nut/man/mge-shut.8

71 lines
2.5 KiB
Groff
Raw Permalink Normal View History

2010-03-25 23:20:59 +00:00
.TH mge\-shut 8 "Thu Nov 19 2009" "" "Network UPS Tools (NUT)"
.SH NAME
mge\(hyshut, newmge\(hyshut \- Driver for SHUT Protocol UPS equipment
.SH NOTE
This man page only documents the hardware\(hyspecific features of the
mge\(hyshut driver. For information about the core driver, see
\fBnutupsdrv\fR(8).
.SH SUPPORTED HARDWARE
mge\(hyshut support all recent Eaton, MGE and Dell UPS models which use the SHUT
(Serial HID UPS Transfer) protocol.
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U\(hyTalk
protocol and should use the mge\(hyutalk driver.
.SH EXTRA ARGUMENTS
This driver supports the following optional settings in the
\fBups.conf\fR(5):
.IP "lowbatt=\fInum\fR"
Set the low battery warning threshold at which shutdown is initiated by
\fBupsmon\fR(8).
The factory default value is 30 (in percentage), and only be settable
depending on the exact model.
.IP "offdelay=\fInum\fR"
Set the timer before the UPS is turned off after the kill power command is
sent (via the \fI\-k\fR switch).
The default value is 20 (in seconds), and MUST BE LOWER than ondelay.
.IP "ondelay=\fInum\fR"
Set the timer for the UPS to switch on in case the power returns after the
kill power command had been sent but before the actual switch off. This
ensures the machines connected to the UPS are, in all cases, rebooted after
a power failure.
The default value is 3 (in 10 seconds units, which means 30 seconds),
and MUST BE GREATER than offdelay.
.IP "notification=\fInum\fR"
Set notification type to 1 (no), 2 (light) or 3 (yes).
The default value is 3 (yes) because of some early Ellipse models which
need it.
.SH KNOWN ISSUES
.SS "Pulsar Ellipse S: Repetitive stale status \(hy Loss of communication"
Several users have reported "data stale" errors with Pulsar Ellipse
equipment. This lasts around 10 seconds and happens once every few hours.
This is due to the fact that the SHUT protocol is verbose, and the driver
sometimes does not handle all of it during the usual polling interval in
upsd. To solve this problem, change the value of MAXAGE to 25 in
upsd.conf. Also add "notification=3" in ups.conf (thanks to Julien
Lesaint and Fabien).
.SH AUTHOR
Arnaud Quette <arnaud.quette@free.fr> or <arnaud.quette@mgeups.com>
Philippe Marzouk <philm@users.sourceforge.net>
.SH SEE ALSO
.SS The core driver:
\fBnutupsdrv\fR(8)
.SS Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
MGE UPS SYSTEMS SHUT protocol information:
http://random.networkupstools.org/protocols/mge/