/* etapro.c - model specific routines for ETA UPS
|
||
|
|
||
|
Copyright (C) 2002 Marek Michalkiewicz <marekm@amelek.gda.pl>
|
||
|
|
||
|
This program is free software; you can redistribute it and/or modify
|
||
|
it under the terms of the GNU General Public License as published by
|
||
|
the Free Software Foundation; either version 2 of the License, or
|
||
|
(at your option) any later version.
|
||
|
|
||
|
This program is distributed in the hope that it will be useful,
|
||
|
but WITHOUT ANY WARRANTY; without even the implied warranty of
|
||
|
MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE. See the
|
||
|
GNU General Public License for more details.
|
||
|
|
||
|
You should have received a copy of the GNU General Public License
|
||
|
along with this program; if not, write to the Free Software
|
||
|
Foundation, Inc., 59 Temple Place, Suite 330, Boston, MA 02111-1307 USA
|
||
|
*/
|
||
|
|
||
|
/*
|
||
|
This driver is for the ETA UPS (http://www.eta.com.pl/) with the
|
||
|
"PRO" option (available at small added cost, highly recommended).
|
||
|
All units (even without that option) should also work in "dumb"
|
||
|
mode with the genericups driver (type 7 or 10), but in that mode
|
||
|
shutdown only works when running on battery.
|
||
|
|
||
|
Tested with ETA mini+UPS 720 PRO. Thanks to ETA for help with
|
||
|
protocol documentation, no free UPS though (but they still can
|
||
|
send me another one if they like me ;-).
|
||
|
|
||
|
Shutdown should work even when on line, so this should help avoid
|
||
|
power races (system remaining in halted or "ATX standby" state,
|
||
|
requiring manual intervention). Delay from power off to power on
|
||
|
can be set in software, currently hardcoded to 15 seconds.
|
||
|
|
||
|
Instant commands CMD_OFF and CMD_ON should work (not tested yet).
|
||
|
Be careful with CMD_OFF - it turns off the load after one second.
|
||
|
|
||
|
Known issues:
|
||
|
- larger units (>= 1000VA) have a 24V battery, so the battery
|
||
|
voltage reported should be multiplied by 2 if the model
|
||
|
string indicates such a larger unit.
|
||
|
- load percentage is only measured when running on battery, and
|
||
|
is reported as 0 when on line. This seems to be a hardware
|
||
|
limitation of the UPS, so we can't do much about it...
|
||
|
- UPS does not provide any remaining battery charge (or time at
|
||
|
current load) information, but we should be able to estimate it
|
||
|
based on battery voltage, load percentage and UPS model.
|
||
|
- error handling not tested (we assume that the UPS is always
|
||
|
correctly connected to the serial port).
|
||
|
*/
|
||
|
|
||
|
#include "main.h"
|
||
|
#include "serial.h"
|
||
|
|
||
|
#define DRIVER_NAME "ETA PRO driver"
|
||
|
#define DRIVER_VERSION "0.04"
|
||
|
|
||
|
/* driver description structure */
|
||
|
upsdrv_info_t upsdrv_info = {
|
||
|
DRIVER_NAME,
|
||
|
DRIVER_VERSION,
|
||
|
"Marek Michalkiewicz <marekm@amelek.gda.pl>",
|
||
|
DRV_STABLE,
|
||
|
{ NULL }
|
||
|
};
|
||
|
|
||
|
static int
|
||
|
etapro_get_response(const char *resp_type)
|
||
|
{
|
||
|
char tmp[256];
|
||
|
char *cp;
|
||
|
unsigned int n, val;
|
||
|
|
||
|
/* Read until a newline is found or there is no room in the buffer.
