234 lines
14 KiB
Text
234 lines
14 KiB
Text
|
Desc: APC UPS cables
|
||
|
File: apc.txt
|
||
|
Date: 12 Februari 2010
|
||
|
Auth: Arjen de Korte <adkorte-guest@alioth.debian.org
|
||
|
|
||
|
http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-August/000118.html
|
||
|
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Black APC 940-0024C Smart Signalling UPS Cable Wiring Diagram |
|
||
|
| This information is verified and tested to be 100% correct. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||
|
| --------- -------- -------------- |
|
||
|
| |
|
||
|
| (SHELL)<---------+----//----+----------------<(SHELL) |
|
||
|
| | | |
|
||
|
| - - |
|
||
|
| | | | | |
|
||
|
| CHASSIS 9<--------------//---------------------<5 SG |
|
||
|
| | | | | |
|
||
|
| TXD 2<--------------//---------------------<2 RXD |
|
||
|
| | | | | |
|
||
|
| RXD 1<--------------//---------------------<3 TXD |
|
||
|
| | | | | |
|
||
|
| - - +--<1 DCD |
|
||
|
| | |
|
||
|
| +--<4 DTR |
|
||
|
| NOTES: |
|
||
|
| Cable type is shielded 28AWG. +--<7 RTS |
|
||
|
| The DB shells are connected | |
|
||
|
| to each other via the shield. +--<8 CTS |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Operation: The UPS communicates with the Computer via |
|
||
|
| ordinary RS-232 serial protocol at 2400-8N1 with software |
|
||
|
| flow control. Jumpered pins in the DB9F connector are for |
|
||
|
| automatic or PNP cable identification by UPS software. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Male (pins) Female (holes) |
|
||
|
| DB9 RS-232 PC |
|
||
|
| type connector 1 5 5 1 |
|
||
|
| ---------------- _______________ _______________ |
|
||
|
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||
|
| looking into the \ . . . . / \ o o o o / |
|
||
|
| end of the cable ----------- ----------- |
|
||
|
| 6 9 9 6 |
|
||
|
| |
|
||
|
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
|
||
|
|
||
|
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Gray APC 940-0020B Simple Signalling UPS Cable Wiring Diagram |
|
||
|
| This information is verified and tested to be 100% correct. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||
|
| --------- -------- -------------- |
|
||
|
| |
|
||
|
| (SHELL)<-------+----//----+-------------------<(SHELL) |
|
||
|
| | | |
|
||
|
| CHASSIS 9<--+ - - |
|
||
|
| | | | | | |
|
||
|
| COMMON 4<--+---------//------------------------<5 SG |
|
||
|
| | | | | |
|
||
|
| POWER-FAIL 2<------------//------------------------<8 CTS |
|
||
|
| | | | | |
|
||
|
| SHUTDOWN 1<------------//------------------------<4 DTR |
|
||
|
| | | | | |
|
||
|
| BATTERY-LOW 5<------------//--------47K--+--47K--+--<7 RTS |
|
||
|
| | | | | | | |
|
||
|
| - - | E | |
|
||
|
| NOTES: |B |<--+ |
|
||
|
| RTS must be held at +V SPACE. +---| |
|
||
|
| TXD must be held at -V MARK. 2N3906 |---+--<1 DCD |
|
||
|
| All resistors are 5% 1/8W CF. C | |
|
||
|
| Cable type is shielded 28AWG. 4K7 |
|
||
|
| The DB shells are connected | |
|
||
|
| to each other via the shield. +--<3 TXD |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Operation: The UPS communicates with the Computer via |
|
||
|
| the RS-232 handshaking lines only, and does not use any |
|
||
|
| serial protocol. Upon power fail, the UPS forces CTS to |
|
||
|
| -V MARK. When the battery is low, the UPS forces DCD to |
|
||
|
| +V SPACE via the transistor. When the Computer forces a |
|
||
|
| +V SPACE on DTR, the UPS will shut down and turn off. |
|
||
|
| Presence of the cable can be sensed by signaling on TXD |
|
||
|
| while monitoring DCD. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Male (pins) Female (holes) |
|
||
|
| DB9 RS-232 PC |
|
||
|
| type connector 1 5 5 1 |
|
||
|
| ---------------- _______________ _______________ |
|
||
|
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||
|
| looking into the \ . . . . / \ o o o o / |
|
||
|
| end of the cable ----------- ----------- |
|
||
|
| 6 9 9 6 |
|
||
|
| |
|
||
|
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
|
||
|
|
||
|
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Gray APC 940-0095A Smart Signalling UPS Cable Wiring Diagram |
