su700@localhost
|
||||
|
||||
( many skipped )
|
||||
|
||||
[ups.test.interval]
|
||||
Interval between self tests
|
||||
Type: ENUM
|
||||
Option: "1209600"
|
||||
Option: "604800" SELECTED
|
||||
Option: "0"
|
||||
|
||||
( more skipped )
|
||||
|
||||
On the other hand, one that doesn't support them won't print anything::
|
||||
|
||||
$ upsrw fenton@gearbox
|
||||
|
||||
( nothing )
|
||||
|
||||
upsrw requires administrator powers to change settings in the hardware.
|
||||
Refer to upsd.users(5) for information on defining users in upsd.
|
||||
|
||||
upscmd
|
||||
------
|
||||
|
||||
Some UPS hardware and drivers support the notion of an instant command -
|
||||
a feature such as starting a battery test, or powering off the load.
|
||||
You can use upscmd to list or invoke instant commands if your
|
||||
hardware/drivers support them.
|
||||
|
||||
Use the -l command to list them, like this::
|
||||
|
||||
$ upscmd -l su700@localhost
|
||||
Instant commands supported on UPS [su700@localhost]:
|
||||
|
||||
load.on - Turn on the load immediately
|
||||
test.panel.start - Start testing the UPS panel
|
||||
calibrate.start - Start run time calibration
|
||||
calibrate.stop - Stop run time calibration
|
||||
|
||||
[ snip ]
|
||||
|
||||
upscmd requires administrator powers to start instant commands.
|
||||
To define users and passwords in upsd, see upsd.users(5).
|
||||
|
||||
============
|
||||
CGI Programs
|
||||
============
|
||||
|
||||
The CGI programs are clients that run through your web server. They
|
||||
allow you to see UPS status and perform certain administrative commands
|
||||
from any web browser. Javascript and cookies are not required.
|
||||
|
||||
These programs are not installed or compiled by default. To compile
|
||||
and install them, first run 'configure --with-cgi', then do 'make' and
|
||||
'make install'. If you receive errors about "gd" during configure, go
|
||||
get it and install it before continuing.
|
||||
|
||||
You can get the source here:
|
||||
|
||||
http://www.boutell.com/gd/
|
||||
|
||||
In the event that you need libpng or zlib in order to compile gd,
|
||||
they can be found at these URLs:
|
||||
|
||||
http://www.libpng.org/pub/png/pngcode.html
|
||||
|
||||
http://www.gzip.org/zlib/
|
||||
|
||||
Access Restrictions
|
||||
-------------------
|
||||
|
||||
The CGI programs use hosts.conf to see if they are allowed to talk to a
|
||||
host. This keeps malicious visitors from creating queries from your web
|
||||
server to random hosts on the Internet.
|
||||
|
||||
If you get error messages that say "Access to that host is not
|
||||
authorized", you're probably missing an entry in your hosts.conf.
|
||||
|
||||
upsstats
|
||||
--------
|
||||
|
||||
upsstats generates web pages from HTML templates, and plugs in status
|
||||
information in the right places. It looks like a distant relative of
|
||||
APC's old Powerchute interface. You can use it to monitor several
|
||||
systems or just focus on one.
|
||||
|
||||
It also can generate IMG references to upsimage.
|
||||
|
||||
upsimage
|
||||
--------
|
||||
|
||||
This is usually called by upsstats via IMG SRC tags to draw either the
|
||||
utility or outgoing voltage, battery charge percent, or load percent.
|
||||
|
||||
upsset
|
||||
------
|
||||
|
||||
upsset provides several useful administration functions through a web
|
||||
interface. You can use upsset to kick off instant commands on your UPS
|
||||
hardware like running a battery test. You can also use it to change
|
||||
variables in your UPS that accept user-specified values.
|
||||
|
||||
Essentially, upsset provides the functions of upsrw and upscmd, but
|
||||
with a happy pointy-clicky interface.
|
||||
|
||||
upsset will not run until you convince it that you have secured your
|
||||
system. You *must* secure your CGI path so that random interlopers
|
||||
can't run this program remotely. See the upsset.conf file. Once you
|
||||
have secured the directory, you can enable this program in that
|
||||
configuration file. It is not active by default.
|
||||
|
||||
|
||||
=====================
|
||||
Support / Help / etc.
