.TH "SNMP\-UPS" "8" "02/25/2014" "Network UPS Tools 2\&.7\&.1\&." "NUT Manual"
2011-01-26 09:35:08 +00:00
.\" -----------------------------------------------------------------
.\" * Define some portability stuff
.\" -----------------------------------------------------------------
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.\" http://bugs.debian.org/507673
.\" http://lists.gnu.org/archive/html/groff/2009-02/msg00013.html
.\" ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
.ie \n(.g .ds Aq \(aq
.el .ds Aq '
.\" -----------------------------------------------------------------
.\" * set default formatting
.\" -----------------------------------------------------------------
.\" disable hyphenation
.nh
.\" disable justification (adjust text to left margin only)
.ad l
.\" -----------------------------------------------------------------
.\" * MAIN CONTENT STARTS HERE *
.\" -----------------------------------------------------------------
.SH "NAME"
snmp-ups \- Multi\-MIB Driver for SNMP UPS equipment
.SH "NOTE"
.sp
This man page only documents the hardware\-specific features of the snmp\-ups driver\&. For information about the core driver, see \fBnutupsdrv\fR(8)\&.
.SH "SUPPORTED HARDWARE"
.sp
2014-04-22 18:39:47 +00:00
The snmp\-ups driver automatically detects and supports a wide range of devices by loading various MIBS:
.PP
\fBietf\fR
.RS 4
UPS that is RFC 1628 (UPS MIB) compliant, e\&.g\&. MGE UPS SYSTEMS, Liebert, perhaps others (default)
.RE
2011-01-26 09:35:08 +00:00
.PP
\fBmge\fR
.RS 4
MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards (ref 66062, 66045, 66074 and 66244)
.RE
.PP
\fBapcc\fR
.RS 4
2012-06-01 13:55:19 +00:00
APC AP9605, AP9606, AP9617, and AP9618 APC network management cards, as well as any others supporting the APC POWERNET MIB
2011-01-26 09:35:08 +00:00
.RE
.PP
\fBnetvision\fR
.RS 4
Socomec Sicon UPS with Netvision Web/SNMP management card/external box
.RE
.PP
\fBpw\fR
.RS 4
Powerware devices with ConnectUPS SNMP cards
.RE
.PP
\fBaphel_genesisII\fR
.RS 4
Eaton Powerware ePDU Monitored
.RE
.PP
\fBaphel_revelation\fR
.RS 4
Eaton Powerware ePDU Managed
.RE
.PP
\fBraritan\fR
.RS 4
Various Raritan PDUs
.RE
.PP
\fBbaytech\fR
.RS 4
Various BayTech PDUs
.RE
.PP
\fBcpqpower\fR
.RS 4
HP/Compaq AF401A management card, perhaps others
.RE
2012-01-24 10:22:33 +00:00
.PP
\fBcyberpower\fR
.RS 4
Cyberpower RMCARD201\&. Should also support RMCARD100 (net version), RMCARD202 and RMCARD301
.RE
2011-01-26 09:35:08 +00:00
.SH "EXTRA ARGUMENTS"
.sp
This driver supports the following optional settings in the \fBups.conf\fR(5):
.PP
\fBmibs\fR=\fIname\fR
.RS 4
2014-04-22 18:39:47 +00:00
Set MIB compliance (default=auto, allowed entries: refer to SUPPORTED HARDWARE above)\&. With "auto", the driver will try a select set of SNMP objects until it finds one that the device responds to\&. Note that since NUT 2\&.6\&.2, snmp\-ups has a new method that uses sysObjectID (which is a pointer to the prefered MIB of the device) to detect supported devices\&. This renders void the use of "mibs" option\&.
2011-01-26 09:35:08 +00:00
.RE
.PP
\fBcommunity\fR=\fIname\fR
.RS 4
2014-04-22 18:39:47 +00:00
Set community name (default = public)\&. Note that a RW community name is required to change UPS settings (as for a powerdown)\&.
