snmp-ups(8)
|
|
|
|
===========
|
|
|
|
|
|
|
|
NAME
|
|
|
|
----
|
|
|
|
|
|
|
|
snmp-ups - Multi-MIB Driver for SNMP UPS equipment
|
|
|
|
|
|
|
|
NOTE
|
|
|
|
----
|
|
|
|
This man page only documents the hardware-specific features of the
|
|
|
|
snmp-ups driver. For information about the core driver, see
|
|
|
|
linkman:nutupsdrv[8].
|
|
|
|
|
|
|
|
SUPPORTED HARDWARE
|
|
|
|
------------------
|
|
|
|
|
|
|
|
The snmp-ups driver automatically detects and supports a wide range of devices by loading various MIBS:
|
|
|
|
*ietf*::
|
|
|
|
UPS that is RFC 1628 (UPS MIB) compliant, e.g. MGE UPS SYSTEMS, Liebert, perhaps others (default)
|
|
|
|
|
|
|
|
*mge*::
|
|
|
|
MGE UPS SYSTEMS and MGE Office Protection Systems devices with SNMP cards (ref 66062, 66045, 66074 and 66244)
|
|
|
|
|
|
|
|
*apcc*::
|
|
|
|
APC AP9606 APC Web/SNMP management card, perhaps others
|
|
|
|
|
|
|
|
*netvision*::
|
|
|
|
Socomec Sicon UPS with Netvision Web/SNMP management card/external box
|
|
|
|
|
|
|
|
*pw*::
|
|
|
|
Powerware devices with ConnectUPS SNMP cards
|
|
|
|
|
|
|
|
*aphel_genesisII*::
|
|
|
|
Eaton Powerware ePDU Monitored
|
|
|
|
|
|
|
|
*aphel_revelation*::
|
|
|
|
Eaton Powerware ePDU Managed
|
|
|
|
|
|
|
|
*raritan*::
|
|
|
|
Various Raritan PDUs
|
|
|
|
|
|
|
|
*baytech*::
|
|
|
|
Various BayTech PDUs
|
|
|
|
|
|
|
|
*cpqpower*::
|
|
|
|
HP/Compaq AF401A management card, perhaps others
|
|
|
|
|
2012-01-24 10:22:33 +00:00
|
|
|
*cyberpower*::
|
|
|
|
Cyberpower RMCARD201. Should also support RMCARD100 (net version), RMCARD202 and RMCARD301
|
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
EXTRA ARGUMENTS
|
|
|
|
---------------
|
|
|
|
|
|
|
|
This driver supports the following optional settings in the
|
|
|
|
linkman:ups.conf[5]:
|
|
|
|
|
|
|
|
*mibs*='name'::
|
|
|
|
Set MIB compliance (default=auto, allowed entries: refer to the above SUPPORTED HARDWARE).
|
|
|
|
With "auto", the driver will try a select set of SNMP objects until it finds
|
|
|
|
one that the device responds to.
|
|
|
|
|
|
|
|
*community*='name'::
|
|
|
|
Set community name (default = public).
|
|
|
|
Note that you require a RW community name to change UPS settings (as for a powerdown).
|
|
|
|
|
|
|
|
*snmp_version*='version'::
|
|
|
|
Set SNMP version (default = v1, the other allowed value is v2c)
|
|
|
|
|
|
|
|
*pollfreq*='value'::
|
|
|
|
Set polling frequency in seconds, to reduce network flow (default=30)
|
|
|
|
|
|
|
|
*notransferoids*::
|
|
|
|
Disable the monitoring of the low and high voltage transfer OIDs in
|
|
|
|
the hardware. This will remove input.transfer.low and input.transfer.high
|
|
|
|
from the list of variables. This should only be used on APCC Symmetra
|
|
|
|
equipment which has strangeness in the three-phase power reporting.
