nut/drivers/eaton-pdu-marlin-mib.c

1367 lines
56 KiB
C
Raw Normal View History

2022-06-29 10:37:36 +00:00
/* eaton-pdu-marlin-mib.c - data to monitor Eaton ePDUs branded as:
* G2 Marlin SW / MI / MO / MA
* G3 Shark SW / MI / MO / MA
*
* Copyright (C) 2008 - 2020
* Arnaud Quette <arnaud.quette@gmail.com>
* Arnaud Quette <ArnaudQuette@Eaton.com>
* Copyright (C) 2015 - 2017
* Jim Klimov <EvgenyKlimov@Eaton.com>
*
* Supported by Eaton <http://www.eaton.com>
* and previously MGE Office Protection Systems <http://www.mgeops.com>
*
* This program is free software; you can redistribute it and/or modify
* it under the terms of the GNU General Public License as published by
* the Free Software Foundation; either version 2 of the License, or
* (at your option) any later version.
*
* This program is distributed in the hope that it will be useful,
* but WITHOUT ANY WARRANTY; without even the implied warranty of
* MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
* GNU General Public License for more details.
*
*
* You should have received a copy of the GNU General Public License
* along with this program; if not, write to the Free Software
* Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
*
*/
#include "eaton-pdu-marlin-mib.h"
#if WITH_SNMP_LKP_FUN
#include "eaton-pdu-marlin-helpers.h"
#endif
/* Eaton PDU-MIB - Marlin MIB
* ************************** */
#define EATON_MARLIN_MIB_VERSION "0.69"
#define EATON_MARLIN_SYSOID ".1.3.6.1.4.1.534.6.6.7"
#define EATON_MARLIN_OID_MODEL_NAME ".1.3.6.1.4.1.534.6.6.7.1.2.1.2.0"
static info_lkp_t marlin_outlet_status_info[] = {
{ 0, "off", NULL, NULL },
{ 1, "on", NULL, NULL },
{ 2, "pendingOff", NULL, NULL }, /* transitional status */
{ 3, "pendingOn", NULL, NULL }, /* transitional status */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_outletgroups_status_info[] = {
{ 0, "off", NULL, NULL },
{ 1, "on", NULL, NULL },
{ 2, "rebooting", NULL, NULL }, /* transitional status */
{ 3, "mixed", NULL, NULL }, /* transitional status, not sure what it means! */
{ 0, NULL, NULL, NULL }
};
/* Ugly hack for older G2 ePDU:
* having the matching OID present means that the outlet/unit is
* switchable. So, it should not require this value lookup */
static info_lkp_t g2_unit_outlet_switchability_info[] = {
{ -1, "yes", NULL, NULL },
{ 0, "yes", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_outlet_switchability_info[] = {
{ 1, "yes", NULL, NULL }, /* switchable */
{ 2, "no", NULL, NULL }, /* notSwitchable */
{ 0, NULL, NULL, NULL }
};
/* Overall outlets switchability info for the unit.
* This is refined per-outlet, depending on user configuration,
* possibly disabling switchability of some outlets */
static info_lkp_t marlin_unit_switchability_info[] = {
{ 0, "no", NULL, NULL }, /* unknown */
{ 1, "yes", NULL, NULL }, /* switched */
{ 2, "no", NULL, NULL }, /* advancedMonitored */
{ 3, "yes", NULL, NULL }, /* managed */
{ 4, "no", NULL, NULL }, /* monitored */
{ 0, NULL, NULL, NULL }
};
/* The physical type of outlet */
static info_lkp_t marlin_outlet_type_info[] = {
{ 0, "unknown", NULL, NULL },
{ 1, "iecC13", NULL, NULL },
{ 2, "iecC19", NULL, NULL },
{ 10, "uk", NULL, NULL },
{ 11, "french", NULL, NULL },
{ 12, "schuko", NULL, NULL },
{ 20, "nema515", NULL, NULL },
{ 21, "nema51520", NULL, NULL },
{ 22, "nema520", NULL, NULL },
{ 23, "nemaL520", NULL, NULL },
{ 24, "nemaL530", NULL, NULL },
{ 25, "nema615", NULL, NULL },
{ 26, "nema620", NULL, NULL },
{ 27, "nemaL620", NULL, NULL },
{ 28, "nemaL630", NULL, NULL },
{ 29, "nemaL715", NULL, NULL },
{ 30, "rf203p277", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_ambient_presence_info[] = {
{ -1, "unknown", NULL, NULL },
{ 0, "no", NULL, NULL }, /* disconnected */
{ 1, "yes", NULL, NULL }, /* connected */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_emp002_ambient_presence_info[] = {
{ 0, "unknown", NULL, NULL },
{ 2, "yes", NULL, NULL }, /* communicationOK */
{ 3, "no", NULL, NULL }, /* communicationLost */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_status_info[] = {
{ 0, "good", NULL, NULL }, /* No threshold triggered */
{ 1, "warning-low", NULL, NULL }, /* Warning low threshold triggered */
{ 2, "critical-low", NULL, NULL }, /* Critical low threshold triggered */
{ 3, "warning-high", NULL, NULL }, /* Warning high threshold triggered */
{ 4, "critical-high", NULL, NULL }, /* Critical high threshold triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_frequency_status_info[] = {
{ 0, "good", NULL, NULL }, /* No threshold triggered */
{ 1, "out-of-range", NULL, NULL }, /* Frequency out of range triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_ambient_drycontacts_info[] = {
{ -1, "unknown", NULL, NULL },
{ 0, "opened", NULL, NULL },
{ 1, "closed", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_voltage_alarms_info[] = {
{ 0, "", NULL, NULL }, /* No threshold triggered */
