BESTUPS(8)
|
|
|
|
==========
|
|
|
|
|
|
|
|
NAME
|
|
|
|
----
|
|
|
|
|
|
|
|
bestups - Driver for Best Power / SOLA (Phoenixtec protocol) UPS equipment
|
|
|
|
|
|
|
|
NOTE
|
|
|
|
----
|
|
|
|
|
|
|
|
This man page only documents the hardware-specific features of the
|
2022-06-29 10:37:36 +00:00
|
|
|
bestups driver. For information about the core driver, see
|
2011-01-26 09:35:08 +00:00
|
|
|
linkman:nutupsdrv[8].
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2022-06-29 10:37:36 +00:00
|
|
|
NOTE
|
|
|
|
----
|
|
|
|
|
|
|
|
Please note that this driver is deprecated and will not receive
|
|
|
|
new development. If it works for managing your devices -- fine,
|
|
|
|
but if you are running it to try setting up a new device, please
|
|
|
|
consider the newer linkman:nutdrv_qx[8] instead, which should
|
|
|
|
handle all 'Q*' protocol variants for NUT.
|
|
|
|
|
|
|
|
Please do also report if your device works with this driver,
|
|
|
|
but linkman:nutdrv_qx[8] would not actually support it with any
|
|
|
|
subdriver!
|
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
SUPPORTED HARDWARE
|
|
|
|
------------------
|
2022-06-29 10:37:36 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
*bestups* was designed to monitor Best Power UPS hardware like the Fortress,
|
2010-03-25 23:20:59 +00:00
|
|
|
Fortress Telecom, Axxium Rackmount and Patriot Pro. It also recognizes
|
2022-06-29 10:37:36 +00:00
|
|
|
and supports SOLA units such as the 325, 520 and 620. In addition, the
|
2010-03-25 23:20:59 +00:00
|
|
|
Best 610 is supported using the `ID' option.
|
|
|
|
|
|
|
|
Other UPS hardware using the Phoenixtec protocol should also work, but
|
|
|
|
they will generate a warning since their battery information is not known.
|
|
|
|
|
|
|
|
This driver does not support some older Best/SOLA units.
|
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
EXTRA ARGUMENTS
|
|
|
|
---------------
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
This driver supports the following optional settings in the
|
2011-01-26 09:35:08 +00:00
|
|
|
linkman:ups.conf[5]:
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
*nombattvolt=*'num'::
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
Override the battery float voltage which is normally determined by
|
|
|
|
asking the hardware. This is useful if your UPS constantly reports
|
2011-01-26 09:35:08 +00:00
|
|
|
`battery.charge` values just below 100% even when it's completely charged.
|
|
|
|
+
|
|
|
|
If you have this problem, set this to whatever `battery.voltage` reports
|
2010-03-25 23:20:59 +00:00
|
|
|
when the UPS is known to be completely charged with a good battery.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
|
|
|
The author's Best Fortress 750 uses `nombattvolt=27.4`.
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
*battvoltmult=*'num'::
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
Multiply the reported battery voltage by this number. Some devices
|
|
|
|
report only a fraction of the total battery voltage.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2010-03-25 23:20:59 +00:00
|
|
|
For example, the SOLA 610 700VA UPS (with a 24V battery) reports the
|
|
|
|
single cell voltage (about 2.27V when fully charged). In this particular
|
2011-01-26 09:35:08 +00:00
|
|
|
case you can set `battvoltmult = 12` in linkman:ups.conf[8] to fix this.
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
*ID=*'string'::
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
Set the Identification response string. This should only be used
|
2022-06-29 10:37:36 +00:00
|
|
|
with hardware that supports the Phoenixtec protocol status inquiry
|
|
|
|
commands, but not the "ID" command, such as the Best/SOLA 610. Format
|
2010-03-25 23:20:59 +00:00
|
|
|
of the ID string is: AAA,BBBB,CCC,DDD,EE.E,FF.F
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2010-03-25 23:20:59 +00:00
|
|
|
AAA is the three-character identification for the UPS model.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
BBBB is the output power in VA (volt amperes). B is an integer number
|
2010-03-25 23:20:59 +00:00
|
|
|
ranging from 0 to 9.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
CCC is the Nominal Input Voltage. C is an integer number ranging from 0
|
2010-03-25 23:20:59 +00:00
|
|
|
to 9. The unit is Volts AC.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
DDD is the Nominal Output Voltage. D is an integer number ranging from 0
|
2010-03-25 23:20:59 +00:00
|
|
|
to 9. The unit is Volts AC.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
EE.E is the Battery Voltage that will cause the UPS to shut itself off.
|
|
|
|
E is an integer number ranging from 0 to 9. Then unit is Volts DC and a
|
2010-03-25 23:20:59 +00:00
|
|
|
decimal point is present.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
FF.F or FFF.F is the Battery Voltage at full charge. F is an integer
|
|
|
|
number ranging from 0 to 9. Then unit is Volts DC. Typically, for 700VA,
|
|
|
|
1KVA and 1.5KVA units, the format is FF.F. For 2KVA and 3KVA units, the
|
2010-03-25 23:20:59 +00:00
|
|
|
format is FFF.F.
|
2011-01-26 09:35:08 +00:00
|
|
|
+
|
2022-06-29 10:37:36 +00:00
|
|
|
Example: a Best 610 1.5KVA unit would use the string
|
2010-03-25 23:20:59 +00:00
|
|
|
"610,1500,120,120,10.0,48.0".
|
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
BUGS
|
|
|
|
----
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
The battery charge percentage value (in `battery.charge`) is derived from
|
2010-03-25 23:20:59 +00:00
|
|
|
the voltage data that the UPS returns, since the UPS doesn't return that
|
|
|
|
value directly. On some hardware, the charge will remain at 100% for a
|
|
|
|
long time and then drops quickly shortly before the battery runs out.
|
2011-01-26 09:35:08 +00:00
|
|
|
You can confirm from the `battery.voltage` readings that this is a problem
|
2022-06-29 10:37:36 +00:00
|
|
|
with the UPS and not this driver.
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
Similarly, the float from the charger in some models forces the battery
|
2022-06-29 10:37:36 +00:00
|
|
|
charge percentage back up to 100% immediately after the UPS goes back
|
2011-01-26 09:35:08 +00:00
|
|
|
on-line, so you can't tell when it is really recharged.
|
2010-03-25 23:20:59 +00:00
|
|
|
|
|
|
|
Finally, some models give one value for the battery's nominal voltage and
|
|
|
|
yet actually have a nominal voltage slightly below that. This leads to
|
|
|
|
things such as the perpetual 98.7% charge on the author's Fortress 750,
|
2022-06-29 10:37:36 +00:00
|
|
|
even when it's been charging for weeks. You can use `nombattvolt=` in
|
2011-01-26 09:35:08 +00:00
|
|
|
linkman:ups.conf[8] to fix this.
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2022-06-29 10:37:36 +00:00
|
|
|
AUTHORS
|
|
|
|
-------
|
|
|
|
|
|
|
|
* Russell Kroll
|
|
|
|
* Jason White
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
SEE ALSO
|
|
|
|
--------
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
The core driver:
|
|
|
|
~~~~~~~~~~~~~~~~
|
2022-06-29 10:37:36 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
linkman:nutupsdrv[8]
|
2010-03-25 23:20:59 +00:00
|
|
|
|
2011-01-26 09:35:08 +00:00
|
|
|
Internet resources:
|
|
|
|
~~~~~~~~~~~~~~~~~~~
|
2022-06-29 10:37:36 +00:00
|
|
|
|
2010-03-25 23:20:59 +00:00
|
|
|
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/
|