|
||
|
Unlike ser_get_line(), don't discard the following characters
|
||
|
because we have to handle multi-line responses. */
|
||
|
n = 0;
|
||
|
while (ser_get_char(upsfd, (unsigned char *)&tmp[n], 1, 0) == 1) {
|
||
|
if (n >= sizeof(tmp) - 1 || tmp[n] == '\n')
|
||
|
break;
|
||
|
n++;
|
||
|
}
|
||
|
tmp[n] = '\0';
|
||
|
if (n == 0) {
|
||
|
upslogx(LOG_ERR, "no response from UPS");
|
||
|
return -1;
|
||
|
}
|
||
|
/* Search for start of response (skip any echoed back command). */
|
||
|
cp = strstr(tmp, resp_type);
|
||
|
if (!cp || *cp == '\0' || cp[strlen(cp) - 1] != '\r') {
|
||
|
upslogx(LOG_ERR, "bad response (%s)", tmp);
|
||
|
return -1;
|
||
|
}
|
||
|
cp[strlen(cp) - 1] = '\0'; /* remove the CR */
|
||
|
|
||
|
switch (cp[1]) {
|
||
|
/* Handle ASCII text responses directly here. */
|
||
|
case 'R':
|
||
|
dstate_setinfo("ups.mfr", "%s", cp + 2);
|
||
|
return 0;
|
||
|
case 'S':
|
||
|
dstate_setinfo("ups.model", "%s", cp + 2);
|
||
|
return 0;
|
||
|
case 'T':
|
||
|
dstate_setinfo("ups.mfr.date", "%s", cp + 2);
|
||
|
return 0;
|
||
|
}
|
||
|
/* Handle all other responses as hexadecimal numbers. */
|
||
|
val = 0;
|
||
|
if (sscanf(cp + 2, "%x", &val) != 1) {
|
||
|
upslogx(LOG_ERR, "bad response format (%s)", tmp);
|
||
|
return -1;
|
||
|
}
|
||
|
return val;
|
||
|
}
|
||
|
|
||
|
static void
|
||
|
etapro_set_on_timer(int seconds)
|
||
|
{
|
||
|
int x;
|
||
|
|
||
|
if (seconds == 0) { /* cancel the running timer */
|
||
|
ser_send(upsfd, "RS\r");
|
||
|
x = etapro_get_response("SV");
|
||
|
if (x == 0x30)
|
||
|
return; /* OK */
|
||
|
} else {
|
||
|
if (seconds > 0x7fff) { /* minutes */
|
||
|
seconds = (seconds + 59) / 60;
|
||
|
if (seconds > 0x7fff)
|
||
|
seconds = 0x7fff;
|
||
|
printf("UPS on in %d minutes\n", seconds);
|
||
|
seconds |= 0x8000;
|
||
|
} else {
|
||
|
printf("UPS on in %d seconds\n", seconds);
|
||
|
}
|
||
|
|
||
|
ser_send(upsfd, "RN%04X\r", seconds);
|
||
|
x = etapro_get_response("SV");
|
||
|
if (x == 0x20)
|
||
|
return; /* OK */
|
||
|
}
|
||
|
upslogx(LOG_ERR, "etapro_set_on_timer: error, status=0x%02x", x);
|
||
|
}
|
||
|
|
||
|
static void
|
||
|
etapro_set_off_timer(int seconds)
|
||
|
{
|
||
|
int x;
|
||
|
|
||
|
if (seconds == 0) { /* cancel the running timer */
|
||
|
ser_send(upsfd, "RR\r");
|
||
|
x = etapro_get_response("SV");
|
||
|
if (x == 0x10)
|
||
|
return; /* OK */
|
||
|
} else {
|
||
|
if (seconds > 0x7fff) { /* minutes */
|
||
|
seconds /= 60;
|
||
|
if (seconds > 0x7fff)
|
||
|
seconds = 0x7fff;
|
||
|
printf("UPS off in %d minutes\n", seconds);
|
||
|
seconds |= 0x8000;
|
||
|
} else {
|
||
|
printf("UPS off in %d seconds\n", seconds);
|
||
|
}
|
||
|
|
||
|
ser_send(upsfd, "RO%04X\r", seconds);
|
||
|
x = etapro_get_response("SV");
|
||
|
if (x == 0)
|
||
|
return; /* OK */
|
||
|
}
|
||
|
upslogx(LOG_ERR, "etapro_set_off_timer: error, status=0x%02x", x);
|
||
|
}
|
||
|
|
||
|
static int instcmd(const char *cmdname, const char *extra)
|
||
|
{
|
||
|
if (!strcasecmp(cmdname, "load.off")) {
|
||
|
etapro_set_off_timer(1);
|
||
|
return STAT_INSTCMD_HANDLED;
|
||
|
}
|
||
|
|
||
|
if (!strcasecmp(cmdname, "load.on")) {
|
||
|
etapro_set_on_timer(1);
|
||
|
return STAT_INSTCMD_HANDLED;
|
||
|
}
|
||
|
|
||
|
if (!strcasecmp(cmdname, "shutdown.return")) {
|
||
|
upsdrv_shutdown();
|
||
|
return STAT_INSTCMD_HANDLED;
|
||
|
}
|
||
|
|
||
|
upslogx(LOG_NOTICE, "instcmd: unknown command [%s]", cmdname);
|
||
|
return STAT_INSTCMD_UNKNOWN;
|
||
|
}
|
||
|
|
||
|
void
|
||
|
upsdrv_initinfo(void)
|
||
|
{
|
||
|
dstate_addcmd("load.off");
|
||
|
dstate_addcmd("load.on");
|
||
|
dstate_addcmd("shutdown.return");
|
||
|
|
||
|
/* First command after power on returns junk - ignore it. */
|
||
|
ser_send(upsfd, "RI\r");
|
||
|
sleep(1);
|
||
|
|
||
|
