2010-02-24 21:58:53 +00:00
|
|
|
#! /bin/sh
|
|
|
|
### BEGIN INIT INFO
|
|
|
|
# Provides: nut
|
2011-09-29 18:17:51 +00:00
|
|
|
# Required-Start: $local_fs $syslog $network $remote_fs udev
|
|
|
|
# Required-Stop: $local_fs $syslog $network $remote_fs udev
|
2010-02-24 21:58:53 +00:00
|
|
|
# Default-Start: 2 3 4 5
|
|
|
|
# Default-Stop: 0 1 6
|
|
|
|
# Short-Description: Network UPS Tools initscript
|
|
|
|
# Description: This script take care of starting and stopping the
|
|
|
|
# Network UPS Tools components. When needed, it also
|
|
|
|
# handle the UPS hardware shutdown.
|
|
|
|
### END INIT INFO
|
|
|
|
|
|
|
|
# Author: Arnaud Quette <aquette@debian.org>
|
|
|
|
|
|
|
|
PATH=/sbin:/usr/sbin:/bin:/usr/bin:/usr/local/sbin:/usr/local/bin
|
|
|
|
|
|
|
|
NAME=nut
|
|
|
|
DESC="Network UPS Tools"
|
|
|
|
CONFIG=/etc/nut/nut.conf
|
|
|
|
|
|
|
|
. /lib/lsb/init-functions
|
|
|
|
|
|
|
|
# set upsd specific options. use "man upsd" for more info
|
|
|
|
UPSD_OPTIONS=""
|
|
|
|
|
|
|
|
# set upsmon specific options. use "man upsmon" for more info
|
|
|
|
UPSMON_OPTIONS=""
|
|
|
|
|
|
|
|
# Include NUT nut.conf
|
|
|
|
if [ -f $CONFIG ] ; then
|
|
|
|
. $CONFIG
|
|
|
|
fi
|
|
|
|
|
|
|
|
# Explicitly require the configuration to be done in /etc/nut/nut.conf
|
|
|
|
if [ "x$MODE" = "xnone" -o -z "$MODE" ] ; then
|
|
|
|
log_action_msg "$NAME disabled, please adjust the configuration to your needs"
|
|
|
|
log_action_msg "Then set MODE to a suitable value in $CONFIG to enable it"
|
|
|
|
# exit success to avoid breaking the install process!
|
|
|
|
exit 0
|
|
|
|
fi
|
|
|
|
|
|
|
|
pid_dir=/var/run/nut
|
|
|
|
upsmon_pid=${pid_dir}/upsmon.pid
|
|
|
|
upsd_pid=${pid_dir}/upsd.pid
|
|
|
|
upsd=/sbin/upsd
|
|
|
|
upsdrvctl=/sbin/upsdrvctl
|
|
|
|
upsmon=/sbin/upsmon
|
|
|
|
log=">/dev/null 2>/dev/null"
|
|
|
|
|
|
|
|
# Check if /var/run/nut exists and has the correct perms
|
|
|
|
check_var_directory() {
|
|
|
|
[ ! -d ${pid_dir} ] && mkdir -p ${pid_dir} \
|
|
|
|
&& chown root:nut ${pid_dir} \
|
|
|
|
&& chmod 770 ${pid_dir}
|
|
|
|
}
|
|
|
|
|
|
|
|
# check if the right components are running
|
|
|
|
check_status() {
|
|
|
|
case "$MODE" in
|
|
|
|
standalone|netserver)
|
|
|
|
status_of_proc -p $upsd_pid $upsd upsd
|
|
|
|
status_of_proc -p $upsmon_pid $upsmon upsmon
|
|
|
|
;;
|
|
|
|
netclient)
|
|
|
|
status_of_proc -p $upsmon_pid $upsmon upsmon
|
|
|
|
;;
|
|
|
|
none|*)
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
}
|
|
|
|
|
|
|
|
start_stop_server () {
|
|
|
|
case "$MODE" in
|
|
|
|
standalone|netserver)
|
|
|
|
case "$1" in
|
|
|
|
start)
|
|
|
|
! $upsdrvctl start >/dev/null 2>&1 && \
|
|
|
|
log_progress_msg "(driver(s) failed)" || log_progress_msg "driver(s)"
|
|
|
|
start-stop-daemon -S -q -p $upsd_pid -x $upsd \
|
|
|
|
-- $UPSD_OPTIONS >/dev/null 2>&1
|
|
|
|
;;
|
|
|
|
stop)
|
|
|
|
start-stop-daemon -K -o -q -p $upsd_pid -n upsd >/dev/null 2>&1
|
|
|
|
! /sbin/upsdrvctl stop >/dev/null 2>&1 && \
|
|
|
|
log_progress_msg "(driver(s) failed)" || log_progress_msg "driver(s)"
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
;;
|
|
|
|
none|netclient|*)
|
|
|
|
return 1
