nut/docs/man/oneac.txt

132 lines
3 KiB
Text
Raw Permalink Normal View History

2011-01-26 09:35:08 +00:00
ONEAC(8)
========
NAME
----
oneac - Driver for Oneac UPS equipment
NOTE
----
This man page only documents the hardware-specific features of the
2010-03-25 23:20:59 +00:00
oneac driver. For information about the core driver, see
2011-01-26 09:35:08 +00:00
linkman:nutupsdrv[8].
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
SUPPORTED HARDWARE
------------------
2012-06-01 13:55:19 +00:00
This driver supports various Oneac UPS families:
- EG (late 80s, early 90s, plug-in serial interface card)
- ON (early and mid-90s, plug-in serial interface card)
- OZ (mid-90s on, DB-25 std., interface slot)
- OB (early 2000's on, big cabinet, DB-25 std., interface slot)
If your UPS is equipped with the Basic Interface card, use the
linkman:genericups[8] driver.
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
EXTRA ARGUMENTS
---------------
2022-06-29 10:37:36 +00:00
2010-03-25 23:20:59 +00:00
This driver supports the following optional settings in the
2011-01-26 09:35:08 +00:00
linkman:ups.conf[5] file:
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
*testtime*='num'::
2010-03-25 23:20:59 +00:00
Change battery test time from the 2 minute default.
2012-06-01 13:55:19 +00:00
*offdelay*='num'::
Change shutdown delay time from 0 second default.
2011-01-26 09:35:08 +00:00
INSTANT COMMANDS
----------------
2022-06-29 10:37:36 +00:00
2010-03-25 23:20:59 +00:00
This driver supports the following Instant Commands.
2012-06-01 13:55:19 +00:00
(See linkman:upscmd[8])
2010-03-25 23:20:59 +00:00
2012-06-01 13:55:19 +00:00
All UPS units
~~~~~~~~~~~~~
2010-03-25 23:20:59 +00:00
2012-06-01 13:55:19 +00:00
*shutdown.return*::
Turn off the load possibly after a delay and return when power is back.
2010-03-25 23:20:59 +00:00
2012-06-01 13:55:19 +00:00
*shutdown.stop*::
Stop a shutdown in progress.
*shutdown.reboot*::
Shut down the load briefly while rebooting the UPS.
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
*test.failure.start*::
2010-03-25 23:20:59 +00:00
Starts a 15 second long simulation of an input power
failure.
2012-06-01 13:55:19 +00:00
*test.battery.start.quick*::
Start a "quick" battery test. The default time is 2 minutes. This
time can be set in the *ups.conf* file. See *testime* above.
*test.battery.stop*::
Stops a battery test that is in progress.
All ON UPS units
~~~~~~~~~~~~~~~~
*reset.input.minmax*::
Reset the minimum and maximum input line voltage values
seen since the last reset or power on.
Newer ON UPS units
~~~~~~~~~~~~~~~~~~
*test.panel.start*::
Start testing the UPS panel.
*test.battery.start.deep*::
Start a "deep" battery test. This test runs the UPS until the low
battery point and then returns to the AC line.
*reset.input.minmax*::
Reset the minimum and maximum input line voltage values
seen since the last reset or power on.
*beeper.enable*::
Enable UPS beeper/buzzer.
*beeper.disable*::
Disable UPS beeper/buzzer.
*beeper.mute*::
Mutes the UPS beeper/buzzer for the current alarm condition(s).
Writable Variables
------------------
2022-06-29 10:37:36 +00:00
2012-06-01 13:55:19 +00:00
See linkman:upsrw[8] to see what variables are writable for the UPS.
NOTE: If your UPS supports writing battery.runtime.low, the new set value
is to be entered in minutes (up to 99) but the reported value is reported
in seconds (set value * 60).
NOTE: If your UPS supports input.transfer.low and input.transfer.high,
2022-06-29 10:37:36 +00:00
those values are used to create an allowable output range. The UPS
will do what it can to keep the output voltage value within the
2012-06-01 13:55:19 +00:00
defined range (for example: tap change or switch to inverter).
2022-06-29 10:37:36 +00:00
AUTHORS
-------
* Bill Elliot <bill@wreassoc.com>
* Eric Lawson <elawson@inficad.com>
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
SEE ALSO
--------
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
The core driver:
~~~~~~~~~~~~~~~~
2022-06-29 10:37:36 +00:00
2011-01-26 09:35:08 +00:00
linkman:nutupsdrv[8]
2010-03-25 23:20:59 +00:00
2011-01-26 09:35:08 +00:00
Internet resources:
~~~~~~~~~~~~~~~~~~~
2022-06-29 10:37:36 +00:00
2010-03-25 23:20:59 +00:00
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/