nut/man/belkinunv.8

328 lines
11 KiB
Groff
Raw Normal View History

2010-03-25 23:20:59 +00:00
.TH BELKINUNV 8 "Sun Dec 7 2003" "" "Network UPS Tools (NUT)"
.SH NAME
belkinunv \- Driver for Belkin "Universal UPS" and compatible
.SH NOTE
This man page only documents the hardware\(hyspecific features of the
belkin driver. For information about the core driver, see
\fBnutupsdrv\fP(8).
.SH SUPPORTED HARDWARE
The belkinunv driver is known to work with the Belkin Universal UPS
models F6C800\(hyUNV and F6C120\(hyUNV, and is expected to work with other
Belkin Universal UPS models. The driver only supports serial
communication, not USB.
The Trust UPS and older Belkin units are not supported by this driver,
and neither are the Belkin Home Office models (F6H500\(hySER and so
forth). However, some Belkin models, such as the Regulator Pro, are
supported by the \fBbelkin\fP(8) driver, and the Home Office models
are supported using the \fBgenericups\fP(8) driver with
\fIupstype=7\fP.
.SH SOFT SHUTDOWN WORKAROUND
One problem with the Belkin Universal UPS is that it cannot enter a
soft shutdown (shut down the load until AC power returns) unless the
batteries are completely depleted. Thus, one cannot just shut off the
UPS after operating system shutdown; it will not come back on when the
power comes back on. Therefore, the belkinunv driver should never be
used with the \fB\-k\fP option. Instead, the \fB\-x wait\fP option is
provided as a workaround.
When called with the \fB\-x wait\fP option, \fBbelkinunv\fP behaves as
a standalone program (i.e., it does not fork into the background). It
performs one simple task: it connects to the UPS, waits for AC power
to return, and then exits with status 0.
This is meant to be used in a shutdown script as follows: during a
shutdown, after all filesystems have been remounted read\(hyonly, and
just before the system would normally be halted: check /etc/killpower
(or similar) to see if this shutdown was caused by \fBupsmon\fP(8),
and if yes, call \fBbelkinunv \-x wait\fP. If AC power comes back on,
\fBbelkinunv\fP exits, and things should be arranged so that the
system reboots in this case. If AC power does not come back on, the
UPS will eventually run out of batteries, kill the computer's power
supply, and go into soft shutdown mode, which means everything will
reboot properly when the power returns. In either case, a deadlock is
avoided.
In addition, if an optional integer argument is given to the \fB\-x
wait\fP option, this causes \fBbelkinunv\fP to wait not only for AC
power to be present, but also for the battery charge to reach the
given level. I use this as part of my startup scripts, to ensure that
the batteries are sufficiently charged before the computer continues
booting. This should be put very early in the startup script, before
any filesystems are mounted read/write, and before any filesystem
checks are performed.
Several other \fB\-x\fP options are provided to fine\(hytune this
behavior. See OPTIONS below for detailed descriptions. See EXAMPLES
below for examples of how to use \fBbelkinunv\fP in shutdown and
startup scripts.
.SH OPTIONS
See also \fBnutupsdrv\fP(8) for generic options. Never use the
\fB\-k\fP option with this driver; it does not work properly.
.TP 12
.B \-x wait[=\fIlevel\fP]
When this option is used, \fBbelkinunv\fP does not fork into the
background, but behaves as a standalone program. It connects to the UPS and
waits until AC power is present. If \fIlevel\fP is specified, it also
waits until the battery charge reaches at least the given level in
percent. Then, and only then, \fBbelkinunv\fP exits. In addition,
while \fBbelkinunv\fP runs in this mode, it displays a status line
with information on the UPS status and battery level. This is intended
for use in the computer's shutdown and startup scripts, as described
under SOFT SHUTDOWN WORKAROUND above.
.TP
.B \-x nohang
This option only has an effect when used in conjunction with the \fB\-x
wait\fP option. It causes \fBbelkinunv\fP to exit if a connection with
the UPS cannot be established or is lost, instead of retrying forever,
which is the default behavior. The \fB\-x nohang\fP option should be
used in a startup
script, to ensure the computer remains bootable even if the UPS has
been disconnected during the power failure (for instance, you attached
your computer to a generator, carried it to a neighbor's house, or
whatever).
.TP
.B \-x flash
This option only has an effect when used in conjunction with the \fB\-x
wait\fP option. It causes the UPS load to be shut off for a short time
("flashed") just after the AC power has returned and the requested
battery level (if any) has been attained. This is useful if slaves are
attached to this UPS; the flash will cause all of them to reboot. Note
that, due to the design of the Belkin UPS hardware, the load shutdown lasts
ca. 1\(hy2 minutes; a shorter flash cannot be performed reliably. Also,
the computers will reboot at the scheduled time, on battery power if
necessary, even if AC power fails again in the meantime. This should
not be a problem, as your startup scripts can catch this situation.
.TP
.B \-x silent
This option only has an effect when used in conjunction with the \fB\-x
wait\fP option. It suppresses the status line which \fBbelkinunv\fP
would normally print.
.TP
.B \-x dumbterm
This option only has an effect when used in conjunction with the \fB\-x
wait\fP option. It changes the way in which \fBbelkinunv\fP prints its
status line. Normally, terminal control sequences are used to
overwrite the same line with new status information, each time the
status is updated. This may not work on all terminals. If the \fB\-x
dumbterm\fP option is given, each status update is written on a new
line.
.PD
.SH VARIABLES:
.TP 12
.B battery.charge
.TP
.B battery.runtime
not supported by all hardware.