{ 1, "low voltage warning!", NULL, NULL }, /* Warning low threshold triggered */
{ 2, "low voltage critical!", NULL, NULL }, /* Critical low threshold triggered */
{ 3, "high voltage warning!", NULL, NULL }, /* Warning high threshold triggered */
{ 4, "high voltage critical!", NULL, NULL }, /* Critical high threshold triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_current_alarms_info[] = {
{ 0, "", NULL, NULL }, /* No threshold triggered */
{ 1, "low current warning!", NULL, NULL }, /* Warning low threshold triggered */
{ 2, "low current critical!", NULL, NULL }, /* Critical low threshold triggered */
{ 3, "high current warning!", NULL, NULL }, /* Warning high threshold triggered */
{ 4, "high current critical!", NULL, NULL }, /* Critical high threshold triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_frequency_alarm_info[] = {
{ 0, "", NULL, NULL }, /* No threshold triggered */
{ 1, "frequency out of range!", NULL, NULL }, /* Frequency out of range triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_temperature_alarms_info[] = {
{ 0, "", NULL, NULL }, /* No threshold triggered */
{ 1, "low temperature warning!", NULL, NULL }, /* Warning low threshold triggered */
{ 2, "low temperature critical!", NULL, NULL }, /* Critical low threshold triggered */
{ 3, "high temperature warning!", NULL, NULL }, /* Warning high threshold triggered */
{ 4, "high temperature critical!", NULL, NULL }, /* Critical high threshold triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_threshold_humidity_alarms_info[] = {
{ 0, "", NULL, NULL }, /* No threshold triggered */
{ 1, "low humidity warning!", NULL, NULL }, /* Warning low threshold triggered */
{ 2, "low humidity critical!", NULL, NULL }, /* Critical low threshold triggered */
{ 3, "high humidity warning!", NULL, NULL }, /* Warning high threshold triggered */
{ 4, "high humidity critical!", NULL, NULL }, /* Critical high threshold triggered */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_outlet_group_type_info[] = {
{ 0, "unknown", NULL, NULL },
{ 1, "breaker1pole", NULL, NULL },
{ 2, "breaker2pole", NULL, NULL },
{ 3, "breaker3pole", NULL, NULL },
{ 4, "outlet-section", NULL, NULL },
{ 5, "user-defined", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_input_type_info[] = {
{ 1, "1", NULL, NULL }, /* singlePhase */
{ 2, "2", NULL, NULL }, /* splitPhase */
{ 3, "3", NULL, NULL }, /* threePhaseDelta */
{ 4, "3", NULL, NULL }, /* threePhaseWye */
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_outlet_group_phase_info[] = {
{ 0, "unknown", NULL, NULL }, /* unknown */
{ 1, "1", NULL, NULL }, /* singlePhase */
{ 2, "1-N", NULL, NULL }, /* phase1toN */
{ 3, "2-N", NULL, NULL }, /* phase2toN */
{ 4, "3-N", NULL, NULL }, /* phase3toN */
{ 5, "1-2", NULL, NULL }, /* phase1to2 */
{ 6, "2-3", NULL, NULL }, /* phase2to3 */
{ 7, "3-1", NULL, NULL }, /* phase3to1 */
{ 0, NULL, NULL, NULL }
};
#if WITH_SNMP_LKP_FUN
/* Note: eaton_sensor_temperature_unit_fun() is defined in eaton-pdu-marlin-helpers.c
* and su_temperature_read_fun() is in snmp-ups.c
* Future work for DMF might provide same-named routines via LUA-C gateway.
*/
#if WITH_SNMP_LKP_FUN_DUMMY
/* Temperature unit consideration */
const char *eaton_sensor_temperature_unit_fun(void *raw_snmp_value) {
/* snmp_value here would be a (long*) */
NUT_UNUSED_VARIABLE(raw_snmp_value);
return "unknown";
}
/* FIXME: please DMF, though this should be in snmp-ups.c or equiv. */
const char *su_temperature_read_fun(void *raw_snmp_value) {
/* snmp_value here would be a (long*) */
NUT_UNUSED_VARIABLE(raw_snmp_value);
return "dummy";
}
#endif // WITH_SNMP_LKP_FUN_DUMMY
static info_lkp_t eaton_sensor_temperature_unit_info[] = {
{ 0, "dummy", eaton_sensor_temperature_unit_fun, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t eaton_sensor_temperature_read_info[] = {
{ 0, "dummy", su_temperature_read_fun, NULL },
{ 0, NULL, NULL, NULL }
};
#else // if not WITH_SNMP_LKP_FUN:
/* FIXME: For now, DMF codebase falls back to old implementation with static
* lookup/mapping tables for this, which can easily go into the DMF XML file.
*/
static info_lkp_t eaton_sensor_temperature_unit_info[] = {
{ 0, "kelvin", NULL, NULL },
{ 1, "celsius", NULL, NULL },
{ 2, "fahrenheit", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
#endif // WITH_SNMP_LKP_FUN
/* Extracted from powerware-mib.c ; try to commonalize */
static info_lkp_t marlin_ambient_drycontacts_polarity_info[] = {
{ 0, "normal-opened", NULL, NULL },
{ 1, "normal-closed", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
static info_lkp_t marlin_ambient_drycontacts_state_info[] = {
{ 0, "inactive", NULL, NULL },
{ 1, "active", NULL, NULL },
{ 0, NULL, NULL, NULL }
};
#if WITH_SNMP_LKP_FUN
/* Note: marlin_device_count_fun() is defined in eaton-pdu-marlin-helpers.c
* Future work for DMF might provide a same-named routine via LUA-C gateway.