|
|
|
|
|
|
|
|
*secLevel*='value'::
|
|
|
|
Set the securityLevel used for SNMPv3 messages (default=noAuthNoPriv,
|
|
|
|
allowed: authNoPriv,authPriv)
|
|
|
|
|
|
|
|
*secName*='value'::
|
|
|
|
Set the securityName used for authenticated SNMPv3 messages (no default)
|
|
|
|
|
|
|
|
*authPassword*='value'::
|
|
|
|
Set the authentication pass phrase used for authenticated SNMPv3 messages
|
|
|
|
(no default)
|
|
|
|
|
|
|
|
*privPassword*='value'::
|
|
|
|
Set the privacy pass phrase used for encrypted SNMPv3 messages (no default)
|
|
|
|
|
|
|
|
*authProtocol*='value'::
|
|
|
|
Set the authentication protocol (MD5 or SHA) used for authenticated SNMPv3
|
|
|
|
messages (default=MD5)
|
|
|
|
|
|
|
|
*privProtocol*='value'::
|
|
|
|
Set the privacy protocol (DES or AES) used for encrypted SNMPv3 messages
|
|
|
|
(default=DES)
|
|
|
|
|
|
|
|
REQUIREMENTS
|
|
|
|
------------
|
|
|
|
You will need to install the Net-SNMP package from
|
|
|
|
http://www.net-snmp.org/ before building this driver.
|
|
|
|
|
|
|
|
SNMP v3 also requires OpenSSL support from http://www.openssl.org.
|
|
|
|
|
|
|
|
LIMITATION
|
|
|
|
----------
|
|
|
|
Shutdown
|
|
|
|
~~~~~~~~
|
|
|
|
|
|
|
|
This driver does not provide a proper upsdrv_shutdown() function. There probably
|
|
|
|
never will be one, since at the time this script should run (near the end of
|
|
|
|
the system halt script), there will be no network capabilities anymore.
|
|
|
|
Probably the only way to shutdown an SNMP UPS is by sending it a shutdown
|
|
|
|
with delay command through linkman:upscmd[8] and hope for the best that the
|
|
|
|
system will have finished shutting down before the power is cut.
|
|
|
|
|
|
|
|
INSTALLATION
|
|
|
|
------------
|
|
|
|
This driver is only built if the Net-SNMP development files are present on the system.
|
|
|
|
You can also force it to be built by using "configure --with-snmp=yes" before calling make.
|
|
|
|
|
|
|
|
IMPLEMENTATION
|
|
|
|
--------------
|
|
|
|
The hostname of the UPS is specified with the "port" value in
|
|
|
|
`ups.conf`, i.e.:
|
|
|
|
|
|
|
|
[snmpv1]
|
|
|
|
driver = snmp-ups
|
|
|
|
port = snmp-ups.example.com
|
|
|
|
community = public
|
|
|
|
snmp_version = v1
|
|
|
|
mibs = ietf
|
|
|
|
pollfreq = 15
|
|
|
|
desc = "Example SNMP v1 device"
|
|
|
|
|
|
|
|
[snmpv3]
|
|
|
|
driver = snmp-ups
|
|
|
|
port = 166.99.224.132
|
|
|
|
mibs = mge
|
|
|
|
secLevel = authPriv
|
|
|
|
secName = mysecurityname
|
|
|
|
authPassword = myauthenticationpassphrase
|
|
|
|
privPassword = myprivatepassphrase
|
|
|
|
desc = "Example SNMP v3 device, with the highest security level"
|
|
|
|
|
|
|
|
AUTHORS
|
|
|
|
-------
|
|
|
|
Arnaud Quette, Dmitry Frolov
|
|
|
|
|
|
|
|
Sponsored by Eaton <http://www.eaton.com>
|
|
|
|
and originally by MGE UPS SYSTEMS <http://www.mgeups.com/>
|
|
|
|
|
|
|
|
|
|
|
|
SEE ALSO
|
|
|
|
--------
|
|
|
|
|
|
|
|
The core driver:
|
|
|
|
~~~~~~~~~~~~~~~~
|
|
|
|
linkman:nutupsdrv[8]
|
|
|
|
|
|
|
|
NUT SNMP Protocols Library
|
|
|
|
~~~~~~~~~~~~~~~~~~~~~~~~~~
|
|
|
|
Available at: http://www.networkupstools.org/protocols/snmp/
|
|
|
|
|
|
|
|
Internet resources:
|
|
|
|
~~~~~~~~~~~~~~~~~~~
|
|
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|