richcomm_usb \- Driver UPS equipment using Richcomm dry\-contact to USB solution
.SH"NOTE"
.sp
This man page only documents the specific features of the richcomm_usb driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.SH"SUPPORTED HARDWARE"
.sp
The Richcomm dry\-contact to USB solution is a generic interface that is used to upgrade an existing (RS\-232) contact closure UPS interface to USB\&. As such, all the limitations of the underlying contact closure interface apply\&. This means that you will only get the essentials in ups\&.status: OL, OB, and LB\&. See also \fBgenericups\fR(8)\&.
.SH"BUGS"
.sp
Most contact\-closure UPSes will not power down the load if the line power is present\&. This can create a race when using slave \fBupsmon\fR(8) systems\&. See the \fBupsmon\fR(8) man page for more information\&.
.sp
The solution to both of these problems is to upgrade to a smart protocol UPS of some kind that allows detection and proper load cycling on command\&.
.SH"AUTHORS"
.sp
Peter van Valderen <p\&.v\&.valderen at probu\&.nl>, Dirk Teurlings <dirk at upexia\&.nl>
.SH"SEE ALSO"
.SS"The core driver:"
.sp
\fBnutupsdrv\fR(8)
.SS"The generic serial driver:"
.sp
\fBgenericups\fR(8)
.SS"Internet resources:"
.sp
The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/