*/
# if WITH_SNMP_LKP_FUN_DUMMY
long marlin_device_count_fun(const char *daisy_dev_list)
{ return 1; }
# endif /* WITH_SNMP_LKP_FUN_DUMMY */
static info_lkp_t marlin_device_count_info[] = {
{ 1, "dummy", NULL, marlin_device_count_fun },
{ 0, NULL, NULL, NULL }
};
#else /* if not WITH_SNMP_LKP_FUN: */
/* FIXME: For now, DMF codebase falls back to old implementation with static
* lookup/mapping tables for this, which can easily go into the DMF XML file.
*/
#endif /* WITH_SNMP_LKP_FUN */
/* Snmp2NUT lookup table for Eaton Marlin MIB */
static snmp_info_t eaton_marlin_mib[] = {
/* standard MIB items */
{ "device.description", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE,
".1.3.6.1.2.1.1.1.0",
NULL, SU_FLAG_OK, NULL },
{ "device.contact", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE,
".1.3.6.1.2.1.1.4.0",
NULL, SU_FLAG_OK, NULL },
{ "device.location", ST_FLAG_STRING | ST_FLAG_RW, SU_INFOSIZE,
".1.3.6.1.2.1.1.6.0",
NULL, SU_FLAG_OK, NULL },
/* Device collection */
{ "device.mfr", ST_FLAG_STRING, SU_INFOSIZE,
NULL,
"EATON", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "device.model", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.2.%i",
"Eaton Powerware ePDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "device.serial", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.4.%i",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "device.type", ST_FLAG_STRING, SU_INFOSIZE,
NULL,
"pdu", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "device.part", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.3.%i",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* For daisychain, there is only 1 physical interface! */
{ "device.macaddr", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.2.1.2.2.1.6.2",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* Daisychained devices support */
/* FIXME : Should this be a static value, or can we expect the amount of
* daisy-chained devices to change without restart of the driver by user?
* If this is a critical matter, should a detected change of amount of
* daisy-chained devices, outlet counts, etc. cause restart/reinit of
* this running driver instance?
*/
#if WITH_SNMP_LKP_FUN
/* Number of daisychained units is processed according to present units
* in the chain with new G3 firmware (02.00.0051, since autumn 2017):
* Take string "unitsPresent" (ex: "0,3,4,5"), and count the amount
* of "," separators+1 using an inline function */
/* FIXME: inline func */
{ "device.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.1.1.0",
"0", SU_FLAG_STATIC | SU_FLAG_UNIQUE,
&marlin_device_count_info[0] /* devices_count */ },
#endif
/* Notes: this older/fallback definition is used to:
* - estimate the number of devices, based on the below OID iteration capabilities
* - determine the base index of the SNMP OID (ie 0 or 1) */
{ "device.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.1.2.1.2.%i",
"1", SU_FLAG_STATIC
#if WITH_SNMP_LKP_FUN
| SU_FLAG_UNIQUE
#endif
, NULL /* devices_count */ },
/* UPS collection */
{ "ups.mfr", ST_FLAG_STRING, SU_INFOSIZE,
NULL,
"EATON", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "ups.model", ST_FLAG_STRING, SU_INFOSIZE,
"1.3.6.1.4.1.534.6.6.7.1.2.1.2.%i",
"Eaton Powerware ePDU", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* FIXME: use unitName.0 (ePDU)?
* { "ups.id", ST_FLAG_STRING, SU_INFOSIZE, AR_OID_DEVICE_NAME,
"unknown", SU_FLAG_STATIC | SU_FLAG_OK, NULL }, */
{ "ups.serial", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.4.%i",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
/* FIXME: this entry should be SU_FLAG_SEMI_STATIC */
{ "ups.firmware", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.5.%i",
"", SU_FLAG_OK, NULL },
{ "ups.type", ST_FLAG_STRING, SU_INFOSIZE,
NULL,
"pdu", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
/* FIXME: needs a date reformating callback
* 2011-8-29,16:27:25.0,+1:0
* Hex-STRING: 07 DB 08 1D 10 0C 36 00 2B 01 00 00
* { "ups.date", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.8.0",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
* { "ups.time", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.8.0",
"", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
*/
/* Input collection */
/* Note: a larger ePDU can have several inputs. The "%i" iterators
* in key names are currently available for daisychain devs, outlets,
* and groups - but not for inputs. These would likely evolve later
* to "input.%i.something" with default (non-%i) same as .1 instance.
* At this time only a single-input (or first of several inputs) is
* supported by this mapping.
*/
/* Historically, some of these data were previously published as
* outlet.{realpower,...}
* However, it's more suitable and logic to have these on input.{...}
*/
/* Note: the below gives the number of input, not the number of phase(s)! */
/* inputCount.0; Value (Integer): 1
{ "input.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.1.2.1.20.0",
NULL, SU_FLAG_STATIC, NULL }, */
/* Note: for daisychain mode, we must handle phase(s) per device,
* not as a whole. In case of daisychain, support of the UNIQUE
* field is not yet implemented (FIXME) so the last resolved OID
* value wins. If a more-preferable OID is not implemented by device,
* this is ok - the previous available value remains in place. */
/* inputType.%i.1 = INTEGER: singlePhase (1) */
{ "input.phases", 0, 1,
".1.3.6.1.4.1.534.6.6.7.3.1.1.2.%i.1",
NULL, SU_FLAG_STATIC,
&marlin_input_type_info[0] },
/* Frequency is measured globally */
{ "input.frequency", 0, 0.1,
".1.3.6.1.4.1.534.6.6.7.3.1.1.3.%i.1",
NULL, 0, NULL },
{ "input.frequency.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.1.1.4.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_frequency_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.1.1.4.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_frequency_alarm_info[0] },
/* inputCurrentPercentLoad (measured globally)
* Current percent load, based on the rated current capacity */
/* FIXME: input.load is mapped on input.L1.load for both single and 3phase !!! */
{ "input.load", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.3.1.11.%i.1.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L1.load", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.3.1.11.%i.1.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L2.load", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.3.1.11.%i.1.2",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L3.load", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.3.1.11.%i.1.3",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
/* FIXME:
* - Voltage is only measured per phase, as mV!
