MGE-SHUT(8)
|
||
|
===========
|
||
|
|
||
|
NAME
|
||
|
----
|
||
|
|
||
|
mge-shut - Driver for SHUT Protocol UPS equipment
|
||
|
|
||
|
SYNOPSIS
|
||
|
--------
|
||
|
|
||
|
*mge-shut* -h
|
||
|
|
||
|
*mge-shut* -a 'UPS_NAME' ['OPTIONS']
|
||
|
|
||
|
NOTE: This man page only documents the hardware-specific features of the
|
||
|
mge-shut driver. For information about the core driver, see
|
||
|
linkman:nutupsdrv[8].
|
||
|
|
||
|
SUPPORTED HARDWARE
|
||
|
------------------
|
||
|
|
||
|
mge-shut supports all recent Eaton, MGE and Dell UPS models which use the SHUT
|
||
|
(Serial HID UPS Transfer) protocol.
|
||
|
|
||
|
Older MGE models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U-Talk
|
||
|
protocol and should use the mge-utalk driver.
|
||
|
|
||
|
EXTRA ARGUMENTS
|
||
|
---------------
|
||
|
|
||
|
This driver also supports the following optional settings:
|
||
|
|
||
|
*lowbatt*='num'::
|
||
|
Set the low battery warning threshold at which shutdown is initiated by
|
||
|
linkman:upsmon[8].
|
||
|
+
|
||
|
The factory default value is 30 (in percent), and can be settable depending on
|
||
|
the exact model.
|
||
|
|
||
|
*offdelay*='num'::
|
||
|
Set the timer before the UPS is turned off after the kill power command is
|
||
|
sent (via the *-k* switch).
|
||
|
+
|
||
|
The default value is 20 (in seconds). Usually this *must be lower* than
|
||
|
'ondelay', but the driver will *not* warn you upon startup if it isn't.
|
||
|
|
||
|
*ondelay*='num'::
|
||
|
Set the timer for the UPS to switch on in case the power returns after the
|
||
|
kill power command had been sent but before the actual switch off. This
|
||
|
ensures the machines connected to the UPS are, in all cases, rebooted after
|
||
|
a power failure.
|
||
|
+
|
||
|
The default value is 30 (in seconds). Usually this *must be greater*
|
||
|
than offdelay, but the driver will *not* warn you upon startup if it
|
||
|
isn't. Some UPS'es will restart no matter what, even if the power is
|
||
|
(still) out at the moment this timer elapses. In that case, you could try
|
||
|
if setting 'ondelay = -1' in *ups.conf* helps.
|
||
|
|
||
|
*notification*='num'::
|
||
|
Set notification type to 1 (no), 2 (light) or 3 (yes).
|
||
|
+
|
||
|
The default value is 3 (yes) because of some early Ellipse models which
|
||
|
need it.
|
||
|
|
||
|
KNOWN ISSUES
|
||
|
------------
|
||
|
|
||
|
Repetitive timeout and staleness
|
||
|
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
|
||
|
|
||
|
Some models tends to be unresponsive with the default polling frequency.
|
||
|
The result is that you have some "data stale" errors in your system log.
|
||
|
|
||
|
In this case, simply modify the general parameter "pollinterval" to a higher
|
||
|
value (like 10 for 10 seconds). This should solve the issue.
|
||
|
|
||
|
Using 'notification=3' might also help.
|
||
|
|
||
|
AUTHOR
|
||
|
------
|
||
|
|
||
|
Arnaud Quette
|
||
|
|
||
|
SEE ALSO
|
||
|
--------
|
||
|
|
||
|
The core driver
|
||
|
~~~~~~~~~~~~~~~~
|
||
|
linkman:nutupsdrv[8]
|
||
|
|
||
|
Internet resources
|
||
|
~~~~~~~~~~~~~~~~~~
|
||
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|