Imported Upstream version 2.7.1
This commit is contained in:
parent
a1fa151fc7
commit
0121794af9
451 changed files with 41339 additions and 10887 deletions
|
|
@ -36,7 +36,7 @@
|
|||
#include "usbhid-ups.h"
|
||||
#include "mge-hid.h"
|
||||
|
||||
#define MGE_HID_VERSION "MGE HID 1.31"
|
||||
#define MGE_HID_VERSION "MGE HID 1.32"
|
||||
|
||||
/* (prev. MGE Office Protection Systems, prev. MGE UPS SYSTEMS) */
|
||||
/* Eaton */
|
||||
|
|
@ -268,6 +268,12 @@ static info_lkp_t mge_battery_capacity[] = {
|
|||
{ 0, NULL, mge_battery_capacity_fun }
|
||||
};
|
||||
|
||||
info_lkp_t eaton_enable_disable_info[] = {
|
||||
{ 0, "disabled", NULL },
|
||||
{ 1, "enabled", NULL },
|
||||
{ 0, NULL, NULL }
|
||||
};
|
||||
|
||||
static info_lkp_t mge_upstype_conversion[] = {
|
||||
{ 1, "offline / line interactive", NULL },
|
||||
{ 2, "online", NULL },
|
||||
|
|
@ -893,6 +899,7 @@ static hid_info_t mge_hid2nut[] =
|
|||
{ "ups.start.auto", ST_FLAG_RW | ST_FLAG_STRING, 5, "UPS.PowerConverter.Input.[1].AutomaticRestart", NULL, "%s", HU_FLAG_SEMI_STATIC, yes_no_info },
|
||||
{ "ups.start.battery", ST_FLAG_RW | ST_FLAG_STRING, 5, "UPS.PowerConverter.Input.[3].StartOnBattery", NULL, "%s", HU_FLAG_SEMI_STATIC, yes_no_info },
|
||||
{ "ups.start.reboot", ST_FLAG_RW | ST_FLAG_STRING, 5, "UPS.PowerConverter.Output.ForcedReboot", NULL, "%s", HU_FLAG_SEMI_STATIC, yes_no_info },
|
||||
{ "ups.shutdown", ST_FLAG_RW | ST_FLAG_STRING, 10, "UPS.PowerSummary.PresentStatus.Switchable", NULL, "%s", HU_FLAG_SEMI_STATIC | HU_FLAG_ENUM, eaton_enable_disable_info },
|
||||
#ifdef HAVE_STRPTIME
|
||||
{ "ups.date", ST_FLAG_RW | ST_FLAG_STRING, 10, "UPS.PowerSummary.Time", NULL, "%s", 0, mge_date_conversion },
|
||||
{ "ups.time", ST_FLAG_RW | ST_FLAG_STRING, 10, "UPS.PowerSummary.Time", NULL, "%s", 0, mge_time_conversion },
|
||||
|
|
@ -924,8 +931,11 @@ static hid_info_t mge_hid2nut[] =
|
|||
{ "BOOL", 0, 0, "UPS.PowerConverter.Input.[1].PresentStatus.VoltageOutOfRange", NULL, NULL, 0, vrange_info },
|
||||
{ "BOOL", 0, 0, "UPS.PowerConverter.Input.[1].PresentStatus.FrequencyOutOfRange", NULL, NULL, 0, frange_info },
|
||||
{ "BOOL", 0, 0, "UPS.PowerSummary.PresentStatus.Good", NULL, NULL, 0, off_info },
|
||||
#if 0
|
||||
/* TODO: UPS.BatterySystem.Charger.PresentStatus.Used is related to ABM */
|
||||
{ "BOOL", 0, 0, "UPS.BatterySystem.Charger.PresentStatus.Used", NULL, NULL, 0, off_info },
|
||||
/* FIXME: on Dell, the above requires an "AND" with "UPS.BatterySystem.Charger.Mode = 4 (ABM Resting)" */
|
||||
#endif
|
||||
{ "BOOL", 0, 0, "UPS.PowerConverter.Input.[2].PresentStatus.Used", NULL, NULL, 0, bypass_auto_info }, /* Automatic bypass */
|
||||
{ "BOOL", 0, 0, "UPS.PowerConverter.Input.[4].PresentStatus.Used", NULL, NULL, 0, bypass_manual_info }, /* Manual bypass */
|
||||
{ "BOOL", 0, 0, "UPS.PowerSummary.PresentStatus.FanFailure", NULL, NULL, 0, fanfail_info },
|
||||
|
|
@ -1099,7 +1109,13 @@ static char *get_model_name(const char *iProduct, const char *iModel)
|
|||
|
||||
/* Search for device type and formatting rules */
|
||||
for (model = mge_model_names; model->iProduct; model++) {
|
||||
upsdebugx(2, "comparing with: %s", model->name);
|
||||
if(model->name) {
|
||||
upsdebugx(2, "comparing with: %s", model->name);
|
||||
}
|
||||
else {
|
||||
upsdebugx(2, "comparing with: %s %s", model->iProduct,
|
||||
model->iModel);
|
||||
}
|
||||
|
||||
if (strcmp(iProduct, model->iProduct)) {
|
||||
continue;
|
||||
|
|
@ -1167,8 +1183,7 @@ static const char *mge_format_serial(HIDDevice_t *hd) {
|
|||
static int mge_claim(HIDDevice_t *hd) {
|
||||
|
||||
#ifndef SHUT_MODE
|
||||
int status = is_usb_device_supported(mge_usb_device_table, hd->VendorID,
|
||||
hd->ProductID);
|
||||
int status = is_usb_device_supported(mge_usb_device_table, hd);
|
||||
|
||||
switch (status) {
|
||||
|
||||
|
|
|
|||
Loading…