* so input.voltage == input.L1.voltage for both single and 3phase
* - As per NUT namespace (http://www.networkupstools.org/docs/developer-guide.chunked/apas01.html#_valid_contexts)
* Voltage has to be expressed either phase-phase or phase-neutral
* This is depending on OID inputVoltageMeasType
* INTEGER {singlePhase (1),phase1toN (2),phase2toN (3),phase3toN (4),phase1to2 (5),phase2to3 (6),phase3to1 (7)
* => RFC input.Lx.voltage.context */
{ "input.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.3.%i.1.1",
NULL, 0, NULL },
{ "input.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_voltage_alarms_info[0] },
{ "input.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.5.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.6.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.7.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.8.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.3.%i.1.1",
NULL, 0, NULL },
{ "input.L1.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L1.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_voltage_alarms_info[0] },
{ "input.L1.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.5.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.6.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.7.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.8.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.3.%i.1.2",
NULL, 0, NULL },
{ "input.L2.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.2",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L2.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.2",
NULL, SU_FLAG_OK,
&marlin_threshold_voltage_alarms_info[0] },
{ "input.L2.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.5.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.6.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.7.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.8.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.3.%i.1.3",
NULL, 0, NULL },
{ "input.L3.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.3",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L3.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.2.1.4.%i.1.3",
NULL, SU_FLAG_OK,
&marlin_threshold_voltage_alarms_info[0] },
{ "input.L3.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.5.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.6.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.7.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.8.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
/* FIXME:
* - input.current is mapped on input.L1.current for both single and 3phase !!! */
{ "input.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.4.%i.1.1",
NULL, 0, NULL },
{ "input.current.nominal", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.3.%i.1.1",
NULL, 0, NULL },
{ "input.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_current_alarms_info[0] },
{ "input.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.6.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.7.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.8.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.9.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.4.0.1.1",
NULL, 0, NULL },
{ "input.L1.current.nominal", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.3.%i.1.1",
NULL, 0, NULL },
{ "input.L1.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L1.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.1",
NULL, SU_FLAG_OK,
&marlin_threshold_current_alarms_info[0] },
{ "input.L1.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.6.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.7.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.8.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L1.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.9.%i.1.1",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.4.%i.1.2",
NULL, 0, NULL },
{ "input.L2.current.nominal", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.3.%i.1.2",
NULL, 0, NULL },
{ "input.L2.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.2",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L2.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.2",
NULL, SU_FLAG_OK,
&marlin_threshold_current_alarms_info[0] },
{ "input.L2.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.6.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.7.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.8.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L2.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.9.%i.1.2",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.4.%i.1.3",
NULL, 0, NULL },
{ "input.L3.current.nominal", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.3.%i.1.3",
NULL, 0, NULL },
{ "input.L3.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.3",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "L3.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.3.1.5.%i.1.3",
NULL, SU_FLAG_OK,
&marlin_threshold_current_alarms_info[0] },
{ "input.L3.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.6.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.7.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.8.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
{ "input.L3.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.3.1.9.%i.1.3",
NULL, SU_FLAG_NEGINVALID, NULL },
/* Sum of all phases realpower, valid for Shark 1ph/3ph only */
{ "input.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.5.1.4.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_UNIQUE | SU_FLAG_OK, NULL },
/* Fallback 1: Sum of all phases realpower, valid for Marlin 3ph only */
{ "input.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.4",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_UNIQUE | SU_FLAG_OK, NULL },
/* Fallback 2: Sum of the phase realpower, valid for Marlin 1ph only */
{ "input.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.2",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L1.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L2.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.2",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L3.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.3",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
/* Sum of all phases apparent power, valid for Shark 1ph/3ph only */
{ "input.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.5.1.3.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_UNIQUE | SU_FLAG_OK, NULL },
/* Fallback 1: Sum of all phases realpower, valid for Marlin 3ph only */
{ "input.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.4",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_UNIQUE | SU_FLAG_OK, NULL },
/* Fallback 2: Sum of the phase realpower, valid for Marlin 1ph only */
{ "input.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.2",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L1.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L2.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.2",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "input.L3.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.3",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
/* Input feed: a feed (A or B) is tied to an input, and this
* sub-collection describes the properties of an actual cable.
*/
/* FIXME: RFC on key name is needed when backporting to NUT upstream ; check type (number? string?) and flags */
/* { "input.feed.%i.id", 0, 1, "???.%i.%i", NULL, SU_FLAG_NEGINVALID, NULL }, */
/* Feed name(s) of the ePDU power input(s), can be set by user (FIXME: rename to .desc?)