|
||
|
| This information is verified and tested to be 100% correct. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| DB9M(UPS) 2m Cable DB9F(Computer) |
|
||
|
| --------- -------- -------------- |
|
||
|
| |
|
||
|
| (SHELL)<-------+----//----+--------------------<(SHELL) |
|
||
|
| | | |
|
||
|
| CHASSIS 9<--+ - - |
|
||
|
| | | | | | |
|
||
|
| COMMON 4<--+---------//-------------------------<5 SG |
|
||
|
| | | | | |
|
||
|
| BATTERY-LOW 5<------------//--------47K--+--47K--+---<4 DTR |
|
||
|
| | | | | | | |
|
||
|
| | +---<6 DSR |
|
||
|
| | | | | | E | |
|
||
|
| NOTES: |B |<--+---<8 CTS |
|
||
|
| DTR must be held at +V SPACE. | | +---| |
|
||
|
| TXD must be held at -V MARK. 2N3906 |---+---<1 DCD |
|
||
|
| All resistors are 5% 1/8W CF. | | C | |
|
||
|
| Cable type is shielded 28AWG. 4K7 |
|
||
|
| The DB shells are connected | | | |
|
||
|
| to each other via the shield. +----4K7---+---<3 TXD |
|
||
|
| | | | | | |
|
||
|
| | |
|
||
|
| | | | | | 1N4148 |
|
||
|
| SHUTDOWN 1<------------//----------+----|<|-------<7 RTS |
|
||
|
| | | | | K A |
|
||
|
| POWER-FAIL 2<------------//---------------------+---<2 RXD |
|
||
|
| | | | | | |
|
||
|
| - - +---<9 RI |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Operation: The UPS can communicate with the Computer |
|
||
|
| solely via the RS-232 handshaking lines, or via RS-232 |
|
||
|
| serial protocol at 2400-8N1 with software flow control. |
|
||
|
| Upon power fail, the UPS forces RI to -V MARK. When the |
|
||
|
| battery is low, the UPS forces DCD to +V SPACE via the |
|
||
|
| transistor. When the Computer forces a +V SPACE on RTS, |
|
||
|
| the UPS will shut down and turn off. Jumpered pins in |
|
||
|
| the DB9F connector allow for automatic automatic or PNP |
|
||
|
| cable identification by UPS software. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Male (pins) Female (holes) |
|
||
|
| DB9 RS-232 PC |
|
||
|
| type connector 1 5 5 1 |
|
||
|
| ---------------- _______________ _______________ |
|
||
|
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||
|
| looking into the \ . . . . / \ o o o o / |
|
||
|
| end of the cable ----------- ----------- |
|
||
|
| 6 9 9 6 |
|
||
|
| |
|
||
|
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
|
||
|
|
||
|
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Universal APC serial extension cable for use in conjunction |
|
||
|
| with an APC UPS cable. This cable is verified to work. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| DB9M to UPS cable Shielded Cable DB9F to Computer |
|
||
|
| ----------------- --- 28AWG ---- ---------------- |
|
||
|
| |
|
||
|
| (SHELL)<----+-------------//-------------+----<(SHELL) |
|
||
|
| | | |
|
||
|
| - - |
|
||
|
| | | | | |
|
||
|
| 1<------------------//------------------<1 DCD |
|
||
|
| | | | | |
|
||
|
| 2<------------------//------------------<2 RXD |
|
||
|
| | | | | |
|
||
|
| 3<------------------//------------------<3 TXD |
|
||
|
| | | | | |
|
||
|
| 4<------------------//------------------<4 DTR |
|
||
|
| | | | | |
|
||
|
| 5<------------------//------------------<5 SG |
|
||
|
| | | | | |
|
||
|
| 6<------------------//------------------<6 DSR |
|
||
|
| | | | | |
|
||
|
| 7<------------------//------------------<7 RTS |
|
||
|
| | | | | |
|
||
|
| 8<------------------//------------------<8 CTS |
|
||
|
| | | | | |
|
||
|
| 9<------------------//------------------<9 RI |
|
||
|
| | | | | |
|
||
|
| - - |
|
||
|
| NOTE: The DB shells are connected to each other via the shield. |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
| |
|
||
|
| Male (pins) Female (holes) |
|
||
|
| DB9 RS-232 PC |
|
||
|
| type connector 1 5 5 1 |
|
||
|
| ---------------- _______________ _______________ |
|
||
|
| Pinout numbering \ . . . . . / \ o o o o o / |
|
||
|
| looking into the \ . . . . / \ o o o o / |
|
||
|
| end of the cable ----------- ----------- |
|
||
|
| 6 9 9 6 |
|
||
|
| |
|
||
|
| NOTE: Solder a wire to the metal shell for use as a FRAME-GND |
|
||
|
| |
|
||
|
+-----------------------------------------------------------------+
|
||
|
|