nut/man/liebert.8

43 lines
1.4 KiB
Groff
Raw Normal View History

2010-03-25 23:20:59 +00:00
.TH LIEBERT 8 "Wed Jul 28 2009" "" "Network UPS Tools (NUT)"
.SH NAME
liebert \- Driver for Liebert contact\(hyclosure UPS equipment
.SH NOTE
This man page only documents the hardware\(hyspecific features of the
liebert driver. For information about the core driver, see
\fBnutupsdrv\fR(8).
.SH SUPPORTED HARDWARE
This driver supports some Liebert UPS equipment with a contact\(hyclosure
interface. This includes the UPStation GXT2 with their contact\(hyclosure
cable. The smart mode ("Multilink") cable is not supported by this
driver.
.SH EXTRA ARGUMENTS
This driver does not support any extra settings in the
\fBups.conf\fR(5).
.SH BUGS
This driver does not yet support shutdowns by raising DTR. Be aware
that shutdowns are not possible with the stock contact\(hyclosure cable.
You may have to build another cable with DTR connected through to the
UPS for it to work.
There is no way for this driver to detect the hardware or cable. It
will start up successfully even if no UPS is present. This is a
fundamental limitation of any contact\(hyclosure driver.
Since the TX and RX signals are only used to detect loopback (when the
contacts close), the baud rate should not matter. However, it is hardcoded to
9600 baud to prevent problems with noise if the port defaults to a higher baud
rate.
.SH SEE ALSO
.SS The core driver:
\fBnutupsdrv\fR(8)
.SS Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/