* inputFeedName.0.1 = Value (OctetString): Feed A
*/
/* FIXME: SU_FLAG_SEMI_STATIC or SU_FLAG_SETTING => refreshed from time to time or upon call to setvar */
/* { "input.%i.feed.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
* ".1.3.6.1.4.1.534.6.6.7.3.1.1.10.%i.%i",
* NULL, SU_FLAG_SEMI_STATIC | SU_FLAG_OK | SU_TYPE_DAISY_1, NULL },
*/
{ "input.feed.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.3.1.1.10.%i.1",
NULL, SU_FLAG_SEMI_STATIC | SU_FLAG_OK | SU_TYPE_DAISY_1, NULL },
/* Feed color (integer RGB)
* inputFeedColor.0.1 = Gauge32: 0 (black)
*/
/* FIXME: RFC on key name is needed when backporting to NUT upstream */
/* { "input.%i.feed.color", 0, 1,
* ".1.3.6.1.4.1.534.6.6.7.3.1.1.9.%i.%i",
* NULL, SU_FLAG_STATIC | SU_FLAG_OK | SU_TYPE_DAISY_1, NULL },
*/
{ "input.feed.color", 0, 1,
".1.3.6.1.4.1.534.6.6.7.3.1.1.9.%i.1",
NULL, SU_FLAG_SEMI_STATIC | SU_FLAG_OK | SU_TYPE_DAISY_1, NULL },
/* inputPowerCapacity.0.1 = INTEGER: 2300 */
/* FIXME: RFC on key name is needed when backporting to NUT upstream */
{ "input.realpower.nominal", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.5.1.9.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
/* Ambient collection */
/* EMP001 (legacy) mapping */
/* Note: this is still published, beside from the new daisychained version! */
{ "ambient.present", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.1.1.3.%i.1",
NULL, SU_FLAG_OK,
&marlin_ambient_presence_info[0] },
{ "ambient.temperature.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.1.1.5.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.1.1.5.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_temperature_alarms_info[0] },
{ "ambient.temperature", 0, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.4.%i.1",
NULL, SU_FLAG_OK, NULL },
/* Low and high threshold use the respective critical levels */
{ "ambient.temperature.low", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.7.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.temperature.low.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.7.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.temperature.low.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.6.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.temperature.high", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.9.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.temperature.high.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.8.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.temperature.high.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.1.1.9.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.2.1.5.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.2.1.5.%i.1",
NULL, SU_FLAG_OK,
&marlin_threshold_humidity_alarms_info[0] },
{ "ambient.humidity", 0, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.4.%i.1",
NULL, SU_FLAG_OK, NULL },
/* Low and high threshold use the respective critical levels */
{ "ambient.humidity.low", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.7.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.low.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.6.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.low.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.7.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.high", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.9.%i.1", NULL,
SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.high.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.8.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
{ "ambient.humidity.high.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.6.7.7.2.1.9.%i.1",
NULL, SU_FLAG_NEGINVALID | SU_FLAG_OK, NULL },
/* Dry contacts on TH module */
{ "ambient.contacts.1.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.3.1.4.%i.1",
NULL, SU_FLAG_OK,
&marlin_ambient_drycontacts_info[0] },
{ "ambient.contacts.2.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.7.3.1.4.%i.2",
NULL, SU_FLAG_OK,
&marlin_ambient_drycontacts_info[0] },
/* EMP002 (EATON EMP MIB) mapping, including daisychain support */
/* Warning: indexes start at '1' not '0'! */
/* sensorCount.0 */
{ "ambient.count", ST_FLAG_RW, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.1.0",
"0", SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* CommunicationStatus.n */
{ "ambient.%i.present", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.1.4.1.1.%i",
NULL, SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_emp002_ambient_presence_info[0] },
/* sensorName.n: OctetString EMPDT1H1C2 @1 */
{ "ambient.%i.name", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.3.1.1.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorManufacturer.n */
{ "ambient.%i.mfr", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.6.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorModel.n */
{ "ambient.%i.model", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.7.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorSerialNumber.n */
{ "ambient.%i.serial", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.9.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorUuid.n */
{ "ambient.%i.id", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.2.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorAddress.n */
{ "ambient.%i.address", 0, 1,
".1.3.6.1.4.1.534.6.8.1.1.2.1.4.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorMonitoredBy.n */
{ "ambient.%i.parent.serial", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.5.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* sensorFirmwareVersion.n */
{ "ambient.%i.firmware", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.1.2.1.10.%i",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* temperatureUnit.1
* MUST be before the temperature data reading! */
{ "ambient.%i.temperature.unit", 0, 1.0,
".1.3.6.1.4.1.534.6.8.1.2.5.0",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&eaton_sensor_temperature_unit_info[0] },
/* temperatureValue.n.1 */
{ "ambient.%i.temperature", 0, 0.1,
".1.3.6.1.4.1.534.6.8.1.2.3.1.3.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
