206 lines
6.4 KiB
Text
206 lines
6.4 KiB
Text
|
POWERCOM(8)
|
||
|
===========
|
||
|
|
||
|
NAME
|
||
|
----
|
||
|
|
||
|
powercom - UPS driver for Powercom/Trust/Advice UPS equipment
|
||
|
|
||
|
NOTE
|
||
|
----
|
||
|
This man page only documents the hardware-specific features of the
|
||
|
powercom driver. For information about the core driver, see
|
||
|
linkman:nutupsdrv[8].
|
||
|
|
||
|
SUPPORTED HARDWARE
|
||
|
------------------
|
||
|
This driver supports many similar kinds of UPS hardware. The most common
|
||
|
ones are the Trust 425/625, Powercom, and Advice Partner/King PR750.
|
||
|
Others using the same protocol may also work.
|
||
|
|
||
|
EXTRA ARGUMENTS
|
||
|
---------------
|
||
|
This driver supports the following optional settings in the
|
||
|
linkman:ups.conf[5] file:
|
||
|
|
||
|
*linevoltage*='value'::
|
||
|
An integer specifying the mains voltage. It can't be auto detected.
|
||
|
Acceptable values are in the range of 110--120 or 220--240. The default
|
||
|
is '230'.
|
||
|
|
||
|
*manufacturer*='name'::
|
||
|
Specify the manufacturer name, which also can't be auto detected. This is
|
||
|
a user defined string, so any name is acceptable. The default is
|
||
|
'PowerCom'.
|
||
|
|
||
|
*modelname*='name'::
|
||
|
Specify the model name, which also can't be auto detected. This is a
|
||
|
user defined string, so any name is acceptable. The default is
|
||
|
'Unknown'.
|
||
|
|
||
|
*serialnumber*='value'::
|
||
|
Like modelname above, but for the serial number. The default is
|
||
|
'Unknown'.
|
||
|
|
||
|
*type*='name'::
|
||
|
The exact type of the communication protocol within the powercom family,
|
||
|
that will be used to communicate with the UPS. The type is named after
|
||
|
the first modelname that was coded with that protocol. The acceptable
|
||
|
names are 'KP625AP', 'Trust', 'Egys', 'KIN', 'BNT', 'IMP' and 'BNT-other'. The
|
||
|
default is 'Trust'.
|
||
|
+
|
||
|
'BNT-other' is a special type for BNT 100-120V models.
|
||
|
For this type you can (I think must!) specify voltage, batteryPercentage,
|
||
|
loadPercentage and validationSequence.
|
||
|
|
||
|
*numOfBytesFromUPS*='value'::
|
||
|
The number of bytes in a UPS frame. The default is type-dependent and
|
||
|
is given below.
|
||
|
|
||
|
*methodOfFlowControl*='name'::
|
||
|
The method of serial communication flow control that is engaged by the
|
||
|
UPS. The default is type-dependent and is given below. Acceptable names
|
||
|
are 'dtr0rts1', 'dtr1' or 'no_flow_control'.
|
||
|
|
||
|
*shutdownArguments*={{'minutes','seconds'},'whether_minutes_should_be_used'}::
|
||
|
The minutes and seconds that the UPS should wait between receiving the
|
||
|
shutdown command and actually shutting off. The other argument should
|
||
|
be set to the character 'n' only when the minutes value should be
|
||
|
skipped and not sent to the UPS. The default is type-dependent and is
|
||
|
given below. The braces and commas are mandatory. Note that there should
|
||
|
be no whitespace characters.
|
||
|
|
||
|
*voltage*={'coefficient1','coefficient2','coefficient3','coefficient4'}::
|
||
|
(Only for types KP625AP, Trust, Egys, BNT-other.)
|
||
|
A quad that is used convert the raw data to a human-readable voltage
|
||
|
reading. The default is type-dependent and is given below. Do note that
|
||
|
the braces and commas are mandatory, as well as the lack of whitespace
|
||
|
characters.
|
||
|
|
||
|
*frequency*={'coefficient1','coefficient2'}::
|
||
|
(Only for types KP625AP, Trust, Egys.)
|
||
|
A pair to convert the raw data to a human-readable frequency reading. The
|
||
|
default is type-dependent and is given below. Do note that the braces
|
||
|
and commas are mandatory as well, as the lack of whitespace characters.
|
||
|
|
||
|
*batteryPercentage*={'coefficient1','coefficient2','coefficient3','coefficient4','coefficient5'}::
|
||
|
(Only for KP625AP, Trust, Egys, BNT-other.)
|
||
|
A 5 tuple to convert the raw data to a human-readable battery percentage
|
||
|
reading. The default is type-dependent and is given below. Do note that
|
||
|
the braces and commas are mandatory, as the lack of white space
|
||
|
characters.