|
||||
=====================
|
||||
|
||||
The main URL:
|
||||
|
||||
http://www.networkupstools.org/
|
||||
|
||||
There is also a mailing list for general queries and discussion about
|
||||
this software called nut-upsuser. It typically moves around 50-100 messages
|
||||
per month at the time of this writing. To join, go to the below address and
|
||||
subscribe to the desired list.
|
||||
|
||||
Finally, there is a developer list called nut-upsdev. This is not
|
||||
an install help list, and any such mails probably will be ignored.
|
||||
|
||||
The mailing lists are archived on the web:
|
||||
|
||||
http://alioth.debian.org/mail/?group_id=30602
|
||||
|
||||
Try running some searches against the archives. Many times, problems have
|
||||
already been answered by someone else. Currently, there is no internal
|
||||
search engine, so you will have to try with a search engine like Google.
|
||||
|
||||
There is more documentation in the docs/ directory within the source
|
||||
tree. Be sure to read through the files in there (especially the
|
||||
FAQ) before mailing the list for help. Many times the questions have
|
||||
already been answered in the files which are right in front of you.
|
||||
|
||||
|
||||
===================================
|
||||
Making your own clients (upsclient)
|
||||
===================================
|
||||
|
||||
The upsclient.a library can be linked into other programs to give access
|
||||
to upsd and UPS status information. Clients like upsc are provided as
|
||||
examples of how to retrieve data using the upsclient functions. Other
|
||||
programs not included in this package may also use this library, as wmnut.
|
||||
|
||||
This library file and the associated header files are not installed by
|
||||
default. You must './configure --with-lib' to enable building and
|
||||
installing these files. The libraries can then be build and installed
|
||||
with 'make' and 'make install' as usual. This must be done before
|
||||
building other (non-NUT) programs which depend on them.
|
||||
|
||||
To obtain the right compilation and link flags, two helpers are provided:
|
||||
one for platform providing pkg-config, and the other (libupsclient-config)
|
||||
for platform not providing pkg-config.
|
||||
|
||||
|
||||
=================
|
||||
Version Numbering
|
||||
=================
|
||||
|
||||
The version numbers work like this: if the middle number is odd, it's a
|
||||
development tree, otherwise it is the stable tree.
|
||||
|
||||
The past stable trees were 1.0, 1.2, 1.4 and 2.0, with the latest stable tree
|
||||
designated 2.2. The development trees were 1.1, 1.3, 1.5 and 2.1.
|
||||
|
||||
The jump to 2.2 is mostly due to the large changes to the features list.
|
||||
There have also been a number of architectural changes which may not be
|
||||
noticeable to most users.
|
||||
|
||||
|
||||
====================================
|
||||
Backwards and Forwards Compatibility
|
||||
====================================
|
||||
|
||||
The old network code spans a range from about 0.41.1 when TCP support
|
||||
was introduced up to the recent 1.4 series. It used variable names
|
||||
like STATUS, UTILITY, and LOADPCT. Many of these names go back to the
|
||||
earliest prototypes of this software from 1997. At that point there
|
||||
was no way to know that so many drivers would come along and introduce
|
||||
so many new variables and commands. The resulting mess grew out of
|
||||
control over the years.
|
||||
|
||||
During the 1.3 development cycle, all variables and instant commands
|
||||
were renamed to fit into a tree-like structure. There are major groups,
|
||||
like input, output and battery. Members of those groups have been
|
||||
arranged to make sense - input.voltage and output.voltage compliment
|
||||
each other. The old names were UTILITY and OUTVOLT. The benefits in
|
||||
this change are obvious.
|
||||
|
||||
The 1.4 clients can talk to either type of server, and can handle either
|
||||
naming scheme. 1.4 servers have a compatibility mode where they can
|
||||
answer queries for both names, even though the drivers are internally
|
||||
using the new format.
|
||||
|
||||
When 1.4 clients talk to 1.4 or 2.0 (or more recent) servers, they will
|
||||
use the new names.