#if WITH_SNMP_LKP_FUN
&eaton_sensor_temperature_read_info[0]
#else
NULL
#endif
},
{ "ambient.%i.temperature.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.2.3.1.1.%i.1",
NULL, SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.2.3.1.1.%i.1",
NULL, SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_threshold_temperature_alarms_info[0] },
/* FIXME: ambient.n.temperature.{minimum,maximum} */
/* temperatureThresholdLowCritical.n.1 */
{ "ambient.%i.temperature.low.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.2.2.1.6.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* temperatureThresholdLowWarning.n.1 */
{ "ambient.%i.temperature.low.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.2.2.1.5.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* temperatureThresholdHighWarning.n.1 */
{ "ambient.%i.temperature.high.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.2.2.1.7.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* temperatureThresholdHighCritical.n.1 */
{ "ambient.%i.temperature.high.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.2.2.1.8.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* humidityValue.n.1 */
{ "ambient.%i.humidity", 0, 0.1,
".1.3.6.1.4.1.534.6.8.1.3.3.1.3.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
{ "ambient.%i.humidity.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.3.3.1.1.%i.1",
NULL, SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_threshold_status_info[0] },
{ "ups.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.3.3.1.1.%i.1",
NULL, SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_threshold_humidity_alarms_info[0] },
/* FIXME: consider ambient.n.humidity.{minimum,maximum} */
/* humidityThresholdLowCritical.n.1 */
{ "ambient.%i.humidity.low.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.3.2.1.6.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* humidityThresholdLowWarning.n.1 */
{ "ambient.%i.humidity.low.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.3.2.1.5.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* humidityThresholdHighWarning.n.1 */
{ "ambient.%i.humidity.high.warning", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.3.2.1.7.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* humidityThresholdHighCritical.n.1 */
{ "ambient.%i.humidity.high.critical", ST_FLAG_RW, 0.1,
".1.3.6.1.4.1.534.6.8.1.3.2.1.8.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* digitalInputName.n.{1,2} */
{ "ambient.%i.contacts.1.name", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.4.2.1.1.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
{ "ambient.%i.contacts.2.name", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.4.2.1.1.%i.2",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY, NULL },
/* digitalInputPolarity.n */
{ "ambient.%i.contacts.1.config", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.4.2.1.3.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_ambient_drycontacts_polarity_info[0] },
{ "ambient.%i.contacts.2.config", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.8.1.4.2.1.3.%i.2",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_ambient_drycontacts_polarity_info[0] },
/* XUPS-MIB::xupsContactState.n */
{ "ambient.%i.contacts.1.status", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.4.3.1.3.%i.1",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_ambient_drycontacts_state_info[0] },
{ "ambient.%i.contacts.2.status", ST_FLAG_STRING, 1.0,
".1.3.6.1.4.1.534.6.8.1.4.3.1.3.%i.2",
"", SU_AMBIENT_TEMPLATE | SU_TYPE_DAISY_MASTER_ONLY,
&marlin_ambient_drycontacts_state_info[0] },
/* Outlet collection */
{ "outlet.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.1.2.1.22.%i",
"0", SU_FLAG_STATIC | SU_FLAG_OK, NULL },
{ "outlet.id", 0, 1,
NULL,
"0", SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
{ "outlet.desc", ST_FLAG_RW | ST_FLAG_STRING, 20,
NULL,
"All outlets",
SU_FLAG_STATIC | SU_FLAG_ABSENT | SU_FLAG_OK, NULL },
/* UnitType
* used to depict the overall outlets switchability of the unit on G3 and newer ePDU*/
{ "outlet.switchable", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.1.2.1.10.%i",
"no", SU_FLAG_STATIC | SU_FLAG_UNIQUE,
&marlin_unit_switchability_info[0] },
/* Ugly hack for older G2 ePDU: check the first outlet to determine unit switchability */
{ "outlet.switchable", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.6.1.3.%i.1",
"no", SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_FLAG_OK | SU_TYPE_DAISY_1,
&g2_unit_outlet_switchability_info[0] },
/* The below ones are the same as the input.* equivalent */
/* FIXME: transition period, TO BE REMOVED, moved to input.* */
{ "outlet.frequency", 0, 0.1,
".1.3.6.1.4.1.534.6.6.7.3.1.1.3.%i.1",
NULL, 0, NULL },
{ "outlet.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.3.2.1.3.%i.1.1",
NULL, 0, NULL },
{ "outlet.current", 0, 0.01,
".1.3.6.1.4.1.534.6.6.7.3.3.1.4.%i.1.1",
NULL, 0, NULL },
{ "outlet.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.4.%i.1.4",
NULL, 0, NULL },
{ "outlet.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.3.4.1.3.%i.1.4",
NULL, 0, NULL },
/* outlet template definition
* Indexes start from 1, ie outlet.1 => <OID>.1 */
/* Note: the first definition is used to determine the base index (ie 0 or 1) */
/* Outlet friendly name, which can be modified by the user
* outletName: = OctetString: "Outlet A16"
*/
/* FIXME: SU_FLAG_SEMI_STATIC or SU_FLAG_SETTING =>
* refreshed from time to time or upon call to setvar */
{ "outlet.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.1.1.3.%i.%i",
NULL, SU_FLAG_SEMI_STATIC | SU_FLAG_OK | SU_OUTLET | SU_TYPE_DAISY_1,
NULL },
{ "outlet.%i.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.6.1.2.%i.%i",
NULL, SU_FLAG_OK | SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_outlet_status_info[0] },
/* Numeric identifier of the outlet, tied to the whole unit */
/* NOTE: For daisychain devices ATM the last listed value presented by
* the SNMP device is kept by the driver - no SU_FLAG_UNIQUE here yet.