upsdrv_updateinfo();
|
||
|
|
||
|
upsh.instcmd = instcmd;
|
||
|
}
|
||
|
|
||
|
void
|
||
|
upsdrv_updateinfo(void)
|
||
|
{
|
||
|
int x, flags;
|
||
|
double utility, outvolt, battvolt, loadpct;
|
||
|
|
||
|
ser_flush_in(upsfd, "", nut_debug_level);
|
||
|
ser_send(upsfd, "RI\r"); /* identify */
|
||
|
|
||
|
x = etapro_get_response("SR"); /* manufacturer */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
x = etapro_get_response("SS"); /* model */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
x = etapro_get_response("ST"); /* mfr date */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
x = etapro_get_response("SU"); /* UPS ident */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
|
||
|
ser_send(upsfd, "RP\r"); /* read measurements */
|
||
|
|
||
|
x = etapro_get_response("SO"); /* status flags */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
flags = x;
|
||
|
|
||
|
x = etapro_get_response("SG"); /* input voltage, 0xFF = 270V */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
utility = (270.0 / 255) * x;
|
||
|
|
||
|
x = etapro_get_response("SH"); /* output voltage, 0xFF = 270V */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
outvolt = (270.0 / 255) * x;
|
||
|
|
||
|
x = etapro_get_response("SI"); /* battery voltage, 0xFF = 14V */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
|
||
|
/* TODO: >= 1000VA models have a 24V battery (max 28V) - check
|
||
|
the model string returned by the RI command. */
|
||
|
battvolt = (14.0 / 255) * x;
|
||
|
|
||
|
x = etapro_get_response("SL"); /* load (on battery), 0xFF = 150% */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
loadpct = (150.0 / 255) * x;
|
||
|
|
||
|
x = etapro_get_response("SN"); /* time running on battery */
|
||
|
if (x < 0) {
|
||
|
dstate_datastale();
|
||
|
return;
|
||
|
}
|
||
|
/* This is the time how long the UPS has been running on battery
|
||
|
(in seconds, reset to zero after power returns), but there
|
||
|
seems to be no variable defined for this yet... */
|
||
|
|
||
|
status_init();
|
||
|
|
||
|
if (!(flags & 0x02))
|
||
|
status_set("OFF");
|
||
|
else if (flags & 0x01)
|
||
|
status_set("OL");
|
||
|
else
|
||
|
status_set("OB");
|
||
|
|
||
|
if (!(flags & 0x04))
|
||
|
status_set("LB");
|
||
|
|
||
|
/* TODO bit 3: 1 = ok, 0 = fault */
|
||
|
|
||
|
if (flags & 0x10)
|
||
|
status_set("BOOST");
|
||
|
|
||
|
if (loadpct > 100.0)
|
||
|
status_set("OVER");
|
||
|
|
||
|
/* Battery voltage out of range (lower than LB, or too high). */
|
||
|
if (flags & 0x20)
|
||
|
status_set("RB");
|
||
|
|
||
|
/* TODO bit 6: 1 = charging, 0 = full */
|
||
|
|
||
|
status_commit();
|
||
|
|
||
|
dstate_setinfo("input.voltage", "%03.1f", utility);
|
||
|
dstate_setinfo("output.voltage", "%03.1f", outvolt);
|
||
|
dstate_setinfo("battery.voltage", "%02.2f", battvolt);
|
||
|
dstate_setinfo("ups.load", "%03.1f", loadpct);
|
||
|
|
||
|
dstate_dataok();
|
||
|
}
|
||
|
|
||
|
/* TODO: delays should be tunable, the UPS supports max 32767 minutes. */
|
||
|
|
||
|
/* Shutdown command to off delay in seconds. */
|
||
|
#define SHUTDOWN_GRACE_TIME 10
|
||
|
|
||
|
/* Shutdown to return delay in seconds. */
|
||
|
#define SHUTDOWN_TO_RETURN_TIME 15
|
||
|
|
||
|
void
|
||
|
upsdrv_shutdown(void)
|
||
|
{
|
||
|
etapro_set_on_timer(SHUTDOWN_GRACE_TIME + SHUTDOWN_TO_RETURN_TIME);
|
||
|
etapro_set_off_timer(SHUTDOWN_GRACE_TIME);
|
||
|
}
|
||
|
|
||
|
void
|
||
|
upsdrv_help(void)
|
||
|
{
|
||
|
}
|
||
|
|
||
|
void
|
||
|
upsdrv_makevartable(void)
|
||
|
{
|
||
|
}
|
||
|
|
||
|
void
|
||
|
upsdrv_initups(void)
|
||
|
{
|
||
|
upsfd = ser_open(device_path);
|
||
|
ser_set_speed(upsfd, device_path, B1200);
|
||
|
|
||
|
ser_set_dtr(upsfd, 0);
|
||
|
ser_set_rts(upsfd, 1);
|
||
|
}
|
||
|
|
||
|
void upsdrv_cleanup(void)
|
||
|
{
|
||
|