|
||||
|
||||
Here's a table to make it easier to visualize:
|
||||
|
||||
+--------+------------------------+
|
||||
| | Server |
|
||||
+--------+-----+-----+-----+------+
|
||||
| Client | 1.0 | 1.2 | 1.4 | 2.0+ |
|
||||
+========+=====+=====+=====+======+
|
||||
| 1.0 | yes | yes | yes | no |
|
||||
+--------+-----+-----+-----+------+
|
||||
| 1.2 | yes | yes | yes | no |
|
||||
+--------+-----+-----+-----+------+
|
||||
| 1.4 | yes | yes | yes | yes |
|
||||
+--------+-----+-----+-----+------+
|
||||
| 2.0 | no | no | yes | yes |
|
||||
+--------+-----+-----+-----+------+
|
||||
|
||||
Version 2.0 (and more recent) does not contain backwards compatibility for
|
||||
the old protocol and variable/command names. As a result, 2.0 clients can't
|
||||
talk to anything older than a 1.4 server. If you ask a 2.0 client to
|
||||
fetch "STATUS", it will fail. You'll have to ask for "ups.status"
|
||||
instead.
|
||||
|
||||
Authors of separate monitoring programs should have used the 1.4 series
|
||||
to write support for the new variables and command names. Client
|
||||
software can easily support both versions as long as they like. If upsd
|
||||
returns 'ERR UNKNOWN-COMMAND' to a GET request, you need to use REQ.
|
||||
|
||||
|
||||
==========================
|
||||
Hacking / Development Info
|
||||
==========================
|
||||
|
||||
Additional documentation can be found in the docs subdirectory.
|
||||
|
||||
Information on creating new drivers can be found in new-drivers.txt.
|
||||
Also be sure to look at skel.c and main.c. All drivers are just
|
||||
collections of support functions built around a common core, so most of
|
||||
the dull housekeeping work has been handled for you.
|
||||
|
||||
Information on the NUT variables naming can be found in new-names.txt.
|
||||
Information on the architecture and how it all fits together is in the
|
||||
design.txt file. In short, there's a lot more documentation out there.
|
||||
|
||||
Also be sure to read developers.txt, as it explains a lot about the
|
||||
tree, including some of the functions that are provided for your use.
|
||||
|
||||
|
||||
================================
|
||||
Acknowledgements / Contributions
|
||||
================================
|
||||
|
||||
MGE UPS SYSTEMS provided extensive technical documents for their UPS product
|
||||
line, along with many units for development of NUT-related projects. The
|
||||
company also sponsored and later hired Arnaud Quette to further officially
|
||||
support these efforts.
|
||||
|
||||
Several drivers such as mge-utalk, mge-shut, snmp-ups, hidups, and usbhid-ups
|
||||
are the result of this collaboration, in addition to the WMNut, MGE HID Parser
|
||||
the libhid projects, .... The features page has improved artwork thanks to Luc
|
||||
and Arnaud of MGE. Other client projects such as KNutClient and ups-monitor
|
||||
have also received assistance.
|
||||
|
||||
The master NUT site and several related projects are hosted on MGE's equipment
|
||||
at no cost to the project.
|
||||
|
||||
More information on their open source support can be found on their web site:
|
||||
http://opensource.mgeups.com/contrib.htm
|
||||
|
||||
Fenton Technologies contributed a PowerPal 660 to the project. Their open
|
||||
stance and quick responses to technical inquiries are appreciated for
|
||||
making the development of the fentonups driver possible.
|
||||
|
||||
Bo Kersey of VirCIO (http://www.vircio.com) provided a Best Power
|
||||
Fortress 750 to facilitate the bestups driver.
|
||||
|
||||
Invensys Energy Systems provided the SOLA/Best "Phoenixtec" protocol
|
||||
document currently residing at the following URL:
|
||||
|
||||
http://random.networkupstools.org/protocols/sola.html
|
||||
|
||||
PowerKinetics technical support provided documentation on their MiniCOL
|
||||
protocol, which is archived in the NUT protocol library online:
|
||||
|
||||
http://random.networkupstools.org/protocols/minicol/
|
||||
|
||||
Cyber Power Systems contributed a 700AVR model for testing and driver
|
||||
development.
|
||||
|
||||
Liebert Corporation supplied serial test boxes and a UPStation GXT2
|
||||
with the Web/SNMP card for development of the liebert driver and
|
||||
expansion of the existing snmp-ups driver.
|
||||
|
Loading…
Add table
Add a link
Reference in a new issue