* Verified that a non-implemented OID does not publish empty values. */
/* Fallback in firmwares issued before Sep 2017 is to use the
* outletID: Outlet physical name, related to its number in the group
* ex: first outlet of the second group (B) is B1, or can default to
* the outlet number (represented as string) and is a read-only string
* outletID.0.8 = Value (OctetString): "8"
*/
{ "outlet.%i.id", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.7.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET | SU_TYPE_DAISY_1,
NULL },
/* Fallback in firmwares issued before Sep 2017 (outletID): */
{ "outlet.%i.name", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.1.1.2.%i.%i",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_FLAG_OK | SU_OUTLET | SU_TYPE_DAISY_1,
NULL },
/* Preferred: Outlet physical name OID in new G3 firmware (02.00.0051)
* is named outletDesignator (other MIBs outletPhysicalName)
* and is a read-only string provided by firmware
* outletDesignator.0.1 = Value (OctetString): "A1"
* outletPhysicalName.0.16 = Value (OctetString): "A16"
*/
{ "outlet.%i.name", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.1.1.6.%i.%i",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_FLAG_OK | SU_OUTLET | SU_TYPE_DAISY_1,
NULL },
/* FIXME: the last part of the OID gives the group number (i.e. %i.1 means "group 1")
* Need to address that, without multiple declaration (%i.%i, SU_OUTLET | SU_OUTLET_GROUP)? */
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.1",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.2",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.3",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.4",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.5",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.groupid", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.2.1.3.%i.%i.6",
NULL, SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.4.1.3.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.4.1.4.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_threshold_status_info[0] },
{ "outlet.%i.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.4.1.4.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_threshold_current_alarms_info[0] },
{ "outlet.%i.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.4.1.5.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.4.1.6.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.4.1.7.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.4.1.8.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.6.5.1.3.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.3.1.2.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.3.1.3.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_threshold_status_info[0] },
{ "outlet.%i.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.3.1.3.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_threshold_voltage_alarms_info[0] },
{ "outlet.%i.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.3.1.4.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.3.1.5.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.3.1.6.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.6.3.1.7.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.6.5.1.2.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
/* outletControlSwitchable */
{ "outlet.%i.switchable", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.6.1.9.%i.%i",
"no", SU_OUTLET | SU_FLAG_UNIQUE | SU_TYPE_DAISY_1,
&marlin_outlet_switchability_info[0] },
/* FIXME: handle non switchable units (only measurements), which do not expose this OID */
{ "outlet.%i.switchable", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.6.1.3.%i.%i",
"no", SU_FLAG_STATIC | SU_FLAG_UNIQUE | SU_OUTLET | SU_FLAG_OK | SU_TYPE_DAISY_1,
&g2_unit_outlet_switchability_info[0] },
{ "outlet.%i.type", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.6.1.1.5.%i.%i",
"unknown", SU_FLAG_STATIC | SU_OUTLET | SU_TYPE_DAISY_1,
&marlin_outlet_type_info[0] },
/* TODO: handle statistics
* outletWh.0.1
* outletWhTimer.0.1
*/
/* Outlet groups collection */
{ "outlet.group.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.1.2.1.21.%i",
"0", SU_FLAG_STATIC | SU_TYPE_DAISY_1, NULL },
/* outlet groups template definition
* Indexes start from 1, ie outlet.group.1 => <OID>.1 */
/* Note: the first definition is used to determine the base index (ie 0 or 1) */
/* groupID.0.1 = OctetString: A */
{ "outlet.group.%i.id", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.1.1.2.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* User-friendly (writeable) description of the outlet group:
* groupName.0.1 = OctetString: Factory Group 1
* groupName.0.2 = OctetString: Branch Circuit B
*/
/* FIXME: SU_FLAG_SEMI_STATIC or SU_FLAG_SETTING =>
* refreshed from time to time or upon call to setvar */
{ "outlet.group.%i.desc", ST_FLAG_RW | ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.1.1.3.%i.%i",
NULL, SU_FLAG_SEMI_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
NULL },
/* Outlet-group physical name, a read-only string,
* is named groupDesignator (other MIBs groupPhysicalName)
* groupPhysicalName.0.1 = Value (OctetString): A
* groupDesignator.0.2 = Value (OctetString): B
*/
{ "outlet.group.%i.name", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.1.1.8.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
NULL },
/* Outlet-group color: groupColor (other MIBs groupBkgColor)
* groupColor.0.1 = Value (Gauge32): 16051527 (0xF4ED47)
*/
/* FIXME: RFC on key name is needed when backporting to NUT upstream */
{ "outlet.group.%i.color", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.1.1.7.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
NULL },
/* groupType.0.1 = Integer: outletSection (4) */
{ "outlet.group.%i.type", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.1.1.4.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_outlet_group_type_info[0] },
/* Phase to which an outlet-group is connected:
* We use the following OID, which gives the voltage measurement type
* groupVoltageMeasType.0.1; Value (Integer): singlePhase (1)
*/
/* FIXME: RFC on key name is needed when backporting to NUT upstream ; check type (number? string?) and flags (daisy?) */
{ "outlet.group.%i.phase", 0, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.3.1.2.%i.%i",
NULL, SU_FLAG_STATIC | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_outlet_group_phase_info[0] },
/* groupControlStatus.0.1 = Integer: on (1) */
{ "outlet.group.%i.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.6.1.2.%i.%i",
NULL, SU_FLAG_OK | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_outletgroups_status_info[0] },
/* groupChildCount.0.1 = Integer: 12 */
{ "outlet.group.%i.count", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.1.1.6.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupVoltage.0.1 = Integer: 243080 */
{ "outlet.group.%i.voltage", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.3.1.3.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupVoltageThStatus.0.1 = Integer: good (0) */
