upsset.cgi \- Web\-based UPS administration program
.SH"SYNOPSIS"
.sp
\fBupsset\&.cgi\fR
.ifn\{\
.sp
.\}
.RS4
.it1an-trap
.nran-no-space-flag1
.nran-break-flag1
.br
.ps+1
\fBNote\fR
.ps-1
.br
.sp
As a CGI program, this should be invoked through your web server\&. If you run it from the command line, it will sit there until you give it input resembling a POST request\&.
.sp.5v
.RE
.SH"DESCRIPTION"
.sp
\fBupsset\&.cgi\fR lets you access many administrative functions within the UPS software from your web browser\&. You can change settings and invoke instant commands where available\&.
.SH"CHANGING SETTINGS"
.sp
Some UPS hardware allows you to change certain variables to other values\&. To see what\(cqs available, pick a UPS from the chooser and select "settings", then select "View" to update the page\&.
.sp
You should see a list of items with the descriptions on the left side and the possible options or input spaces on the right\&. After changing something, be sure to "Save changes" to update the values in your UPS\&.
.sp
If your UPS doesn\(cqt support any read/write variables, there will be nothing to do on this page\&.
.sp
Setting values in read/write variables can also be done from the command line with \fBupsrw\fR(8)\&.
.SH"INSTANT COMMANDS"
.sp
Some UPS hardware also has provisions for performing certain actions at the user\(cqs command\&. These include battery tests, battery calibration, front panel tests (beep!) and more\&. To access this section, do as above, but pick "Commands" as the function\&.
.sp
If your UPS supports any instant commands, they will be listed in a chooser widget\&. Pick the one you like and "Issue command" to make it happen\&.
.ifn\{\
.sp
.\}
.RS4
.it1an-trap
.nran-no-space-flag1
.nran-break-flag1
.br
.ps+1
\fBNote\fR
.ps-1
.br
.sp
some dangerous commands like "Turn off load" may not happen right away\&. This is a feature, not a bug\&.
.sp.5v
.RE
.sp
The apcsmart driver and some others require that you send this command twice within a short window in order to make it happen\&. This is to keep you from accidentally killing your systems by picking the wrong one\&.
.sp
To actually turn off the load, you have to send the command once, then send it again after 3 seconds elapse but before 15 seconds pass\&. If you do it too quickly or slowly, you have to wait at least 3 seconds but not 15 seconds again\&.
.sp
You can also invoke instant commands from the command line with \fBupscmd\fR(8)\&.
.SH"ACCESS CONTROL"
.sp
upsset will only talk to \fBupsd\fR(8) servers that have been defined in your \fBhosts.conf\fR(8)\&. If it complains about "Access to that host is not authorized", check your hosts\&.conf first\&.
.SH"SECURITY"
.sp
upsset will not run until you convince it that your CGI directory has been secured\&. This is due to the possibility of someone using upsset to try password combinations against your \fBupsd\fR(8) server\&.
.sp
See the example upsset\&.conf file for more information on how you do this\&. The short explanation is\(emif you can\(cqt lock it down, don\(cqt try to run it\&.