2011-01-26 09:35:08 +00:00
.RE
.PP
\fBsnmp_version\fR=\fIversion\fR
.RS 4
2013-11-24 15:00:12 +00:00
Set SNMP version (default = v1, allowed: v2c, v3)
2011-01-26 09:35:08 +00:00
.RE
.PP
\fBpollfreq\fR=\fIvalue\fR
.RS 4
Set polling frequency in seconds, to reduce network flow (default=30)
.RE
.PP
\fBnotransferoids\fR
.RS 4
Disable the monitoring of the low and high voltage transfer OIDs in the hardware\&. This will remove input\&.transfer\&.low and input\&.transfer\&.high from the list of variables\&. This should only be used on APCC Symmetra equipment which has strangeness in the three\-phase power reporting\&.
.RE
.PP
\fBsecLevel\fR=\fIvalue\fR
.RS 4
Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv, allowed: authNoPriv,authPriv)
.RE
.PP
\fBsecName\fR=\fIvalue\fR
.RS 4
Set the securityName used for authenticated SNMPv3 messages (no default)
.RE
.PP
\fBauthPassword\fR=\fIvalue\fR
.RS 4
Set the authentication pass phrase used for authenticated SNMPv3 messages (no default)
.RE
.PP
\fBprivPassword\fR=\fIvalue\fR
.RS 4
Set the privacy pass phrase used for encrypted SNMPv3 messages (no default)
.RE
.PP
\fBauthProtocol\fR=\fIvalue\fR
.RS 4
Set the authentication protocol (MD5 or SHA) used for authenticated SNMPv3 messages (default=MD5)
.RE
.PP
\fBprivProtocol\fR=\fIvalue\fR
.RS 4
Set the privacy protocol (DES or AES) used for encrypted SNMPv3 messages (default=DES)
.RE
.SH "REQUIREMENTS"
.sp
You will need to install the Net\-SNMP package from http://www\&.net\-snmp\&.org/ before building this driver\&.
.sp
SNMP v3 also requires OpenSSL support from http://www\&.openssl\&.org\&.
2014-04-22 18:39:47 +00:00
.SH "LIMITATIONS"
2011-01-26 09:35:08 +00:00
.SS "Shutdown"
.sp
2014-04-22 18:39:47 +00:00
The shutdown sequence should be tested before relying on NUT to send a shutdown command to the UPS\&. The problem is that the host network stack may have been torn down by the time the driver is invoked to send the shutdown command\&. The driver attempts to send shutdown\&.return, shutdown\&.reboot, and load\&.off\&.delay commands to the UPS in sequence, stopping after the first supported command\&.
2011-01-26 09:35:08 +00:00
.SH "INSTALLATION"
.sp
2014-04-22 18:39:47 +00:00
This driver is only built if the Net\-SNMP development files are present at configuration time\&. You can also force it to be built by using configure \-\-with\-snmp=yes before calling make\&.
.SH "EXAMPLES"
2011-01-26 09:35:08 +00:00
.sp
2014-04-22 18:39:47 +00:00
The hostname of the UPS is specified with the "port" value in ups\&.conf:
2011-01-26 09:35:08 +00:00
.sp
.if n \{\
.RS 4
.\}
.nf
[snmpv1]
driver = snmp\-ups
port = snmp\-ups\&.example\&.com
community = public
snmp_version = v1
pollfreq = 15
desc = "Example SNMP v1 device"
.fi
.if n \{\
.RE
.\}
.sp
.if n \{\
.RS 4
.\}
.nf
[snmpv3]
driver = snmp\-ups
port = 166\&.99\&.224\&.132
2013-11-24 15:00:12 +00:00
snmp_version = v3
2011-01-26 09:35:08 +00:00
secLevel = authPriv
secName = mysecurityname
authPassword = myauthenticationpassphrase
privPassword = myprivatepassphrase
desc = "Example SNMP v3 device, with the highest security level"
.fi
.if n \{\
.RE
.\}
.SH "AUTHORS"
.sp
Arnaud Quette, Dmitry Frolov
.SH "SEE ALSO"
.SS "The core driver:"
.sp
\fBnutupsdrv\fR(8)
.SS "NUT SNMP Protocols Library"
.sp
Available at: http://www\&.networkupstools\&.org/protocols/snmp/
.SS "Internet resources:"
.sp
The NUT (Network UPS Tools) home page: http://www\&.networkupstools\&.org/