NAME
----
mge-utalk - Driver for MGE UPS SYSTEMS UTalk protocol equipment
SYNOPSIS
--------
*mge-utalk* -h
*mge-utalk* -a 'UPS_NAME' ['OPTIONS']
NOTE: This man page only documents the hardware-specific features of the
2022-06-29 10:37:36 +00:00
mge-utalk driver. For information about the core driver, see
2011-01-26 09:35:08 +00:00
linkman:nutupsdrv[8].
SUPPORTED HARDWARE
------------------
mge-utalk supports the following legacy units, using the MGE UTalk protocol:
2022-06-29 10:37:36 +00:00
* Pulsar ESV+
* Pulsar ES+
* Pulsar EL
* Pulsar EX
* Pulsar EXtreme
* Comet EXtreme
* Comet (Utalk Serial Card, ref 66060)
* Galaxy (Utalk Serial Card, ref 66060)
2011-01-26 09:35:08 +00:00
This driver also support some newer models with backward UTalk compatibility,
such as Pulsar Evolution and Pulsar EXtreme C. As these models also support
the SHUT protocol, prefer mge-shut for serial communication, or use the USB
port, if available, with the usbhid-ups driver.
EXTRA ARGUMENTS
---------------
This driver supports the following optional settings in the linkman:ups.conf[5]:
*lowbatt*='num'::
Set the low battery warning threshold at which shutdown is initiated by
linkman:upsmon[8].
+
The factory default value is 30 (in percent), and can be settable depending on
the exact model.
*offdelay*='num'::
Set the timer before the UPS is turned off after the kill power command is
sent (via the *-k* switch).
+
The default value is 20 (in seconds).
*ondelay*='num'::
Set the delay before the UPS is turned on, after the power returns.
+
The default value is 1 (in minutes).
*oldmac*::
Set this flag if you are running Linux on an Oldworld Macintosh box
(all beige Apple Macintosh). This might also be needed for other
OSs (like *BSD) running on PowerMac.
KNOWN ISSUES
------------
Repetitive timeout and staleness
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Older models, such as ES/ESV ones, might report repetitive "data stale" errors.
This is due to the fact that these models don't support too much polling.
To solve this problem, add "pollinterval=20" in ups.conf, and change the value
of MAXAGE to 25 in upsd.conf, and DEADTIME to 25 in upsmon.conf.
2022-06-29 10:37:36 +00:00
AUTHORS
-------
2011-01-26 09:35:08 +00:00
2022-06-29 10:37:36 +00:00
* Hans Ekkehard Plesser
* Arnaud Quette
* Martin Loyer
* Patrick Agrain
* Nicholas Reilly
* Dave Abbott
* Marek Kralewski
2011-01-26 09:35:08 +00:00
SEE ALSO
--------
The core driver
~~~~~~~~~~~~~~~~
2022-06-29 10:37:36 +00:00
2011-01-26 09:35:08 +00:00
linkman:nutupsdrv[8]
Internet resources
~~~~~~~~~~~~~~~~~~
2022-06-29 10:37:36 +00:00
2011-01-26 09:35:08 +00:00
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/