.TP
.B battery.voltage
.TP
.B battery.voltage.nominal
.TP
.B driver.version.internal
.TP
.B input.frequency
.TP
.B input.frequency.nominal
e.g. 60 for 60Hz
.TP
.B input.sensitivity
writable: normal/medium/low
.TP
.B input.transfer.high
writable: high transfer voltage point in V
.TP
.B input.transfer.low
writable: low transfer voltage point in V
.TP
.B input.voltage
.TP
.B input.voltage.maximum
.TP
.B input.voltage.minimum
.TP
.B input.voltage.nominal
.TP
.B output.frequency
.TP
.B output.voltage
.TP
.B ups.beeper.status
writable. Values: enabled/disabled/muted. This variable controls the
state of the panel beeper. Enabled means sound when the alarm is
present, disabled means never sound, and muted means the sound is
temporarily disabled until the alarm would normally stop sounding. In
the muted state, the beeper is automatically turned back on at the
next event (AC failure, battery test, etc). Also, the beeper can't be
turned off during a critical event (low battery). Note that not all
UPS models support the "disabled" state.
.TP
.B ups.firmware
.TP
.B ups.load
.TP
.B ups.model
.TP
.B ups.power.nominal
e.g. 800 for an 800VA system
.TP
.B ups.status
a list of flags; see STATUS FLAGS below.
.TP
.B ups.temperature
not supported by all hardware.
.TP
.B ups.test.result
.TP
.B ups.delay.restart
time to restart (read only)
.TP
.B ups.delay.shutdown
time to shutdown (read only). This is always a multiple of 60 seconds.
.TP
.B ups.type
ONLINE/OFFLINE/LINEINT. This describes the basic layout of this UPS
(for GUI clients which want to draw an animated picture of power
flow). An offline UPS has a direct connection from AC input to AC
output, and also a connection from AC input to the battery, and from
the battery to AC output. An online UPS lacks the direct connection
from AC input to AC output, whereas a line interactive UPS lacks the
connection from AC input to the battery.
.PD
.SH COMMANDS:
.TP 12
.B beeper.enable, beeper.disable, beeper.mute
enable, disable or mute the panel beeper. Note that if the beeper is
muted, it is automatically turned back on at the next event (AC failure,
battery test, etc). Also, the beeper can't be turned muted during a
critical event (low battery).
.TP
.B reset.input.minmax
reset the variables \fBinput.voltage.minimum\fP and
\fBinput.voltage.maximum\fP.
.TP
.B shutdown.reboot
shut down load immediately for ca. 1\(hy2 minutes
.TP
.B shutdown.reboot.graceful
after 40 second delay, shut down load for ca. 1\(hy2 minutes
.TP
.B shutdown.stayoff
shut down load immediately and stay off. The only way it can be turned
back on is by manually pressing the front panel button.
.TP
.B test.battery.start, test.battery.stop
start/stop 10 second battery test
.TP
.B test.failure.start, test.failure.stop
start/stop "deep" battery test
.PD
.SH STATUS FLAGS:
.TP 12
.B OB
load is on battery, including during tests
.TP
.B OFF
load is off
.TP
.B OL
load is online
.TP
.B ACFAIL
AC failure. Note that this refers to the AC input, and thus it is not
the same as "OB". An AC failure can occur at any time, for instance,
during a battery test, or when the UPS load is off.
.TP
.B OVER
overload
.TP
.B OVERHEAT
overheat
.TP
.B COMMFAULT
UPS fault
.TP
.B LB
low battery
.TP
.B CHRG
charging
.TP
.B DEPLETED
the battery is depleted. When the UPS raises this flag, it
simultaneously switches off the load.
.TP
.B RB
replace battery
.PD
.SH EXAMPLES
Here is an example for how \fBbelkinunv\fP should be used in a
computer's shutdown script. These commands should go in the very last
part of the shutdown script, after all file systems have been mounted
read\(hyonly, and just before the computer halts. Note that
\fBbelkinunv\fP must be installed in a directory which is still
readable at that point.
.nf
# NEAR END OF SHUTDOWN SCRIPT:
# if shutdown was caused by UPS, perform Belkin UPS workaround.
if [ \-f /etc/killpower ] ; then
echo "Waiting for AC power, or for UPS batteries to run out..."
/usr/bin/belkinunv \-x wait /dev/ttyS1
# we get here if the power came back on. Reboot.
echo "Power is back. Rebooting..."
reboot
fi
.fi
And here is an example of how to use \fBbelkinunv\fP in the startup
script. These commands should go near the beginning of the startup
script, before any file systems are mounted read/write, and before any
file system integrity checks are done.
.nf
# NEAR BEGINNING OF STARTUP SCRIPT:
# if we are recovering from a power failure, wait for the UPS to
# charge to a comfortable level before writing anything to disk
if [ \-f /etc/killpower ] ; then
echo "Waiting for UPS battery charge to reach 60%..."
/usr/bin/belkinunv \-x wait=60 \-x nohang /dev/ttyS1
fi
.fi
.SH EXIT STATUS
When used normally, \fBbelkinunv\fP forks into the background and its
diagnostics are the same as for all NUT drivers, see
\fBnutupsdrv\fP(8).
When used with the \fB\-x wait\fP option, the exit status is normally
0. If the \fB\-x nohang\fP option has also been specified, an exit
status of 1 indicates that communication with the UPS was lost. If the
\fB\-x flash\fP option has been specified, an exit status of 2
indicates that the timed shutdown has failed.
.SH EXTRA ARGUMENTS
This driver does not support any extra settings in \fBups.conf\fP(5).
.SH SEE ALSO
.SS The documentation for the protocol used by this UPS:
belkin\(hyuniversal\(hyups.html
.SS The core driver:
\fBnutupsdrv\fP(8)
.SS Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
.SH AUTHOR
Peter Selinger <selinger@users.sourceforge.net>