|
||
|
|
||
|
*loadPercentage*={'coefficient1','coefficient2','coefficient3','coefficient4'}::
|
||
|
(Only for types KP625AP, Trust, Egys, BNT-other.)
|
||
|
A quad to convert the raw data to human readable load percentage
|
||
|
reading. The default is type-dependent and is given below. Do note that
|
||
|
the braces and commas are mandatory, as the lack of white space
|
||
|
characters.
|
||
|
|
||
|
*validationSequence*={{'index1','value1'},{'index2','value2'},{'index3','value3'}}::
|
||
|
(Only for types KP625AP, Trust, Egys, BNT-other.)
|
||
|
3 pairs to be used for validating the UPS by comparing bytes of the raw
|
||
|
data with constant values. The default is type-dependent and is given
|
||
|
below. The braces and commas are mandatory, as the lack of white space
|
||
|
characters.
|
||
|
|
||
|
DEFAULT VALUES FOR THE EXTRA ARGUMENTS
|
||
|
--------------------------------------
|
||
|
linevoltage = 230
|
||
|
manufacturer = PowerCom
|
||
|
modelname = Unknown
|
||
|
serialnumber = Unknown
|
||
|
type = Trust
|
||
|
|
||
|
The rest of the default values for the extra arguments are type-dependent:
|
||
|
|
||
|
Trust
|
||
|
~~~~~
|
||
|
numOfBytesFromUPS = 11
|
||
|
methodOfFlowControl = dtr0rts1
|
||
|
validationSequence = {{5,0},{7,0},{8,0}}
|
||
|
shutdownArguments = {{0,10},n}
|
||
|
frequency = {0.00020997,0.00020928}
|
||
|
loadPercentage = {6.1343,-0.3808,4.3110,0.1811}
|
||
|
batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}
|
||
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
||
|
|
||
|
KP625AP
|
||
|
~~~~~~~
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = dtr0rts1
|
||
|
validationSequence = {{5,0x80},{7,0},{8,0}}
|
||
|
shutdownArguments = {{0,10},n}
|
||
|
frequency = {0.00020997,0.00020928}
|
||
|
loadPercentage = {6.1343,-0.3808,4.3110,0.1811}
|
||
|
batteryPercentage = {5.0000,0.3268,-825.00,4.5639,-835.82}
|
||
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
||
|
|
||
|
|
||
|
Egys
|
||
|
~~~~
|
||
|
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = no_flow_control
|
||
|
validationSequence = {{5,0x80},{7,0},{8,0}}
|
||
|
shutdownArguments = {{0,10},n}
|
||
|
frequency = {0.00020997,0.00020928}
|
||
|
loadPercentage = {6.1343,-0.3808,1.3333,0.6667}
|
||
|
batteryPercentage = {5.0000,0.3268,-825.00,2.2105,-355.37}
|
||
|
voltage = {1.9216,-0.0977,0.9545,0.0000}
|
||
|
|
||
|
|
||
|
IMP
|
||
|
~~~
|
||
|
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = no_flow_control
|
||
|
validationSequence = {{5,0xFF},{7,0},{8,0}}
|
||
|
shutdownArguments = {{1,30},y}
|
||
|
|
||
|
|
||
|
KIN
|
||
|
~~~
|
||
|
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = no_flow_control
|
||
|
validationSequence = {{11,0x4b},{8,0},{8,0}}
|
||
|
shutdownArguments = {{1,30},y}
|
||
|
|
||
|
|
||
|
BNT
|
||
|
~~~
|
||
|
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = no_flow_control
|
||
|
validationSequence = {{11,0x42},{8,0},{8,0}}
|
||
|
shutdownArguments = {{1,30},y}
|
||
|
|
||
|
|
||
|
BNT-other
|
||
|
~~~~~~~~~
|
||
|
|
||
|
numOfBytesFromUPS = 16
|
||
|
methodOfFlowControl = no_flow_control
|
||
|
validationSequence = {{8,0},{8,0},{8,0}}
|
||
|
shutdownArguments = {{1,30},y}
|
||
|
loadPercentage = {1.4474,0.0,0.8594,0.0}
|
||
|
batteryPercentage = {5.0000,0.3268,-825.00,0.46511,0}
|
||
|
voltage = {1.9216,-0.0977,0.82857,0.0000}
|
||
|
|
||
|
AUTHOR
|
||
|
------
|
||
|
Peter Bieringer <pb@bieringer.de>,
|
||
|
Alexey Sidorov <alexsid@altlinux.org>
|
||
|
|
||
|
SEE ALSO
|
||
|
--------
|
||
|
|
||
|
The core driver:
|
||
|
~~~~~~~~~~~~~~~~
|
||
|
linkman:nutupsdrv[8]
|
||
|
|
||
|
Internet resources:
|
||
|
~~~~~~~~~~~~~~~~~~~
|
||
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|