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
}
|
|
|
|
|
|
|
|
start_stop_client () {
|
|
|
|
case "$MODE" in
|
|
|
|
standalone|netserver|netclient)
|
|
|
|
case "$1" in
|
|
|
|
start)
|
|
|
|
start-stop-daemon -S -q -p $upsmon_pid -x $upsmon \
|
|
|
|
-- $UPSMON_OPTIONS >/dev/null 2>&1
|
|
|
|
;;
|
|
|
|
stop)
|
|
|
|
start-stop-daemon -K -o -q -p $upsmon_pid -n upsmon >/dev/null 2>&1
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
;;
|
|
|
|
none|*)
|
|
|
|
return 1
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
}
|
|
|
|
|
|
|
|
case "$1" in
|
|
|
|
|
|
|
|
start)
|
|
|
|
log_daemon_msg "Starting $DESC"
|
|
|
|
check_var_directory
|
|
|
|
start_stop_server start && log_progress_msg "upsd"
|
|
|
|
start_stop_client start && log_progress_msg "upsmon"
|
|
|
|
log_end_msg 0
|
|
|
|
;;
|
|
|
|
|
|
|
|
stop)
|
|
|
|
log_daemon_msg "Stopping $DESC"
|
|
|
|
start_stop_server stop && log_progress_msg "upsd"
|
|
|
|
start_stop_client stop && log_progress_msg "upsmon"
|
|
|
|
log_end_msg 0
|
|
|
|
;;
|
|
|
|
|
|
|
|
reload)
|
|
|
|
$upsd -c reload >/dev/null 2>&1
|
|
|
|
$upsmon -c reload >/dev/null 2>&1
|
|
|
|
;;
|
|
|
|
|
|
|
|
restart|force-reload)
|
|
|
|
log_daemon_msg "Restarting $DESC"
|
|
|
|
start_stop_client stop
|
|
|
|
start_stop_server stop
|
|
|
|
sleep 5
|
|
|
|
check_var_directory
|
|
|
|
start_stop_server start && log_progress_msg "upsd"
|
|
|
|
start_stop_client start && log_progress_msg "upsmon"
|
|
|
|
log_end_msg 0
|
|
|
|
;;
|
|
|
|
|
|
|
|
status)
|
|
|
|
#log_daemon_msg "Checking status of $DESC"
|
|
|
|
echo "Checking status of $DESC"
|
|
|
|
check_status
|
|
|
|
exit $?
|
|
|
|
;;
|
|
|
|
|
|
|
|
poweroff)
|
|
|
|
flag=`sed -ne 's#^ *POWERDOWNFLAG *\(.*\)$#\1#p' /etc/nut/upsmon.conf`
|
|
|
|
wait_delay=`sed -ne 's#^ *POWEROFF_WAIT= *\(.*\)$#\1#p' /etc/nut/nut.conf`
|
|
|
|
if [ -f "$flag" ] ; then
|
|
|
|
if $upsmon -K >/dev/null 2>&1 ; then
|
|
|
|
log_daemon_msg "Shutting down the UPS ..."
|
|
|
|
sleep 1
|
|
|
|
if $upsdrvctl shutdown ; then
|
|
|
|
sleep 5
|
|
|
|
log_progress_msg "Waiting for UPS to cut the power"
|
|
|
|
log_end_msg 0
|
|
|
|
else
|
|
|
|
log_progress_msg "Shutdown failed."
|
|
|
|
log_progress_msg "Waiting for UPS batteries to run down"
|
|
|
|
log_end_msg 0
|
|
|
|
fi
|
|
|
|
if [ "$wait_delay" ] ; then
|
|
|
|
log_daemon_msg " (will reboot after $wait_delay) ..."
|
|
|
|
sleep "$wait_delay"
|
|
|
|
invoke-rc.d reboot stop
|
|
|
|
fi
|
|
|
|
else
|
|
|
|
log_daemon_msg "Power down flag is not set (UPS shutdown not needed)"
|
|
|
|
fi
|
|
|
|
else
|
|
|
|
if [ -z "$flag" ] ; then
|
|
|
|
log_daemon_msg "##########################################################"
|
|
|
|
log_progress_msg "## POWERDOWNFLAG is not defined in /etc/nut/upsmon.conf ##"
|
|
|
|
log_progress_msg "## ##"
|
|
|
|
log_progress_msg "## Please read the Manual page upsmon.conf(5) ##"
|
|
|
|
log_progress_msg "##########################################################"
|
|
|
|
log_end_msg 0
|
|
|
|
fi
|
|
|
|
fi
|
|
|
|
;;
|
|
|
|
|
|
|
|
*)
|
|
|
|
N=/etc/init.d/$NAME
|
|
|
|
echo "Usage: $N {start|stop|reload|restart|force-reload|status|poweroff}" >&2
|
|
|
|
exit 1
|
|
|
|
;;
|
|
|
|
esac
|
|
|
|
|
|
|
|
exit 0
|