{ "outlet.group.%i.voltage.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.3.1.4.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_threshold_status_info[0] },
{ "outlet.group.%i.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.3.1.4.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_threshold_voltage_alarms_info[0] },
{ "outlet.group.%i.voltage.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.3.1.5.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
{ "outlet.group.%i.voltage.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.3.1.6.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
{ "outlet.group.%i.voltage.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.3.1.7.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
{ "outlet.group.%i.voltage.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.3.1.8.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrent.0.1 = Integer: 0 */
{ "outlet.group.%i.current", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.3.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentCapacity.0.1 = Integer: 16000 */
{ "outlet.group.%i.current.nominal", 0, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.2.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentThStatus.0.1 = Integer: good (0) */
{ "outlet.group.%i.current.status", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.4.1.4.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_threshold_status_info[0] },
{ "outlet.group.%i.alarm", ST_FLAG_STRING, SU_INFOSIZE,
".1.3.6.1.4.1.534.6.6.7.5.4.1.4.%i.%i",
NULL, SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
&marlin_threshold_current_alarms_info[0] },
/* groupCurrentPercentLoad.0.1 = Integer: 0 */
{ "outlet.group.%i.load", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.5.4.1.10.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentThLowerWarning.0.1 = Integer: 0 */
{ "outlet.group.%i.current.low.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.5.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentThLowerCritical.0.1 = Integer: -1 */
{ "outlet.group.%i.current.low.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.6.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentThUpperWarning.0.1 = Integer: 12800 */
{ "outlet.group.%i.current.high.warning", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.7.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupCurrentThUpperCritical.0.1 = Integer: 16000 */
{ "outlet.group.%i.current.high.critical", ST_FLAG_RW, 0.001,
".1.3.6.1.4.1.534.6.6.7.5.4.1.8.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupWatts.0.1 = Integer: 2670 */
{ "outlet.group.%i.realpower", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.5.5.1.3.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupVA.0.1 = Integer: 3132 */
{ "outlet.group.%i.power", 0, 1.0,
".1.3.6.1.4.1.534.6.6.7.5.5.1.2.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
NULL },
/* Input to which an outlet-group is connected
* groupInputIndex.0.1 = Integer: 1
*/
/* FIXME: RFC on key name is needed when backporting to NUT upstream */
{ "outlet.group.%i.input", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.1.1.9.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET_GROUP | SU_TYPE_DAISY_1,
NULL },
/* instant commands. */
/* Notes:
* - load.cycle might be replaced by / mapped on shutdown.reboot
* - outletControl{Off,On,Reboot}Cmd values:
* 0-n : Timer
* -1 : Cancel
* we currently use "0", so instant On | Off | Reboot... */
/* no counterpart found!
{ "outlet.load.off", 0, DO_OFF, AR_OID_OUTLET_STATUS ".0",
NULL, SU_TYPE_CMD, NULL },
{ "outlet.load.on", 0, DO_ON, AR_OID_OUTLET_STATUS ".0",
NULL, SU_TYPE_CMD, NULL },
{ "outlet.load.cycle", 0, DO_CYCLE, AR_OID_OUTLET_STATUS ".0",
NULL, SU_TYPE_CMD, NULL }, */
/* Delays handling:
* 0-n :Time in seconds until the group command is issued
* -1:Cancel a pending group-level Off/On/Reboot command */
{ "outlet.%i.load.off", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.3.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.load.on", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.4.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.load.cycle", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.5.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
/* Per-outlet shutdown / startup delay (configuration point, not the timers)
* outletControlShutoffDelay.0.3 = INTEGER: 120
* outletControlSequenceDelay.0.8 = INTEGER: 8
* (by default each output socket startup is delayed by its number in seconds)
*/
{ "outlet.%i.delay.shutdown", ST_FLAG_RW, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.10.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.delay.start", ST_FLAG_RW, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.7.%i.%i",
NULL, SU_FLAG_NEGINVALID | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
/* Delayed version, parameter is mandatory (so dfl is NULL)! */
{ "outlet.%i.load.off.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.3.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.load.on.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.4.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.load.cycle.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.5.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET | SU_TYPE_DAISY_1, NULL },
/* Per-outlet shutdown / startup timers
* outletControlOffCmd.0.1 = INTEGER: -1
* outletControlOnCmd.0.1 = INTEGER: -1
*/
{ "outlet.%i.timer.shutdown", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.3.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
{ "outlet.%i.timer.start", 0, 1,
".1.3.6.1.4.1.534.6.6.7.6.6.1.4.%i.%i",
NULL, SU_OUTLET | SU_TYPE_DAISY_1, NULL },
/* Delays handling:
* 0-n :Time in seconds until the group command is issued
* -1:Cancel a pending group-level Off/On/Reboot command */
/* groupControlOffCmd.0.1 = Integer: -1 */
{ "outlet.group.%i.load.off", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.3.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupControl0nCmd.0.1 = Integer: -1 */
{ "outlet.group.%i.load.on", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.4.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupControlRebootCmd.0.1 = Integer: -1 */
{ "outlet.group.%i.load.cycle", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.5.%i.%i",
"0", SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* Delayed version, parameter is mandatory (so dfl is NULL)! */
{ "outlet.group.%i.load.off.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.3.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupControl0nCmd.0.1 = Integer: -1 */
{ "outlet.group.%i.load.on.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.4.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* groupControlRebootCmd.0.1 = Integer: -1 */
{ "outlet.group.%i.load.cycle.delay", 0, 1,
".1.3.6.1.4.1.534.6.6.7.5.6.1.5.%i.%i",
NULL, SU_TYPE_CMD | SU_OUTLET_GROUP | SU_TYPE_DAISY_1, NULL },
/* end of structure. */
{ NULL, 0, 0, NULL, NULL, 0, NULL }
};
mib2nut_info_t eaton_marlin = { "eaton_epdu", EATON_MARLIN_MIB_VERSION, NULL, EATON_MARLIN_OID_MODEL_NAME, eaton_marlin_mib, EATON_MARLIN_SYSOID, NULL };